7

 

Gas water heater 

   _________ Btu/Hr

 

Vent-free fireplace  +_

 _________ Btu/Hr

 Total 

= _________ Btu/Hr

4.  Compare the maximum Btu/Hr the space 

can support with the actual amount of Btu/

Hr used.

 

 _______ Btu/Hr (maximum the space can 

support) 

 

 _______ Btu/Hr (actual amount of Btu/Hr 

used)

 

Example:

  51,200  Btu/Hr  (maximum  the 

space can support) 

 

 

71,500 Btu/Hr (actual amount of 

Btu/Hr used)

The space in the example is a confined space 

because the actual Btu/Hr used is more than the 

maximum Btu/Hr the space can support. You 

must provide additional fresh air. Your options 

are as follows:

A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air From Inside Building

page 7.

B.  Vent room directly to the outdoors. See 

Ventilation Air From Outdoors

, page 7.

C.  Install a lower Btu/Hr fireplace, if lower Btu/

Hr size makes room unconfined. 

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support,

 

the space is 

an unconfined space. You will need no additional 

fresh air ventilation.

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus-

tion and ventilation air shall be 

provided by one of the methods 

described in the 

National Fuel 

Gas Code, ANSI Z223.1/NFPA 

54, 

the

 International Fuel Gas 

Code,

 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining 

unconfined  space.  When  ventilating  to  an 

adjoining unconfined space, you must provide 

two permanent openings: one within 12" of the 

ceiling and one within 12" of the floor on the 

40,000
31,500
71,500

AIR FOR COMBUSTION AND VENTILATION

Continued

Figure 2 - Ventilation Air from Inside 

Building

Or 

Remove 

Door into 
Adjoining 

Room, 
Option 

Ventilation Grills  

Into Adjoining Room, 

Option 2 

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12" 

12" 

Figure 3 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

wall connecting the two spaces (see options 

1 and 2, Figure 2). You can also remove door 

into adjoining room (see option 3, Figure 2). 

Follow the 

National Fuel Gas Code ANSI 

Z223.1/NFPA 54, Air for Combustion and 

Ventilation

  for  required  size  of  ventilation 

grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation 

grills or ducts. You must provide two perma-

nent openings: one within 12" of the ceiling 

and one within 12" of the floor. Connect these 

items directly to the outdoors or spaces open 

to the outdoors. These spaces include attics 

and crawl spaces. Follow the 

National Fuel 

Gas Code ANSI Z223.1/NFPA 54, Air for 

Combustion and Ventilation

 for required size 

of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings 

for inlet or outlet air into attic if attic has a 

thermostat-controlled power vent. Heated air 

entering the attic will activate the power vent.

Содержание VS1824NM

Страница 1: ...that includes instructions stating it has not been tested or should not be used with unvented gas logs This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Pr...

Страница 2: ...ING This is an unvented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion...

Страница 3: ...G Do not use a blower insert heat exchanger insert or other accessory not approved for use with this heater SAFETY Continued WARNING Do not allow fans to blow directly into the fireplace Avoid any dra...

Страница 4: ...fire department 5 This heater shall not be installed in a bedroom or bathroom unless installed as a vented appliance see Installing Damper Clamp Accessory for Vented Operation page 11 This gas log set...

Страница 5: ...of vent free heaters Non thermostat models may also be operated as a vented decorative ANSI Z21 60 product by opening flue damper SAFETY PILOT This heater has a pilot with an Oxygen Deple tion Sensin...

Страница 6: ...e whose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the ag AIR FOR COMBUSTION AND VENTILATION Continued gregate input rating of all appliances installed in that space and...

Страница 7: ...Fuel Gas Code or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined sp...

Страница 8: ...eplace If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damper INSTALLATION WARNING Never install the heater in a bedroom or bathroom unless inst...

Страница 9: ...4 Minimum Clearance for Combustible to Wall Minimum 16 from Side Wall Example INSTALLATION Continued NOTICE Manual control heaters may be used as a vented product If so you must always run heater with...

Страница 10: ...nd the top of the fireplace opening as shown in Figure 6 Determining Minimum Mantel Clearance When Using a Hood If minimum clearances in Figure 6 page 10 are not met you must have a hood When using a...

Страница 11: ...vented mode 1 The fireplace does not meet the clear ance to combustibles requirements for vent free operation 2 State or local codes do not permit vent free operation 3 You prefer vented operation If...

Страница 12: ...ealant resistant to propane LP gas not provided electric drill with 3 16 drill bit flathead screwdriver 1 Apply pipe joint sealant lightly to male threads of the fitting to be threaded into gas regula...

Страница 13: ...incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 of water If you do not reduce incoming gas pressure heater regulator damage could occur Install external regulator wit...

Страница 14: ...Cap off open end of gas pipe where equip ment shutoff valve was connected 3 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas or opening main gas valve...

Страница 15: ...e log installation instructions in this manual Flames contact ing log will create soot MODELS LVS18 VO AND LVS24 VO It is very important to install these logs exactly as instructed Do not modify logs...

Страница 16: ...er log as shown in Left Crossover Log Figure 19 Installing Left Crossover Log Figure 20 Installing Center Crossover Log Center Crossover Log Figure 21 Installing Left Crossover Log Right Crossover Log...

Страница 17: ...FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A This appliance h...

Страница 18: ...in for 30 sec onds after lighting pilot After 30 seconds release control knob Note If pilot goes out repeat steps 3 through 7 If control knob does not pop out when released contact a qualified servic...

Страница 19: ...shut down If pilot flame pattern is incorrect as shown in Figure 25 turn heater off see To Turn Off Gas to Ap pliance page 19 see Troubleshooting page 22 Note The pilot flame on natural gas units will...

Страница 20: ...ifice holder located at the end of the burner tube again Remove any large particles of dust dirt lint or pet hair with a soft cloth or vacuum cleaner nozzle Figure 26 Orifice Holder On Outlet Burner T...

Страница 21: ...sition 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When control knob is pressed in and turn...

Страница 22: ...atural or propane LP gas company 1 Contact local natural or propane LP gas company 2 Clean burner see Cleaning and Maintenance page 20 or replace burner orifice 1 Clean burner see Cleaning and Mainten...

Страница 23: ...perate burner until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see page 8 4 Clean burner see Cleaning and Main...

Страница 24: ...leaks see Checking Gas Con nections page 14 1 Open window and or door for ventilation 2 Contact local natural or propane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 20 1 Locate...

Страница 25: ...www SuperiorFireplaces US com 126842 01A 25 PARTS VARIABLE MANUALLY CONTROLLED BURNER SYSTEMS VS1824NM AND VS1824PM 15 3 14 16 11 10 4 2 12 8 5 14 13 7 9 1 15 15...

Страница 26: ...1 099415 24 Gas Regulator LP 1 8 122142 01 Manual Valve with Ignitor NG 1 122142 02 Manual Valve with Ignitor LP 1 9 122141 01 Manual Valve Outlet Tube 1 10 122146 02 Natural Gas Plate 1 11 107186 05...

Страница 27: ...8 02 Rear Log 1 124519 02 Rear Log 1 3 124518 03 Left Crossover Log 1 124519 03 Left Crossover Log 1 4 124518 04 Center Crossover Log 1 124519 04 Center Crossover Log 1 5 124518 05 Right Crossover Log...

Страница 28: ...s Pressure in of water Maximum 14 W C Minimum 11 W C Shipping Weight 27 lbs SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition heater will not produc...

Страница 29: ...HEARTH PRODUCTS at 1 800 655 2008 for informa tion You can also write to the address listed on the back page of this manual FLOOR MEDIA KIT FM100 For all models Includes lava rock burner embers and bu...

Страница 30: ...ll produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product...

Страница 31: ...IS WARRANTY Model located on product or identification tag ______________________________ Serial No located on product or identification tag ___________________________ Date Purchased ________________...

Страница 32: ...126842 01 Rev A 01 14 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 www IHP US com P126842 01...

Отзывы: