background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

15

Figure 18

Roof 

Framing

Ceiling

Framing

Plumb

Bob

10-1/2" Min. 

(267 mm)

10-1/2" Min. 

(267 mm)

Figure 19

Align the dimple (four places) of the 

upper vent section with the opening 

of the locking incline channel on the 

lower vent section or appliance col-

lar.  Twist vent component clockwise 

to engage and seal until arrow and 

dimple align.

Dimple

Locking Incline 

Channel

Connected Vent 

Sections

Arrow

Arrow

Appliance Collar or 

Vent Section

Vertical (Offset) Installation
Analyze  the  vent  routing  and  determine  the 

number of vent sections and elbows required. 

Refer to Vertical Vent Figures and Tables on 

Pages 18 and 19

  to select the type of vertical 

installation desired. Vent sections are available 

in net lengths of 4-1/2" (114 mm), 10-1/2" (267 

mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 

46-1/2" (1181 mm).  Refer to the Vent Section 

Length Charts

 

on 

Page 14

  for an aid in selecting 

vent length combinations.  Elbows are available 

in 45° and 90° configurations.  Refer to 

Figure 

24 on Page 16 

for the SV4.5E45 and SV4.5E90 

elbow dimensional specifications.   
Where  required,  a  Telescopic  Vent  Section  

(SV4.5LA)  may be used to provide the installer 

with an option in installing in tight and confined 

spaces or where the vent run made up of fixed 

length pieces develops a joint in a undesirable 

location, or will not build up to the required 

length. The SV4.5LA Telescopic Vent Section 

has an effective length of from 1-1/2" (38 mm) 

to 7-1/2" (191 mm). The SV4.5LA  is fitted with 

a locking inclined channel end (identical to a 

normal vent section component) and a plain end 

with 3 pilot holes. Slip the plain end over the 

locking channel end of a standard  SV4.5 vent 

component the required distance and secure 

with three screws.
Maintain a minimum 1" (25 mm) clearance 

to combustible materials for all vertical ele-

ments. Clearances for all horizontal elements 

are 3" (76 mm) on top, 1" (25 mm) on sides 

and 1" (25 mm) on the bottom.
A.
 Frame ceiling opening - Use a plumb line 

from the ceiling above the appliance to locate 

center  of  the  vertical  run.  Cut  and/or  frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center mark 

(Figure 18)

.

14" Min.

Outer Pipe Of

Chimney

Use correct firestop

thimble depending on the

pitch of the interior

ceiling.

Note:  Regular Thimble

(SV-FSTFE) Can Be Used

If A Header Is Constructed

At This Point

 Figure 20

Push the vent component against the previous 

section  until  it  fully  engages,  then  twist  the 

component clockwise running the dimples down 

and along the incline channels until they seat at 

the end of the channels.  This seating position 

is indicated by the alignment of the arrow and 

dimple as shown in 

Figure 19.

D1. Install firestop/spacer at ceiling between 

stories  -  Install  a  firestop/spacer  (catalog 

no. H2247 - Secure Vent; catalog no. H2249 

- Secure Flex) at the bottom side of the ceiling 

to the ceiling joists. Route the vent sections 

through  the  framed  opening  and  secure  the 

firestop/spacer  with  appropriate  fasteners  at 

each corner.

Remember  to  maintain  1"  (25  mm)  clear-

ance between vertical chimney sections and 

combustibles,  framing  members,  and  attic 

or ceiling insulation.

D2. Install firestop thimble at the ceiling to 

roof location  - Position appropriate firestop 

thimble 

(see Table on Page 36)

 at the bottom 

side  of  ceiling  and  secure    temporarily  with 

two appropriate fasteners. Attach permanently, 

using at least two more fasteners, after vent sec-

tions have been assembled through the firestop 

thimble and after any necessary adjustments 

have been made.

Ensure the thimble penetrates the roof opening. 

The thimble must extend completely through the 

ceiling or roof cavity to the outermost plane of 

the roof. Use thimble extension SVTE26 when 

the distance between the outside of the roof and 

the inside of the ceiling exceeds the height of 

the firestop thimble. The thimble provides for 

zero clearances to combustibles and must be 

used at the ceiling/roof in manufactured homes 

with  Secure  Vent  double  wall  vent  sections. 

Maintain 1 in. (25.4 mm) clearance between 

the thimble and the outer pipe of the secure 

vent chimney system. See 

Figure 21 (Page 

16)

  for  pitched  roofs  or  flat  roofs  with  flat 

ceilings or 

Figure 20 

 for pitched roofs with 

cathedral ceilings.

To attach a vent component to the appliance 

collar,  align the  dimpled end over  the collar, 

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlet of the four 

inclined channels on the collar (

refer to Figure 

19)

. Push the vent component against the collar 

until it fully engages, then twist the component 

clockwise, running the dimples down and along 

the incline channels until they seat at the end of 

the channels.  The unitized design of the Secure 

Vent components will engage and seal both the 

inner and outer pipe  without the need for sealant 

or screws.  If desired a #6 x 1/2" screw may be 

used at the joint, but it not required as the pipe 

will securely lock when twisted.

Note: An elbow may also be attached to the 

appliance collar.  Attach in the same manner 

as you would a vent section. 

C.  Attach  vent  components  to  each  other 

-  Other  vent  sections  may  be  added  to  the 

previously installed section in accordance with 

the requirements of the vertical vent Figures 

and Tables.  To add another vent component 

to a length of vent run, align the dimpled end 

over the inclined channel end of the previously 

installed section, adjusting the radial alignment 

until the four locking dimples are aligned with 

the inlets of the four incline channels of the 

previous section.  

B. Attach vent components to appliance - Se-

cure Vent  SV4.5 direct-vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connections (

see 

Figure 19)

.  

All of the appliances covered in this document 

are fitted with collars having locking inclined 

channels.  The dimpled end  of the vent com-

ponents fit over the appliance collar to create 

the positive twist lock connection.

Содержание SDVPF-N-B

Страница 1: ...sing property damage personal injury or death vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrica...

Страница 2: ...with piezo ignition system If any optional accessories that will require electrical power are to be installed the electrical power must be provided at the time of appliance in stallation These vented...

Страница 3: ...en marche Note Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent c...

Страница 4: ...n and in the USA the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition or in Canada the CAN CSA B149 1 latest edition NOTE Flame appearance will diminish 4 per thousand feet NOTE Each model ha...

Страница 5: ...pareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utilis e CAUTION Ensure that the cross mem bers are not cut or weakened during installation The structural integrity of t...

Страница 6: ...s For Vents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10...

Страница 7: ...Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15cm for appliances 10 000 Btuh 3kW 12 in 30cm for appliances 10 000 Btuh 3kW and 100 0...

Страница 8: ...mantels vary according to the depth of the mantel See Figure 6 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however do not allow anythin...

Страница 9: ...flanges as shown in Figure 10 using the existing screws Position the fireplace within the framing When required the tabs may be bent 90 degrees by hand or with the assistance of a hammer Use wood scr...

Страница 10: ...2 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left Side...

Страница 11: ...ral Propane Gas BTU Input 37 500 MV Low 30 000 Co axial DV Vent Size 4 1 2 Inner 7 1 2 Outer EFFICIENCIES SDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door...

Страница 12: ...ts for installations in the state of Massachusetts in the USA The gas supply line should Not be connected to the appliance until Step 6 Page 28 Apipejointcompoundratedforgasshouldbe used on the thread...

Страница 13: ...learances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz Use only approved ve...

Страница 14: ...4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2 0 1 5 8 2...

Страница 15: ...to the ceiling joists Route the vent sections through the framed opening and secure the firestop spacer with appropriate fasteners at each corner Remember to maintain 1 25 mm clear ance between verti...

Страница 16: ...the vent E Support the vertical vent run sections Note Properventingsupportisveryimportant The weight of the vent must not be supported by the fireplace in any degree Support the vertical portion of t...

Страница 17: ...ertical vent termination section Page 6 Figures 3A and 3B The SV4 5CGV 1 Vertical Termination Figure 27 can be installed in the exact same fashionasanyotherSecureVentsection Align the termination over...

Страница 18: ...table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet VERTICAL VENT FIGURES TABLES Notes Secure Vent rigid...

Страница 19: ...very 1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum total horizontal run of 20 feet Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum...

Страница 20: ...the component clockwise runningthedimplesdownandalong the incline channels until they seat at the end of thechannels TheunitizeddesignoftheSecure Ventcomponentswillengageandsealboththe inner and oute...

Страница 21: ...riodoftime following the use of the fireplace Young children should be carefully supervised when they are in the same area as a hot termination To prevent contact with hot surfaces we recommend the us...

Страница 22: ...degree elbows are used SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceil ing SV4 5HF Secure Vent SF4 5HF Secure Flex fir...

Страница 23: ...rizontal run up to a maximum horizontal run of 20 feet V H H 1 Table G H H1 Maximum V Minimum feet meter feet meter 3 0 914 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 21...

Страница 24: ...eof exterior wall thicknesses vWall Firestop Spacer SV4 5HF Square termination SV4 5HT 2 shown V H2 H1 H v Wall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Fir...

Страница 25: ...e inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pul...

Страница 26: ...ing the gas valve control knob or connect wires to optional wall thermostat wall switch or remote control to operate unit 1 If any of the original wire as supplied must be replaced 1 it must be replac...

Страница 27: ...ply wire to the top outlet sblackpigtailleadandtotheswitch s black lead Connect the white supply wire to the neutral terminal of the outlet box CAUTIONS Remove the carton support from the control comp...

Страница 28: ...ge 12 to a point within the control compartment that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securel...

Страница 29: ...appliance will not require such purging Inspect the pilot flame Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of oran...

Страница 30: ...ea on both sides of the log set The glowing embers may touch one another but should not overlap each other FRONT OF FIREPLACE REAR BURNER FRONT BURNER Outer Log Notch Location FIREBOX SUBFLOOR Outer L...

Страница 31: ...re n est pas en place est craqu ou bris Top Flange on Glass Door Bottom Vee flange Glass Door Glass Door Latch Glass Door Firebox Floor INSTALLING OR REMOVING GLASS DOOR Figure 55 Note When installing...

Страница 32: ...aming Step 11 Hood Installation All of these appliances must have hoods installed prior to operating see Figure 58 Slide the hood into the slots on the lower edge of the cabinet top see Figure 58 Fini...

Страница 33: ...sadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeelinterruptor ope...

Страница 34: ...SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Collar 6 per box 8 H2246 SV4 5HF Firestop Spacer Hor...

Страница 35: ...ent roof support collar assembly roof flashing and storm collar 19 56L75 SFVT45 Vertical Termination for flex 6 12 to 12 12 with flex adapter section of rigid vent roof support collar assembly roof fl...

Страница 36: ...2 12 Pitch 25 92L09 SV FSTFE Firestop Thimble SV Flat with Extension 25 92L10 SV FST1E Firestop Thimble SV 1 12 Pitch with Extension 25 92L11 SV FST2E Firestop Thimble SV 2 12 Pitch with Extension 26...

Страница 37: ...or dance with the manufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproduct...

Страница 38: ...Page 29 Step 11 Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3 5 inches water column 0 87 kPa for natural gas and 10 0 inches water column 2 49 kPa f...

Страница 39: ...39 NOTES...

Страница 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Отзывы: