5.

 

LCD Screen 

 

The LCD provides the user with a variety of useful information.  The LCD has a real- time meter to display, in numeric fashion, the 
following data: 

 

Input Voltage and Frequency 

 

Output Voltage and Frequency 

 

Connected Load KVA and KW 

 

Estimated runtime in the AC and DC mode Connected Load Capacity Bar 
Graph Battery Capacity Bar Graph 

 

The LCD will include dedicated icons for the following information:  

 

AC Normal / AVR Mode (Boost: The AC Normal icon will flash) On Battery 

 

Weak/Bad Battery 

 

UPS-1000-Li-2 Fault 

 

Site Wiring Fault 

 

Overload 

 

The LCD backlight  will turn on when the UPS-1000-Li-2 is turned on. After approximately 
20-seconds the backlight will turn off to conserve energy.  When an event (alarm) occurs, such as going to the battery mode, 
the backlight will turn on for approximately 20-seconds to alert the user that an event has occurred and then the back- light will 
turn off.  While the Scroll button is in use the backlight will remain on.  Approximately 20-seconds after the Scroll button has 
stopped being used the back- light will turn off to conserve energy. 
 

6.

 

Self-Test

 

The self-test feature is useful to verify the correct operation of the UPS-1000-Li-2 and the condition of the batteries.  The start-
up and user invoked test are used to measure the 

battery’

s capability to support the connected load.  If the UPS-1000-Li-2 fails 

one of these  tests,  one  of  the  icons  or  the  information  displayed  on  the  LCD  will  remain  illuminated indicating the type of 
problem. 

NOTE: 

The UPS-1000-Li-2 will automatically perform a self-test on start-up. 

 

7.

 

Alarms

 

 

ON BATTERY

 

When the UPS-1000-Li-2 is operating on the batteries, the AC normal icon will extinguish, the On-Battery icon will illuminate, the 
LCD will display the estimated runtime remaining and the alarm will sound one beep every 10 seconds.  Once the UPS-1000-
Li-2 returns to the normal AC mode, the alarm will stop, the On-Battery icon will extinguish and the AC normal icon will illuminate. 

 

LOW BATTERY WARNING

 

When the batteries reach the predetermined level, the alarm will sound two beeps every five seconds, the Battery Bar Graph 
will display the remaining battery capacity and the LCD will display error code E07.  This information is to inform the user that 
there is approximately two minutes of runtime remaining before the UPS-1000-Li-2 shuts down.  This condition will continue until 
either AC returns or the UPS-1000-Li-2

’s

 self-protection circuit shuts the UPS-1000-Li-2 down to protect the battery from over 

discharging. 

WEAK/BAD BATTERY

 

The UPS-1000-Li-2 automatically tests the 

battery’

s condition.  If the battery is weak, bad or disconnected, the Weak/Bad Battery 

icon will illuminate and the Battery Capacity Bar Graph will turn off and the alarm will sound three beeps every five minutes until 
the battery is either reconnected or replaced.  This alarm will be repeated until the batteries pass a self-test.  It is recommended 
that  the  UPS-1000-Li-2  be  allowed  to  charge  overnight  before  performing  a  battery  test  to  confirm  a  Weak/Bad  Battery 
condition. 

 

OVERLOAD

 

When the amount of load attached to the UPS-1000-Li-2 exceeds its power rating, the Overload icon will illuminate and the 
alarm will sound continuously (AC and Battery modes).  This alarm will remain on until the excess load is removed or the UPS-
1000-Li-2

’s

 self-protection circuit shuts the UPS-1000-Li-2 down. 

 

 

 

Содержание UPS-1000-Li-2

Страница 1: ...UPS 1000 Li 2 UserManual UPS 1000 Li 2 User Manual 2019 AMETEK Electronic Systms Protecion Technical Support 1 800 645 9721 surgex com UM UPS 1000 Li 2 Rev A...

Страница 2: ...UPS 1000 Li 2 UserManual 2018 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com...

Страница 3: ...IES 3 3 CONNECTING THE UPS 1000 LI 2 TO AN AC SOURCE 3 4 CHECKING THE SITE WIRING FAULT 3 5 CHARGING THE BATTERY 3 6 CONNECTING YOUR EQUIPMENT 4 7 USB COMMUNICATION PORT CONNECTION OPTIONAL 4 8 POWER...

Страница 4: ...or adapter plugs or surge protectors CAUTION To reduce the risk of fire connect only to a utility powered circuit provided with 20 amperes maximum branch circuit over current protection in accordance...

Страница 5: ...e as 20 40 60 80 100 When the amount of load attached to the UPS 1000 Li 2 exceeds 110 of its power rating the Overload icon will flash Off and On all of the LEDs in the Load Level Bar Graph will be i...

Страница 6: ...llation 3 Connecting the UPS 1000 Li 2 to an AC Source CAUTION To reduce the risk of fire connect only to a utility powered circuit provided with 20 amperes maximum branch circuit over current protect...

Страница 7: ...onfigured ConnectingtotheCommunications Port is optional The UPS 1000 Li 2 works properly without this connection 8 POWER MONITORING SOFTWARE This productsupports Power Monitoring Software Please go t...

Страница 8: ...orma self test onstart up 7 Alarms ONBATTERY When the UPS 1000 Li 2 is operating on the batteries the AC normal icon will extinguish the On Battery icon will illuminate the LCD will display the estima...

Страница 9: ...nction The unit does not provide expectedruntime Charge the batteries for 8 hours and retest If the runtime is still less than expected the batteries may need to be replaced The AC normal icon is illu...

Страница 10: ...properly The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly Refer to local codes for proper disposal requirements CAUTION The battery system...

Страница 11: ...2 3 Unplug the UPS 1000 Li 2 sAC power cord from theAC wall outlet 4 Unplug the equipment from the output receptacles of the UPS 1000 Li 2 5 Unplug the computer interface cable from the rear panel of...

Страница 12: ...wer at 136V or lower InputProtection ResettableCircuitBreaker OUTPUTNON BATTERYOPERATION VoltageRange 104 140VAC VoltageRegulation 120VAC 13 3 16 7 FrequencyRange 60Hz 54 66Hz Efficiency LineMode 96 F...

Страница 13: ...life SURGE PROTECTIONAND FILTERING Voltage Protection Rating VPR 330V Line Neutral NoiseFilter Normal Mode Battery 30dB 130kHz 50MHz Surge Only 30dB 120kHz 50MHz Common Mode Battery 10dB 300kHz 50MHz...

Отзывы: