INSTALLATION

Continued

Figure 14 - Gas Connection

* Purchase the optional equipment shutoff 

valve from your dealer.
** Min. inlet pressure for purpose of input 

adjustment.

 Tee  Cap  Pipe

   Joint 

  Nipple

3" Min.

Sediment Trap

Gas 

Regulator

Equipment Shutoff Valve 

With 1/8" NPT Tap*

Approved 

Flexible 

Gas Hose (if 

allowed by 

local codes)

Natural

From Gas Meter 

(5" W.C.** to 

10.5" W.C. 

Pressure)

Propane/LP

From External 

Regulator

(11" W.C.** 

to 14" W.C. 

Pressure

CHECKING GAS CONNECTIONS

 WARNING: Test all gas piping 

and connections, internal and 

external to unit, for leaks after 

installing or servicing. Correct 

all leaks at once.

 WARNING: Never use an 

open flame to check for a leak. 

Apply a commercial leak de-

tection solution to all joints. 

Bubbles  forming  show  a  leak. 

Correct all leaks at once.

  CAUTION:  For  propane/LP 

units, make sure external regula

-

tor has been installed between 

propane/LP supply and heater. 

See guidelines under 

Connecting 

to Gas Supply

, page 13.

PRESSURE TESTING GAS SUPPLY 

PIPING SYSTEM 

Test Pressures In Excess Of 1/2 PSIG 

(3.5 kPa)

1.  Disconnect appliance with its appliance 

main gas valve (control valve) and equip

-

ment shutoff valve from gas supply piping. 

Pressures in excess of 1/2 psig (3.5 kPa)

will damage heater regulator.

2.  Cap off open end of gas pipe where equip

-

ment shutoff valve was connected.

3.  Pressurize supply piping system by either 

opening propane/LP supply tank valve 

for propane/LP gas or opening main gas 

valve located on or near gas meter for 

natural gas or using compressed air.

4.  Check all joints of gas supply piping system. 

Apply a commercial leak detection solution 

to all joints. Bubbles forming show a leak. 

5.  Correct all leaks at once.

6.  Reconnect heater and equipment shutoff 

valve to gas supply. Check reconnected 

fittings for leaks. 

Test Pressures Equal To or Less Than 

1/2 PSIG (3.5 kPa)

1.  Close equipment shutoff valve (see Fig

-

ure 15).

2.  Pressurize supply piping system by either 

opening propane/LP supply tank valve 

for propane/LP gas or opening main gas 

valve located on or near gas meter for 

natural gas or using compressed air.

Figure 15 - Equipment Shutoff Valve

Open

Closed

Equipment 

Shutoff Valve

We recommend that you install sediment 

trap in supply line as shown in Figure 14. 

Locate sediment trap where it is within reach 

for cleaning. Install in piping system between 

fuel supply and heater. Locate sediment trap 

where trapped matter is not likely to freeze. 

A sediment trap traps moisture and contami-

nants. This keeps them from going into heater 

controls. If sediment trap is not installed or is 

installed wrong, heater may not run properly.

 CAUTION: Avoid damage to 

regulator. Hold gas regulator with 

wrench when connecting it to gas 

piping and/or fittings.

Содержание VS1824NM

Страница 1: ...that includes instructions stating it has not been tested or should not be used with unvented gas logs This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Pr...

Страница 2: ...ING This is an unvented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion...

Страница 3: ...G Do not use a blower insert heat exchanger insert or other accessory not approved for use with this heater SAFETY Continued WARNING Do not allow fans to blow directly into the fireplace Avoid any dra...

Страница 4: ...fire department 5 This heater shall not be installed in a bedroom or bathroom unless installed as a vented appliance see Installing Damper Clamp Accessory for Vented Operation page 11 This gas log set...

Страница 5: ...of vent free heaters Non thermostat models may also be operated as a vented decorative ANSI Z21 60 product by opening flue damper SAFETY PILOT This heater has a pilot with an Oxygen Deple tion Sensin...

Страница 6: ...e whose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the ag AIR FOR COMBUSTION AND VENTILATION Continued gregate input rating of all appliances installed in that space and...

Страница 7: ...Fuel Gas Code or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined sp...

Страница 8: ...eplace If not drafting may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damper INSTALLATION WARNING Never install the heater in a bedroom or bathroom unless inst...

Страница 9: ...4 Minimum Clearance for Combustible to Wall Minimum 16 from Side Wall Example INSTALLATION Continued NOTICE Manual control heaters may be used as a vented product If so you must always run heater with...

Страница 10: ...nd the top of the fireplace opening as shown in Figure 6 Determining Minimum Mantel Clearance When Using a Hood If minimum clearances in Figure 6 page 10 are not met you must have a hood When using a...

Страница 11: ...vented mode 1 The fireplace does not meet the clear ance to combustibles requirements for vent free operation 2 State or local codes do not permit vent free operation 3 You prefer vented operation If...

Страница 12: ...ealant resistant to propane LP gas not provided electric drill with 3 16 drill bit flathead screwdriver 1 Apply pipe joint sealant lightly to male threads of the fitting to be threaded into gas regula...

Страница 13: ...incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 of water If you do not reduce incoming gas pressure heater regulator damage could occur Install external regulator wit...

Страница 14: ...Cap off open end of gas pipe where equip ment shutoff valve was connected 3 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas or opening main gas valve...

Страница 15: ...e log installation instructions in this manual Flames contact ing log will create soot MODELS LVS18 VO AND LVS24 VO It is very important to install these logs exactly as instructed Do not modify logs...

Страница 16: ...er log as shown in Left Crossover Log Figure 19 Installing Left Crossover Log Figure 20 Installing Center Crossover Log Center Crossover Log Figure 21 Installing Left Crossover Log Right Crossover Log...

Страница 17: ...FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A This appliance h...

Страница 18: ...in for 30 sec onds after lighting pilot After 30 seconds release control knob Note If pilot goes out repeat steps 3 through 7 If control knob does not pop out when released contact a qualified servic...

Страница 19: ...shut down If pilot flame pattern is incorrect as shown in Figure 25 turn heater off see To Turn Off Gas to Ap pliance page 19 see Troubleshooting page 22 Note The pilot flame on natural gas units will...

Страница 20: ...ifice holder located at the end of the burner tube again Remove any large particles of dust dirt lint or pet hair with a soft cloth or vacuum cleaner nozzle Figure 26 Orifice Holder On Outlet Burner T...

Страница 21: ...sition 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When control knob is pressed in and turn...

Страница 22: ...atural or propane LP gas company 1 Contact local natural or propane LP gas company 2 Clean burner see Cleaning and Maintenance page 20 or replace burner orifice 1 Clean burner see Cleaning and Mainten...

Страница 23: ...perate burner until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see page 8 4 Clean burner see Cleaning and Main...

Страница 24: ...leaks see Checking Gas Con nections page 14 1 Open window and or door for ventilation 2 Contact local natural or propane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 20 1 Locate...

Страница 25: ...www SuperiorFireplaces US com 126842 01A 25 PARTS VARIABLE MANUALLY CONTROLLED BURNER SYSTEMS VS1824NM AND VS1824PM 15 3 14 16 11 10 4 2 12 8 5 14 13 7 9 1 15 15...

Страница 26: ...1 099415 24 Gas Regulator LP 1 8 122142 01 Manual Valve with Ignitor NG 1 122142 02 Manual Valve with Ignitor LP 1 9 122141 01 Manual Valve Outlet Tube 1 10 122146 02 Natural Gas Plate 1 11 107186 05...

Страница 27: ...8 02 Rear Log 1 124519 02 Rear Log 1 3 124518 03 Left Crossover Log 1 124519 03 Left Crossover Log 1 4 124518 04 Center Crossover Log 1 124519 04 Center Crossover Log 1 5 124518 05 Right Crossover Log...

Страница 28: ...s Pressure in of water Maximum 14 W C Minimum 11 W C Shipping Weight 27 lbs SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition heater will not produc...

Страница 29: ...HEARTH PRODUCTS at 1 800 655 2008 for informa tion You can also write to the address listed on the back page of this manual FLOOR MEDIA KIT FM100 For all models Includes lava rock burner embers and bu...

Страница 30: ...ll produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product...

Страница 31: ...IS WARRANTY Model located on product or identification tag ______________________________ Serial No located on product or identification tag ___________________________ Date Purchased ________________...

Страница 32: ...126842 01 Rev A 01 14 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 www IHP US com P126842 01...

Отзывы: