Chapter 3: Maintenance and Component Installation
Figure 3-12. Securing the HDD Bracket to the Chassis Floor
System Fans
The SC514 chassis includes four heavy-duty fans for system cooling plus the option to add
two additional fans.
Replacing a System Fan
1. If necessary, open the chassis cover while the power is running to determine which fan
requires changing. (Do not run the server for an extended time with the chassis open.)
2. Power down the system as described in section 3-1.
3. Remove the cables of both the failed fan and the other fan sharing the same tray (since
two fans occupy one housing).
4. Lift the fan housing with the two fans attached up and out of the chassis. Remove the
failed fan by gently pulling it out of the housing.
5. Place the new fan into the vacant space in the housing. Make sure that the arrows on
the sides of the fan (indicating air direction) point in the same direction as the arrows on
the other fans.
6. Plug the fan cable into the connector on the serverboard.
Figure 3-11. Installing Hard Drives into the Bracket
3.4 Chassis Components
Hard Drives
The 1019S-M2 supports two fixed 2.5" hard disk drives with the use of a hard drive bracket
(included with the system).
Installing Hard Disk Drives
1. Identify the HDD bracket and secure the drive(s) to the bracket. (Figure 3-11).
2.
Secure the HDD bracket to the chassis floor. (Figure 3-12).
3. Connect the drive cabling.
Hard Drive
Bracket
Note:
Enterprise level hard disk drives are recommended for use in Supermicro chassis and
servers. For information on recommended HDDs, visit the Supermicro website at
supermicro.com/products/nfo/files/storage/SBB-HDDCompList.pdf