Chapter 2: Rack Installation

Chapter 2  

 

Rack Installation

This chapter provides instructions for mounting your chassis in a rack.

2-1  Preparing for Setup

The box in which your system was shipped should include two sets of rail 

assemblies,  two  rail  mounting  brackets  and  the  mounting  screws  to  mount  the 
system into the rack. Please read this chapter in its entirety before beginning the 

installation procedure.

Choosing a Setup Location

Decide on a suitable location for the rack unit that will hold your system. It should 

be a clean, dust-free area that is well ventilated. Avoid areas where heat, electrical 

noise and electromagnetic fields are generated. A nearby grounded power outlet. 

is required 

• 

Leave at least 25 inches clearance in front of the rack to open the front door 

completely.

• 

Leave approximately 30 inches of clearance in the back of the rack to allow for 
sufficient airflow and access for servicing.

• 

It should be a restricted access location, such as a dedicated equipment room 
or a service closet.

Содержание SUPERSERVER 1018R-WR

Страница 1: ...SUPERSERVER 1018R WR USER S MANUAL 1 0...

Страница 2: ...cense IN NO EVENT WILL SUPERMICRO BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL SPECULATIVE OR CONSEQUENTIAL DAMAGES ARISING FROM THE USE OR INABILITY TO USE THIS PRODUCT OR DOCUMENTATION EVEN IF A...

Страница 3: ...g uring the motherboard Chapter 6 Advanced Chassis Setup Refer to Chapter 6 for detailed information on the SC514 R407W server chassis You should follow the procedures given in this chapter when insta...

Страница 4: ...ii SUPERSERVER 1018R WR User s Manual Overheat Temperature Setting 3 3 Responses 3 3 3 4 Power Supply LEDs 3 4 Chapter 4 Standardized Warning Statements for AC Systems 4 1 About Standardized Warning S...

Страница 5: ...the Chassis Cover 6 3 6 4 Installing Hard Drives 6 4 6 4 System Fans 6 6 6 5 Installing Expansion Cards 6 8 6 7 Power Supply 6 10 Chapter 7 BIOS 7 1 Introduction 7 1 Starting BIOS Setup Utility 7 1 Ho...

Страница 6: ...rotating fans FAN 0156L4 One air shroud MCP 310 19007 0N Dual 2 5 fixed HDD bracket MCP 220 51401 0N Two riser cards RSC R1UW 2E16 RSC R1UW E8R Rail mounting sets MCP 290 00102 0N and MCP 290 00108 0N...

Страница 7: ...two SATA DOM ports are also included on the motherboard Rear I O Ports Ports on the I O backplane include a COM port a VGA port two USB 3 0 ports two USB 2 0 ports two gigabit Ethernet ports and one...

Страница 8: ...micro nl Customer Support Web Site www supermicro nl Asia Pacific Address Super Micro Computer Inc 3F No 150 Jian 1st Rd Zhonghe Dist New Taipei City 235 Taiwan R O C Tel 886 2 8226 3990 Fax 886 2 822...

Страница 9: ...1 6 SUPERSERVER 1018R WR User s Manual Notes...

Страница 10: ...cedure Choosing a Setup Location Decide on a suitable location for the rack unit that will hold your system It should be a clean dust free area that is well ventilated Avoid areas where heat electrica...

Страница 11: ...ains stable The following guidelines are provided to ensure your safety This unit should be mounted at the bottom of the rack if it is the only unit in the rack When mounting this unit in a partially...

Страница 12: ...e outer rail 1 A 1 B Round Hole Bracket with Square Pegs 2 3 Installing the System into a Rack This section provides information on installing the chassis into a rack unit with the rails provided Ther...

Страница 13: ...a bracket with square pegs to fit into your rack holes If you have an older rack with round holes these brackets must be removed and you must use screws to secure the rail to the rack Outer Rail Inst...

Страница 14: ...ger chassis should be positioned to balance the weight between front and back If a bezel is included on your server remove it Then attach the two front brackets to each side of the chassis then the tw...

Страница 15: ...3 System Interface Chapter 3 System Interface 3 1 Overview The control panel on the front that includes power buttons and status LEDs There are also status lights on the power supplies Figure 3 1 Con...

Страница 16: ...he server in a rack mount environment Blinking blue Remote UID is on Use this function to identify the server from a remote location 3 2 Control Panel Buttons The chassis includes two push buttons Pow...

Страница 17: ...r supply is on Solid Amber When illuminated indicates the power supply is plugged in and turned off or the system is off but in an abnormal state Blinking Amber When blinking this system power supply...

Страница 18: ...nt for assistance Only certified technicians should attempt to install or configure components Read this appendix in its entirety before installing or configuring components in the Supermicro chassis...

Страница 19: ...rtado de traducciones que acompa a a este dispositivo GUARDE ESTAS INSTRUCCIONES IMPORTANTES INFORMATIONS DE S CURIT Ce symbole d avertissement indique un danger Vous vous trouvez dans une situation p...

Страница 20: ...that the protective device is rated not greater than 250 V 20 A Waarschuwing Raadpleeg de installatie instructies voordat u het systeem op de voedingsbron aansluit 250 V 20 A Warnung Dieses Produkt i...

Страница 21: ...iliging overspanning van uw electrische installatie Controleer of het beveiligde aparaat niet groter gedimensioneerd is dan 220V 20A Advertencia El sistema debe ser disconnected de todas las fuentes d...

Страница 22: ...onfier l installation le remplacement et la maintenance de ces quipements des personnels qualifi s et exp riment s Waarschuwing Deze apparatuur mag alleen worden ge nstalleerd vervangen of hersteld do...

Страница 23: ...semblable ou quivalent recommand e par le fabricant Jeter les piles usag es conform ment aux instructions du fabricant Advertencia Existe peligro de explosi n si la bater a se reemplaza de manera inco...

Страница 24: ...Warnung Wenn das System in Betrieb ist treten auf der R ckwandplatine gef hrliche Spannungen oder Energien auf Vorsicht bei der Wartung Advertencia Cuando el sistema est en funcionamiento el voltaje d...

Страница 25: ...oduct Disposal Warning Ultimate disposal of this product should be handled according to all national laws and regulations Backplane Waarschuwing Een gevaarlijke spanning of energie is aanwezig op de b...

Страница 26: ...using Hot Swap Fan Warning Warnung Die L fter drehen sich u U noch wenn die L fterbaugruppe aus dem Chassis genommen wird Halten Sie Finger Schraubendreher und andere Gegenst nde von den ffnungen des...

Страница 27: ...lfunktion oder ein Brand entstehen Elektrische Ger te und Material Safety Law verbietet die Verwendung von UL oder CSA zertifizierte Kabel UL oder CSA auf der Code f r alle anderen elektrischen Ger te...

Страница 28: ...4 20 SUPERSERVER 1018R WR User s Manual Notes...

Страница 29: ...e hand under the center of the board to support it when handling The following measures are generally sufficient to protect your equipment from electric static discharge Precautions Use a grounded wri...

Страница 30: ...is a 8 pin 12V processor power con nector JPWR1 that must be connected to your power supply See Section 5 9 for power connector pin definitions Connecting the Control Panel JF1 contains header pins f...

Страница 31: ...contact your retailer immediately Refer to the Supermicro web site for updates on CPU support OPEN1st WARNING OPEN1st WARNING Press down on the lever labeled Close 1st Pull lever away from the socket...

Страница 32: ...sink on top of the CPU so that the four mounting holes are aligned with those on the serverboard and the heatsink bracket underneath 3 Screw in two diagonal screws i e the 1 and the 2 screws until jus...

Страница 33: ...per Channel SPC and DIMMs per Channel DPC 2 Slots per Channel 1 DPC 2 DPC E5 2600 V3 E5 2600 V4 E5 2600 V3 E5 2600 V4 4 GB 8 GB 1 2 V 1 2 V 1 2 V 1 2 V RDIMM SRx4 8 GB 16 GB 2133 2400 1866 2133 RDIMM...

Страница 34: ...2 FAN1 LE1 LEDM1 JUIDB1 JIPMB1 SP1 J23 JBRSET1 JPL2 JPL3 JPG1 JI2C2 J29 JPL1 JI2C1 J30 JPF2 JPF1 JPME2 JVR1 JPB1 JBR1 JWD1 T SGPIO3 T SGPIO2 T SGPIO1 JTPM1 DM2 BT1 JSTBY1 JL1 JOH1 JD1 JF1 JPWR1 JPI2C1...

Страница 35: ...n Blinking BMC Normal Reset Button The Reset Button connection is located on pins 3 and 4 of JF1 and attaches to the reset switch on the computer chassis See the table on the right for pin definitions...

Страница 36: ...ate Definition Off Normal On Overheat Flashing 1 Hz Fan Fail Flashing 1 4 Hz Redundant Power Supply Fail Fan Headers There are six fan headers on the serverboard all of which are 4 pin fans Fan 1 2 Fa...

Страница 37: ...D can also be triggered via IPMI For more information please refer to the IPMI User s Guide posted on our website UID Switch Pin Definition 1 Ground 2 Ground 3 Button In 4 Button In UID LED Status Col...

Страница 38: ...nection on your system IPMB Header Pin Definitions Pin Definition 1 Data 2 Ground 3 Clock 4 No Connection Standby Power Header The 5V Standby Power header is lo cated at JSTBY1 See the table on the ri...

Страница 39: ...I2 C1 I2 C2 Use jumpers I2 C1 I2 C2 to enable PCI E SMB System Management Bus sup port to improve system management for the PCI E slots See the table on the right for jumper settings 5 10 Onboard Ind...

Страница 40: ...s easy identifica tion of a system unit that may be in need of service Note UID can also be triggered via IPMI on the motherboard For more information on IPMI please refer to the IPMI User s Guide pos...

Страница 41: ...fter installing each item you must re boot the system before moving on to the next item on the list The bottom icon with a CD on it allows you to view the entire contents Figure 5 7 Driver Tool Instal...

Страница 42: ...in any way a damaged battery may release hazardous materials into the environment Do not discard a used battery in the garbage or a public landfill Please comply with the regulations set up by your l...

Страница 43: ...nted circuit boards PCBs it is important to handle them very carefully The following measures are generally sufficient to protect your equipment from ESD damage Precautions Use a grounded wrist strap...

Страница 44: ...t out of the back of the power supply Remove the cords from both power supply modules 3 Disconnect the cords from the power strip or wall outlet 6 3 Removing the Chassis Cover You may need to remove t...

Страница 45: ...tify the HDD bracket and secure the drive s to the bracket Figure 6 3 2 Secure the HDD bracket to the chassis floor Figure 6 4 3 Connect the HDD cabling Figure 6 3 Installing Hard Drives into the Brac...

Страница 46: ...e the new fan into the vacant space in the housing Make sure that the arrows on the sides of the fan indicating air direction point in the same direction as the arrows on the other fans 6 Plug the fan...

Страница 47: ...ng only those screws inidcated by the screwdriver icon as illustrated in Figure 6 7 2 Lift the riser card bracket from the chassis 3 Install the riser card on the bracket using the two screws provided...

Страница 48: ...out powering down the system Replacement units can be ordered directly from Supermicro Changing a Redundant Power Supply 1 Press the release button on the failed power supply 2 Use the handle to gentl...

Страница 49: ...configured Options in blue can be configured by the user The right frame displays the key legend Above the key legend is an area reserved for a text message When an option is selected in the left fram...

Страница 50: ...e Setup Utility Normally the only visible Power On Self Test POST routine is the memory test As the memory is being tested press the Delete key to enter the main menu of the AMI BIOS setup utility Fro...

Страница 51: ...f the host adaptors will not capture Interrupt 19 immediately and allow the drives attached to these adaptors to function as bootable devices at bootup The options are Immediate and Postponed Re try B...

Страница 52: ...ate P0 lasts less than two seconds The options are Traditional and Power Optimized Execute Disable Bit Available if supported by the OS the CPU Set to Enabled for Execute Disable Bit support which wil...

Страница 53: ...the DMAR ACPI Tables This feature offers fully protected I O resource sharing across the Intel platforms providing the user with greater reliability security and availability in networking and data s...

Страница 54: ...with P0 being the state with the highest frequency clock speed and power consumption and P1 a step lower in performance than P0 with its frequency and voltage scaled back a notch The options are Betwe...

Страница 55: ...ble Relaxed Ordering Select Enable to enable Relaxed Ordering support which will allow certain trans actions to violate the strict ordering rules of PCI and to be completed prior to other transactions...

Страница 56: ...e and Disable Data Scrambling Select Enabled to enable data scrambling to enhance system performance and data integrity The options are Auto Disabled and Enabled Enable ADR Select Enabled for ADR Auto...

Страница 57: ...error is corrected and sent to the requestor the original source Memory is corrected as well Select Enable to use Demand Scrubbing for ECC memory correction The options are Enable and Disable Device...

Страница 58: ...r Management When this item is set to Enabled the SATA AHCI controller manages the power usage of the SATA link The controller will put the link in a low power mode during extended periods of I O inac...

Страница 59: ...te drive or a Hard Disk Drive The options are Hard Disk Drive and Solid State Drive sSATA Configuration When this submenu is selected the AMI BIOS automatically detects the presence of the SATA device...

Страница 60: ...initialization to the device The options are Enabled and Disabled Port 0 Port 3 sSATA Device Type Use this item to specify if the sSATA port specified by the user should be con nected to a Solid State...

Страница 61: ...Bytes 2048 Bytes and 4096 Bytes ASPM Support Use this item to set the Active State Power Management ASPM level for a PCI E device Select Auto for the system BIOS to automatically set the ASPM level ba...

Страница 62: ...00 to use the ASCII Character set Select VT100 to add color and function key support Select ANSI to use the Extended ASCII Char acter Set Select VT UTF8 to use UTF8 encoding to map Unicode characters...

Страница 63: ...The options are ANSI VT100 VT100 and VT UTF8 Bits Per second Use this feature to set the transmission speed for a serial port used in Console Redirection Make sure that the same speed is used in the...

Страница 64: ...to add color and function key support Select ANSI to use the extended ASCII character set Select VT UTF8 to use UTF8 encoding to map Unicode characters into one or more bytes The options are ANSI VT10...

Страница 65: ...ect Enabled to enable SMBIOS System Management BIOS Event Logging during system boot The options are Enabled and Disabled Runtime Error Logging Support Select Enabled to support Runtime Error Logging...

Страница 66: ...le event counter wait before generating a new event log Enter a number between 0 to 99 The default setting is 60 Note Please reboot the system for the changes to take effect View System Event Log This...

Страница 67: ...IP address for this computer If Static is selected you will need to know the IP address of this computer and enter it to the system manually in the field If DHCP is selected the BIOS will search for a...

Страница 68: ...ot Settings Use this feature to configure Boot Settings Setup Prompt Timeout Use this item to indicate the length of time the number of seconds for the BIOS to wait before rebooting the system when th...

Страница 69: ...delete 7 8 Save Exit Select the Save Exit tab from the BIOS setup screen to configure the settings below Discard Changes and Exit Select this option to quit the BIOS setup without making any permanen...

Страница 70: ...or future use Restore User Defaults To set this feature select Restore User Defaults from the Exit menu and press En ter Use this feature to retrieve user defined settings that were saved previously B...

Страница 71: ...a fatal error occurs you should consult with your system manufacturer for possible repairs These fatal errors are usually communicated through a series of audible beeps The numbers on the fatal error...

Страница 72: ...A 2 SUPERSERVER 1018R WR User s Manual Notes...

Страница 73: ...et BIOS 128 Mb AMI SPI Flash ROM Memory Capacity Eight DIMM sockets supporting up to 1 TB of ECC 3DS LRDIMM 512 GB of ECC LRDIMM or 256 GB of ECC RDIMM DDR4 2400 2133 1866 1600 memory Note see Section...

Страница 74: ...o 140 F Operating Relative Humidity 8 to 90 non condensing Non operating Relative Humidity 5 to 95 non condensing Regulatory Compliance Electromagnetic Emissions FCC Class A EN 55022 Class A EN 61000...

Страница 75: ...form be reasonably expected to result in significant injury or loss of life or catastrophic property damage Accordingly Supermicro dis claims any and all liability and should buyer use or sell such pr...

Отзывы: