NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

38

SIT Millivolt Gas Valve

Pilot for SIT Millivolt 

Gas Valve

Figure 61

Pressure

Regulator

Remove 

These 

Components

Figure 60

Pilot
Orifice

NOTE: Flame appearance will diminish 4% per 

thousand feet.

NOTE:  Each  model  has  two  burners  and  2 

Orifices.

Burner Orifice Sizes 

Elevation 0-4500 feet ( 0-1372 meters)

Elevation

Feet (meters)

Natural Gas

drill size (inches)

Propane 

Gas

drill size (inches)

0-4500

(0-1372)

#44 (.086") *

60J80 •

#55 (.052")**

19L52 •

Table 9

Figure 63

BURNER POSITIONING

REAR BURNER

FRONT BURNER

PILOT

BURNER

Note: The burners are not identical. Position them so

that  the  circular  burner  ports  run  as  shown.  Note

especially the vertical run of ports relative to the pilot

burner. Bracket A on the rear burner will interfere with

the  pilot  burner  if  an  attempt  is  made  to  install  the

rear burner in the front burner’s position.

BRACKET A

BURNER

PORTS

NOTE: INSTALL REAR BURNER FIRST,

 THEN FRONT BURNER.

Step 8. Reassemble the remaining components 

by  reversing  the  procedures  outlined  in  the 

preceding steps.  

Step 9. Attach the conversion label provided 

in the conversion kit to the rating plate on the 

appliance. 

Step 10. Turn on gas supply and test for gas 

leaks. See

 Test All Connections For Gas Leaks 

on 

Page 29

.

Step  11.  Attach  manometer  to  the  manifold 

side pressure test fitting and verify manifold 

pressure reads 3.5 inches water column (0.87 

kPa)  for  natural  gas,  and  10.0  inches  water 

column (2.49 kPa) for propane gas.

ALWAYS TEST PRESSURES WITH THE VALVE 

REGULATOR  CONTROL  AT  THE  HIGHEST 

SETTING.

Step 6.  See 

Figure 61

 and remove the pilot 

hood assembly to access the hexed pilot orifice.  
Remove and replace the orifice with the one 
provided with the kit.

Figure 62

BURNER 

ORIFICE

Step 7.  (Refer to 

Figure 59 on Page 37 and 

Figure 62)

VERIFY  THE  PROPER  ORIFICE  SIZES 

BEFORE INSTALLING THEM.

A. Remove  the two orifices from the manifold 

and replace them with the ones provided in the 

kit. 

Table 9 

 shows the orifice sizes for natural 

and propane models. 

Figure 62 

illustrates the 

orifice. Use pipe joint compound or Teflon tape 

on  all  pipe  fittings  before  installing  (ensure 

propane  resistant  compounds  are  used  in 

propane  applications,  do  not  use  pipe  joint 

compounds on flare fittings). 

B. Install rear burner first, followed by front 

burner, as shown in 

Figure 63

.  Ensure that the 

arm of the venturi of each burner is hooked onto 

the air shutter adjustment lever (refer to

 Figure 

59

 on 

Page 37)

.  The primary air opening can 

be adjusted by rotating the adjustment lever 

from beneath the firebox floor. Refer to 

Figure 

56 

on 

Page 32

 for the recommended minimum 

primary air opening setting.

* Standard size installed at factory

** Standard size in LP conversion kit

•  Part /Cat. Number

Содержание SDVPF-N-B

Страница 1: ...sing property damage personal injury or death vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrica...

Страница 2: ...with piezo ignition system If any optional accessories that will require electrical power are to be installed the electrical power must be provided at the time of appliance in stallation These vented...

Страница 3: ...en marche Note Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent c...

Страница 4: ...n and in the USA the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition or in Canada the CAN CSA B149 1 latest edition NOTE Flame appearance will diminish 4 per thousand feet NOTE Each model ha...

Страница 5: ...pareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utilis e CAUTION Ensure that the cross mem bers are not cut or weakened during installation The structural integrity of t...

Страница 6: ...s For Vents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10...

Страница 7: ...Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15cm for appliances 10 000 Btuh 3kW 12 in 30cm for appliances 10 000 Btuh 3kW and 100 0...

Страница 8: ...mantels vary according to the depth of the mantel See Figure 6 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however do not allow anythin...

Страница 9: ...flanges as shown in Figure 10 using the existing screws Position the fireplace within the framing When required the tabs may be bent 90 degrees by hand or with the assistance of a hammer Use wood scr...

Страница 10: ...2 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left Side...

Страница 11: ...ral Propane Gas BTU Input 37 500 MV Low 30 000 Co axial DV Vent Size 4 1 2 Inner 7 1 2 Outer EFFICIENCIES SDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door...

Страница 12: ...ts for installations in the state of Massachusetts in the USA The gas supply line should Not be connected to the appliance until Step 6 Page 28 Apipejointcompoundratedforgasshouldbe used on the thread...

Страница 13: ...learances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz Use only approved ve...

Страница 14: ...4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2 0 1 5 8 2...

Страница 15: ...to the ceiling joists Route the vent sections through the framed opening and secure the firestop spacer with appropriate fasteners at each corner Remember to maintain 1 25 mm clear ance between verti...

Страница 16: ...the vent E Support the vertical vent run sections Note Properventingsupportisveryimportant The weight of the vent must not be supported by the fireplace in any degree Support the vertical portion of t...

Страница 17: ...ertical vent termination section Page 6 Figures 3A and 3B The SV4 5CGV 1 Vertical Termination Figure 27 can be installed in the exact same fashionasanyotherSecureVentsection Align the termination over...

Страница 18: ...table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet VERTICAL VENT FIGURES TABLES Notes Secure Vent rigid...

Страница 19: ...very 1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum total horizontal run of 20 feet Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum...

Страница 20: ...the component clockwise runningthedimplesdownandalong the incline channels until they seat at the end of thechannels TheunitizeddesignoftheSecure Ventcomponentswillengageandsealboththe inner and oute...

Страница 21: ...riodoftime following the use of the fireplace Young children should be carefully supervised when they are in the same area as a hot termination To prevent contact with hot surfaces we recommend the us...

Страница 22: ...degree elbows are used SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceil ing SV4 5HF Secure Vent SF4 5HF Secure Flex fir...

Страница 23: ...rizontal run up to a maximum horizontal run of 20 feet V H H 1 Table G H H1 Maximum V Minimum feet meter feet meter 3 0 914 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 21...

Страница 24: ...eof exterior wall thicknesses vWall Firestop Spacer SV4 5HF Square termination SV4 5HT 2 shown V H2 H1 H v Wall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Fir...

Страница 25: ...e inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pul...

Страница 26: ...ing the gas valve control knob or connect wires to optional wall thermostat wall switch or remote control to operate unit 1 If any of the original wire as supplied must be replaced 1 it must be replac...

Страница 27: ...ply wire to the top outlet sblackpigtailleadandtotheswitch s black lead Connect the white supply wire to the neutral terminal of the outlet box CAUTIONS Remove the carton support from the control comp...

Страница 28: ...ge 12 to a point within the control compartment that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securel...

Страница 29: ...appliance will not require such purging Inspect the pilot flame Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of oran...

Страница 30: ...ea on both sides of the log set The glowing embers may touch one another but should not overlap each other FRONT OF FIREPLACE REAR BURNER FRONT BURNER Outer Log Notch Location FIREBOX SUBFLOOR Outer L...

Страница 31: ...re n est pas en place est craqu ou bris Top Flange on Glass Door Bottom Vee flange Glass Door Glass Door Latch Glass Door Firebox Floor INSTALLING OR REMOVING GLASS DOOR Figure 55 Note When installing...

Страница 32: ...aming Step 11 Hood Installation All of these appliances must have hoods installed prior to operating see Figure 58 Slide the hood into the slots on the lower edge of the cabinet top see Figure 58 Fini...

Страница 33: ...sadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeelinterruptor ope...

Страница 34: ...SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Collar 6 per box 8 H2246 SV4 5HF Firestop Spacer Hor...

Страница 35: ...ent roof support collar assembly roof flashing and storm collar 19 56L75 SFVT45 Vertical Termination for flex 6 12 to 12 12 with flex adapter section of rigid vent roof support collar assembly roof fl...

Страница 36: ...2 12 Pitch 25 92L09 SV FSTFE Firestop Thimble SV Flat with Extension 25 92L10 SV FST1E Firestop Thimble SV 1 12 Pitch with Extension 25 92L11 SV FST2E Firestop Thimble SV 2 12 Pitch with Extension 26...

Страница 37: ...or dance with the manufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproduct...

Страница 38: ...Page 29 Step 11 Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3 5 inches water column 0 87 kPa for natural gas and 10 0 inches water column 2 49 kPa f...

Страница 39: ...39 NOTES...

Страница 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Отзывы: