COLD CLIMATE INSULATION

For cold climate installations, seal all cracks 

around your appliance with noncombustible 

material  and  wherever  cold  air  could  enter 

the room. It is especially important to insulate 

outside chase cavity between studs and under 

floor on which appliance rests, if floor is above 

ground level.  Gas line holes and other open-

ings should be caulked or stuffed with unfaced 

fiberglass insulation.  

If the fireplace is being installed on a cement 

slab in cold climates, a sheet of plywood or 

other raised platform can be placed underneath 

to prevent cold transfer to the fireplace and into 

the room.  It also helps to sheetrock inside 

surfaces and tape for maximum air tightness 

and caulk firestops.

MANUFACTURED HOME 

REQUIREMENTS

This appliance may be installed in an aftermar-

ket permanently located, manufactured  home 

(USA only) or Manufactured Home, where not 

prohibited by local codes. 

This  appliance  may  be  installed  as  an  OEM 

installation  in  a  manufactured  home  (USA 

only)  or  Manufactured  Home  and  must  be 

installed in accordance with the manufacturer's 

instructions  and  the  Manufactured  Home 

Construction  and  Safety  Standard,

  Title  24 

CPF, Part 3280 

or Standard  for 

Installation 

in Manufactured Homes, CAN/CSA Z240 MH. 

Cet  appareil  peut  être  installé  comme  du 

matériel d'origine dans une maison préfabri-

quée (É.-U. seulement) ou mobile  et doit être 

installé selon les instructions du fabricant et 

conformément à la norme Manufactured Home 

Construction and Safety Standard, Title 24 CPF, 

Part 3280 ou à la norme CAN/CSA Z240 Série 

MM, Maisons Mobiles.

Cet appareil peut être installé dans un maison 

préfabriquée (É.-U. seulement) ou mobile  déjà  

installée à demeure si les réglements locaux 

le permettent.

This appliance is only for use with the type of gas 

indicated on the rating plate.  This appliance is 

not convertible for use with other gases, unless 

a certified kit is used.

Cet appareil doit être utilisé uniquement avec le 

type de gaz indiqué sur la plaque signalétique.  

Cet appareil ne peut être converti à d'autres 

gaz,  sauf  si  une  trousse  de  conversion  est 

utilisée.

CAUTION:  Ensure  that  the  cross  mem-
bers  are  not  cut  or  weakened  during 
installation.  The  structural  integrity  of 
the manufactured home floor, wall, and 
ceiling / roof must be maintained. 

Vertical

Vent

Horizontal Vent 

(side vent)

Horizontal Vent 

(top vent)

Figure 2 

Typical Locations

Vertical

Venting

Offset Venting

(one end flush

with wall)

CAUTION:  This  appliance  must  be 
grounded  to  the  chassis  of  the  manu-
factured home in accordance with local 
codes or in the absence of local codes, 
with the National Electrical Code ANSI / 
NFPA 70 - latest edition or the Canadian 
Electrical Code CSA C22.1 - latest edi-
tion.

LOCATION

In  selecting  the  location,  the  aesthetic  and 

functional  use  of  the  appliance  are  primary 

concerns.  However,  vent  system  routing  to 

the exterior and access to the fuel supply are 

also important.  

Due  to  high  temperatures,  the  appliance 

should be located out of traffic and away from 

furniture and draperies (Figure 2). 

En raison des températures élevées, l’appareil 

devrait être installé dans un endroit où il y a 

peu de circulation et loin du mobilier et des 

tentures (Figure 2).

The location should also be free of electrical, 

plumbing  or  other  heating/air  conditioning 

ducting.

These  direct-vent  appliances  are  uniquely 

suited for installations requiring a utility shelf 

positioned directly above the fireplace. Utility 

shelves like these are commonly used for locat-

ing television sets and decorative plants. 

Be aware that this is a heat producing ap-

pliance.  Objects  placed  above  the  unit  are 

exposed to elevated temperatures.

Do not insulate the space between the ap-

pliance and the area above it 

(see Figure 8 

on Page 8)

.

The minimum height from the base of the appli-

ance to the underside of combustible materials 

used to construct a utility shelf in this fashion 

is shown in 

Figure 8 on Page 8

.  

The appliance should be mounted on a fully 

supported  base  extending  the  full  width  and 

depth of the unit. The appliance may be located 

on or near conventional construction materials. 

However, if installed on combustible materials, 

such as carpeting, vinyl tile, etc., a metal or 

wood barrier covering the entire bottom surface 

must be used.

Содержание SDVPF-N-B

Страница 1: ...sing property damage personal injury or death vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrica...

Страница 2: ...with piezo ignition system If any optional accessories that will require electrical power are to be installed the electrical power must be provided at the time of appliance in stallation These vented...

Страница 3: ...en marche Note Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent c...

Страница 4: ...n and in the USA the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition or in Canada the CAN CSA B149 1 latest edition NOTE Flame appearance will diminish 4 per thousand feet NOTE Each model ha...

Страница 5: ...pareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utilis e CAUTION Ensure that the cross mem bers are not cut or weakened during installation The structural integrity of t...

Страница 6: ...s For Vents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10...

Страница 7: ...Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15cm for appliances 10 000 Btuh 3kW 12 in 30cm for appliances 10 000 Btuh 3kW and 100 0...

Страница 8: ...mantels vary according to the depth of the mantel See Figure 6 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however do not allow anythin...

Страница 9: ...flanges as shown in Figure 10 using the existing screws Position the fireplace within the framing When required the tabs may be bent 90 degrees by hand or with the assistance of a hammer Use wood scr...

Страница 10: ...2 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left Side...

Страница 11: ...ral Propane Gas BTU Input 37 500 MV Low 30 000 Co axial DV Vent Size 4 1 2 Inner 7 1 2 Outer EFFICIENCIES SDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door...

Страница 12: ...ts for installations in the state of Massachusetts in the USA The gas supply line should Not be connected to the appliance until Step 6 Page 28 Apipejointcompoundratedforgasshouldbe used on the thread...

Страница 13: ...learances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz Use only approved ve...

Страница 14: ...4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2 0 1 5 8 2...

Страница 15: ...to the ceiling joists Route the vent sections through the framed opening and secure the firestop spacer with appropriate fasteners at each corner Remember to maintain 1 25 mm clear ance between verti...

Страница 16: ...the vent E Support the vertical vent run sections Note Properventingsupportisveryimportant The weight of the vent must not be supported by the fireplace in any degree Support the vertical portion of t...

Страница 17: ...ertical vent termination section Page 6 Figures 3A and 3B The SV4 5CGV 1 Vertical Termination Figure 27 can be installed in the exact same fashionasanyotherSecureVentsection Align the termination over...

Страница 18: ...table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet VERTICAL VENT FIGURES TABLES Notes Secure Vent rigid...

Страница 19: ...very 1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum total horizontal run of 20 feet Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum...

Страница 20: ...the component clockwise runningthedimplesdownandalong the incline channels until they seat at the end of thechannels TheunitizeddesignoftheSecure Ventcomponentswillengageandsealboththe inner and oute...

Страница 21: ...riodoftime following the use of the fireplace Young children should be carefully supervised when they are in the same area as a hot termination To prevent contact with hot surfaces we recommend the us...

Страница 22: ...degree elbows are used SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceil ing SV4 5HF Secure Vent SF4 5HF Secure Flex fir...

Страница 23: ...rizontal run up to a maximum horizontal run of 20 feet V H H 1 Table G H H1 Maximum V Minimum feet meter feet meter 3 0 914 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 21...

Страница 24: ...eof exterior wall thicknesses vWall Firestop Spacer SV4 5HF Square termination SV4 5HT 2 shown V H2 H1 H v Wall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Fir...

Страница 25: ...e inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pul...

Страница 26: ...ing the gas valve control knob or connect wires to optional wall thermostat wall switch or remote control to operate unit 1 If any of the original wire as supplied must be replaced 1 it must be replac...

Страница 27: ...ply wire to the top outlet sblackpigtailleadandtotheswitch s black lead Connect the white supply wire to the neutral terminal of the outlet box CAUTIONS Remove the carton support from the control comp...

Страница 28: ...ge 12 to a point within the control compartment that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securel...

Страница 29: ...appliance will not require such purging Inspect the pilot flame Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of oran...

Страница 30: ...ea on both sides of the log set The glowing embers may touch one another but should not overlap each other FRONT OF FIREPLACE REAR BURNER FRONT BURNER Outer Log Notch Location FIREBOX SUBFLOOR Outer L...

Страница 31: ...re n est pas en place est craqu ou bris Top Flange on Glass Door Bottom Vee flange Glass Door Glass Door Latch Glass Door Firebox Floor INSTALLING OR REMOVING GLASS DOOR Figure 55 Note When installing...

Страница 32: ...aming Step 11 Hood Installation All of these appliances must have hoods installed prior to operating see Figure 58 Slide the hood into the slots on the lower edge of the cabinet top see Figure 58 Fini...

Страница 33: ...sadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeelinterruptor ope...

Страница 34: ...SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Collar 6 per box 8 H2246 SV4 5HF Firestop Spacer Hor...

Страница 35: ...ent roof support collar assembly roof flashing and storm collar 19 56L75 SFVT45 Vertical Termination for flex 6 12 to 12 12 with flex adapter section of rigid vent roof support collar assembly roof fl...

Страница 36: ...2 12 Pitch 25 92L09 SV FSTFE Firestop Thimble SV Flat with Extension 25 92L10 SV FST1E Firestop Thimble SV 1 12 Pitch with Extension 25 92L11 SV FST2E Firestop Thimble SV 2 12 Pitch with Extension 26...

Страница 37: ...or dance with the manufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproduct...

Страница 38: ...Page 29 Step 11 Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3 5 inches water column 0 87 kPa for natural gas and 10 0 inches water column 2 49 kPa f...

Страница 39: ...39 NOTES...