SurgeX UPS-1000-Li-2 Скачать руководство пользователя страница 9

    UPS-1000-Li-2                         User Manual

 

 

 

 

 

 

 

       

   © 2019 AMETEK Electronic Systems Protection   /   Technical Support: 1-800-645-9721   /   surgex.com                       

  6 

 

 

 
To clear the overload alarm when the UPS-1000-Li-2 has shutdown requires that the UPS-1000-Li-2 perform a battery test.  First 
remove part of the load, then turn the UPS-1000-Li-2 on, the Overload icon and the alarm will be on.  Second either use the Test 
Button or unplug the input power cord to perform the battery test.

 

 
UPS-1000-Li-2 FAULT

 

When the UPS-1000-Li-2 detects an internal fault, the Fault icon will illuminated and an error code will be displayed on the LCD 
screen,  the alarm will sound continuously and the output will be turned off.  The fault condition, in some instances, may be cleared 
by turning the UPS-1000-Li-2 off and then on.  If the fault condition does not clear the UPS-1000-Li-2 must be sent in for service. 
See the Troubleshooting section. 

 

TROUBLESHOOTING 

 

Symptom / Error Code 

Cause / What To Do 

Unit will not turn on. 

Press the On/Off/Test button and release after one beep. 

Unit operates in battery mode only, 
even though there is AC present. 

Reset  the  input  circuit  breaker  by  pressing  the 
plunger back in. If the input circuit breaker trips after restart, reduce the load on the UPS. 

The AC Normal icon is blinking 
and the alarm is silent. 

The unit is in Boost mode. It is performing its in- tended  function. 

The unit does not provide 
expected runtime. 

Charge the batteries for 8-hours and retest. If the runtime is still less than expected, the 
batteries may need to be replaced. 

The AC normal icon is 
illuminated, but there is no output. 

Disconnect the computer cable from the unit, press the On button. If UPS works normally, 
the software has control of the UPS. 

Fault icon is illuminated and a 
constant alarm. 

The unit has an internal problem. Call for service. 

Error Code: E01. UPS 
is shutdown. 

The unit has detected a short-circuit on its output. Check the attached load. 

Error Code: E02. Overload icon 
is illumi- nated and a constant 
alarm. 

Check the specifications and remove part of the load. If the unit shuts down because of an 
Overload, the UPS must perform an Inverter function or a Self Test to clear the Overload 
Alarm. 

Error Code: E03. Over 
Temperature Shut- down. 

The internal or ambient temperature has exceeded the safe operating range for the unit. 
Check the specifications. 

Error Code: E04: In- 
verter/Output Failure Shutdown. 

The unit has an internal fault. Call for service. 

Error Code: E05. Charger 
Failure Warning. 

The charger has failed, call for service. 

Error Code: E06. Weak/Bad 
Battery icon is illuminated. 

Check the battery connections, charge the batteries 
for 8-hours and retest, or replace the batteries. 

Error Code: E07. Low 
Battery Warning. 

The 

unit’

s battery reserve is low.  This condition will continue until AC returns or the UPS shuts 

down from battery exhaustion. 

Error Code: E08. SWF 
icon is illuminated.

 

Have a qualified electrician correct the service wiring. 

 

 
 

Содержание UPS-1000-Li-2

Страница 1: ...UPS 1000 Li 2 UserManual UPS 1000 Li 2 User Manual 2019 AMETEK Electronic Systms Protecion Technical Support 1 800 645 9721 surgex com UM UPS 1000 Li 2 Rev A...

Страница 2: ...UPS 1000 Li 2 UserManual 2018 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com...

Страница 3: ...IES 3 3 CONNECTING THE UPS 1000 LI 2 TO AN AC SOURCE 3 4 CHECKING THE SITE WIRING FAULT 3 5 CHARGING THE BATTERY 3 6 CONNECTING YOUR EQUIPMENT 4 7 USB COMMUNICATION PORT CONNECTION OPTIONAL 4 8 POWER...

Страница 4: ...or adapter plugs or surge protectors CAUTION To reduce the risk of fire connect only to a utility powered circuit provided with 20 amperes maximum branch circuit over current protection in accordance...

Страница 5: ...e as 20 40 60 80 100 When the amount of load attached to the UPS 1000 Li 2 exceeds 110 of its power rating the Overload icon will flash Off and On all of the LEDs in the Load Level Bar Graph will be i...

Страница 6: ...llation 3 Connecting the UPS 1000 Li 2 to an AC Source CAUTION To reduce the risk of fire connect only to a utility powered circuit provided with 20 amperes maximum branch circuit over current protect...

Страница 7: ...onfigured ConnectingtotheCommunications Port is optional The UPS 1000 Li 2 works properly without this connection 8 POWER MONITORING SOFTWARE This productsupports Power Monitoring Software Please go t...

Страница 8: ...orma self test onstart up 7 Alarms ONBATTERY When the UPS 1000 Li 2 is operating on the batteries the AC normal icon will extinguish the On Battery icon will illuminate the LCD will display the estima...

Страница 9: ...nction The unit does not provide expectedruntime Charge the batteries for 8 hours and retest If the runtime is still less than expected the batteries may need to be replaced The AC normal icon is illu...

Страница 10: ...properly The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly Refer to local codes for proper disposal requirements CAUTION The battery system...

Страница 11: ...2 3 Unplug the UPS 1000 Li 2 sAC power cord from theAC wall outlet 4 Unplug the equipment from the output receptacles of the UPS 1000 Li 2 5 Unplug the computer interface cable from the rear panel of...

Страница 12: ...wer at 136V or lower InputProtection ResettableCircuitBreaker OUTPUTNON BATTERYOPERATION VoltageRange 104 140VAC VoltageRegulation 120VAC 13 3 16 7 FrequencyRange 60Hz 54 66Hz Efficiency LineMode 96 F...

Страница 13: ...life SURGE PROTECTIONAND FILTERING Voltage Protection Rating VPR 330V Line Neutral NoiseFilter Normal Mode Battery 30dB 130kHz 50MHz Surge Only 30dB 120kHz 50MHz Common Mode Battery 10dB 300kHz 50MHz...

Отзывы: