Note that the Alarm Indicator is positioned in the upper left hand corner
of the touch screen by default. The symbol can be moved to any
location on the screen by clicking on it, holding and moving it. The
Alarm Indicator disappears when all alarms are both acknowledged and
have returned to inactive status. Mark an Alarm and Acknowledge
Selected or Acknowledge All Alarms using the Alarm Menu. ALARM LOG
and alarm indicator
The Alarm Indicator disappears when all alarms are both acknowledged and have returned to inactive
status. Mark an Alarm and Acknowledge Selected or Acknowledge All Alarms using the Alarm Menu.
The alarms that must be acknowledged are:
Emergency stop
Cylinder is not rotating according to settings
Cylinder motor - fuse tripped
Cylinder motor - inverter fault
Fan motor – fuse tripped
Fan motor – inverter fault
In-conveyor has automatically reversed 2 times but is still unable to run
Infeed motor - fuse tripped
Infeed motor – inverter fault
Heater – fuse tripped
10.3
ALARM – CYLINDER IS NOT ROTATING ACCORDING TO SETTINGS
More than 10 hours have elapsed since the cylinder rotated:
- Inspect sprocket and chain for wear. The chain wheel and chain are
easily accessible behind inspection door number 2 on the hood.
- Rotate the cylinder using the manual rotation menu
- Check the function of the limit switch on the cylinder
If this alarm shows up repeatedly - contact service personnel
Note that this ALARM needs to be acknowledged in the ALARM list in order to turn off the Alarm
Indicator which is visible in the left hand upper corner on all screens.
Use the ALARM button to go to alarm log menu.
10.3.1
INDUCTIVE SENSOR (110121) FOR INSPECTION DOOR POSITION
Normally, the cylinder rotates one full revolution, always returning the inspection doors to the same
position which is controlled by the inductive sensor for the inspection door position (110121).
This alarm is triggered by the touch screen plc when the cylinder steel target (11 below) has not
passed the inductive sensor (12). Therefore, check the function of this sensor, both electrics and
mechanics.