NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

26

Step 4. FIELD WIRING 

Note:

 The gas valve is set in place and pre-wired 

at the factory.

A. SIT and Honeywell Millivolt Wiring 

(See Figure 44)

1. Select  any of the following optional controls: 

wall-mounted    switch,  wall  thermostat  or 

remote  control  kit.  If  appliance-mounted 

ON/OFF control is selected mount it in the 

gas valve mounting bracket. 

2. If  wall-mounted  ON/OFF  control  or  ther-

mostat is selected mount it in a convenient 

location on a wall near the fireplace.

3. Wire the control within the millivolt control 

circuit  using the 15 feet of 2 conductor wire 

supplied with the unit .  Caution:    Do  NOT 

connect the optional wall switch to a 120V 

power supply.

4. Alternatively, the appliance may be operated 

without the use of the controls indicated in 

Step 1

, solely  by manipulating the gas valve 

control knob. In order to use this method, 

twist the free ends of the two conductor wire 

(which would otherwise go to an Optional 

Control Switch) together as shown in 

Figure 

44

 

Note:

  Wire  is  located  inside  the  control 

compartment.

Note: The supplied 15 feet of 2 conductor wire 

has one end of each conductor connected to 

the gas valve circuit and the other end of each 

conductor  placed  loose  inside  the  control 

compartment. 

Figure 45 -  

Blower Wiring Diagram

Figure 44 - 

Millivolt Wiring Diagram

Field Wired

Factory 

Wired

TH

TP

TH

TP

 

 

 

 

u

 Optional 

Control Switch

Thermopile

Schematic
Representation
Only

•  If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 

105 C - 18 gage wire.

u

  

Optional Kits Installed - ON/OFF  wall switch, wall thermostat or remote control receiver. 

HT

PT

HT

PT

*

u

 Twist wires together to operate 

unit solely by manipulating the gas 

valve control knob; or connect wires 

to optional wall thermostat, wall 

switch or remote control to operate 

unit.

1. If any of the original wire as supplied must be replaced,

1.

it must be replaced with Type AWM 105

°

C – 18 GA. wire.

2. 120V, 60Hz – Less than 3 amps.

Wiring Diagram

Showing the Blower Wiring 

for the Optional FBK-100 Kit

Factory Wired

Field Wired

Schematic Representation Only

Junction Box 

Tab Intact

Tab 

Broken

Plug blower

into this 

receptacle

n

e

e

r

G

 -

 

d

n

u

o

r

G

*Optional Accessory Switch

Optional

Blower

Ground

e

ti

h

W

 -

 l

a

rt

u

e

N

120 VAC - Black

Green

Ground

Screw

White

Green

Neutral 

Side of

Receptacle

Hot

Side of

Receptacle

Red

Black

*J-BOX WIRING FOR

OPTIONAL (BLOWER 

CONTROL) ACCESSORY 

SWITCH

u

CAUTION:  Label all wires prior to disconnec-

tion when servicing controls. Wiring errors can 

cause improper and dangerous operation. 

ATTENTION:  Au moment de l'entretien des 

commandes, étiquetez tous les fils avant de 

les débrancher.  Des erreurs de cáblage peu-

vent entraîner un fonctionnement inadéquat 

et dangereux.

Verify proper operation after servicing.

S'assurer que l'appareil fonctionne adé-

quatement une fois l'entretien terminé.

       

CAUTION

Ground supply lead must be con-

nected to the wire attached to the 

green ground screw located on the  

outlet box.   See 

Figure 45

. Failure to 

do so will result in a potential  safety 

hazard.    The  appliance  must  be 

electrically grounded in accordance 

with local codes or, in the absence of 

local codes, the National Electrical 

Code, ANSI/NFPA 70-latest edition. 

(In Canada, the current CSA C22-1 

Canadian Electrical Code).

Figure 46

Outlet Receptacle

Junction Box

Field-provided Metal Junction Box

 Cover Plate With Screw

View Of Right

Bottom Corner Of Unit

Receptacle, Junction Box 

and Cover Plate Installation

Fireplace 

Side

Junction Box 

knock-out (2 

places each side)

Valve Access Side

Press snap 

bushing into the  

knock-out for 

control switch 

wires. 

Содержание SDVPF-N-B

Страница 1: ...sing property damage personal injury or death vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrica...

Страница 2: ...with piezo ignition system If any optional accessories that will require electrical power are to be installed the electrical power must be provided at the time of appliance in stallation These vented...

Страница 3: ...en marche Note Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent c...

Страница 4: ...n and in the USA the National Fuel Gas Code NFPA 54 ANSI Z223 1 latest edition or in Canada the CAN CSA B149 1 latest edition NOTE Flame appearance will diminish 4 per thousand feet NOTE Each model ha...

Страница 5: ...pareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utilis e CAUTION Ensure that the cross mem bers are not cut or weakened during installation The structural integrity of t...

Страница 6: ...s For Vents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10...

Страница 7: ...Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15cm for appliances 10 000 Btuh 3kW 12 in 30cm for appliances 10 000 Btuh 3kW and 100 0...

Страница 8: ...mantels vary according to the depth of the mantel See Figure 6 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however do not allow anythin...

Страница 9: ...flanges as shown in Figure 10 using the existing screws Position the fireplace within the framing When required the tabs may be bent 90 degrees by hand or with the assistance of a hammer Use wood scr...

Страница 10: ...2 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left Side...

Страница 11: ...ral Propane Gas BTU Input 37 500 MV Low 30 000 Co axial DV Vent Size 4 1 2 Inner 7 1 2 Outer EFFICIENCIES SDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door...

Страница 12: ...ts for installations in the state of Massachusetts in the USA The gas supply line should Not be connected to the appliance until Step 6 Page 28 Apipejointcompoundratedforgasshouldbe used on the thread...

Страница 13: ...learances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz Use only approved ve...

Страница 14: ...4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2 0 1 5 8 2...

Страница 15: ...to the ceiling joists Route the vent sections through the framed opening and secure the firestop spacer with appropriate fasteners at each corner Remember to maintain 1 25 mm clear ance between verti...

Страница 16: ...the vent E Support the vertical vent run sections Note Properventingsupportisveryimportant The weight of the vent must not be supported by the fireplace in any degree Support the vertical portion of t...

Страница 17: ...ertical vent termination section Page 6 Figures 3A and 3B The SV4 5CGV 1 Vertical Termination Figure 27 can be installed in the exact same fashionasanyotherSecureVentsection Align the termination over...

Страница 18: ...table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet VERTICAL VENT FIGURES TABLES Notes Secure Vent rigid...

Страница 19: ...very 1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum total horizontal run of 20 feet Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum...

Страница 20: ...the component clockwise runningthedimplesdownandalong the incline channels until they seat at the end of thechannels TheunitizeddesignoftheSecure Ventcomponentswillengageandsealboththe inner and oute...

Страница 21: ...riodoftime following the use of the fireplace Young children should be carefully supervised when they are in the same area as a hot termination To prevent contact with hot surfaces we recommend the us...

Страница 22: ...degree elbows are used SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceil ing SV4 5HF Secure Vent SF4 5HF Secure Flex fir...

Страница 23: ...rizontal run up to a maximum horizontal run of 20 feet V H H 1 Table G H H1 Maximum V Minimum feet meter feet meter 3 0 914 Elbow Only 5 1 524 1 0 305 10 3 048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 21...

Страница 24: ...eof exterior wall thicknesses vWall Firestop Spacer SV4 5HF Square termination SV4 5HT 2 shown V H2 H1 H v Wall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Fir...

Страница 25: ...e inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pul...

Страница 26: ...ing the gas valve control knob or connect wires to optional wall thermostat wall switch or remote control to operate unit 1 If any of the original wire as supplied must be replaced 1 it must be replac...

Страница 27: ...ply wire to the top outlet sblackpigtailleadandtotheswitch s black lead Connect the white supply wire to the neutral terminal of the outlet box CAUTIONS Remove the carton support from the control comp...

Страница 28: ...ge 12 to a point within the control compartment that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securel...

Страница 29: ...appliance will not require such purging Inspect the pilot flame Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of oran...

Страница 30: ...ea on both sides of the log set The glowing embers may touch one another but should not overlap each other FRONT OF FIREPLACE REAR BURNER FRONT BURNER Outer Log Notch Location FIREBOX SUBFLOOR Outer L...

Страница 31: ...re n est pas en place est craqu ou bris Top Flange on Glass Door Bottom Vee flange Glass Door Glass Door Latch Glass Door Firebox Floor INSTALLING OR REMOVING GLASS DOOR Figure 55 Note When installing...

Страница 32: ...aming Step 11 Hood Installation All of these appliances must have hoods installed prior to operating see Figure 58 Slide the hood into the slots on the lower edge of the cabinet top see Figure 58 Fini...

Страница 33: ...sadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeelinterruptor ope...

Страница 34: ...SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Collar 6 per box 8 H2246 SV4 5HF Firestop Spacer Hor...

Страница 35: ...ent roof support collar assembly roof flashing and storm collar 19 56L75 SFVT45 Vertical Termination for flex 6 12 to 12 12 with flex adapter section of rigid vent roof support collar assembly roof fl...

Страница 36: ...2 12 Pitch 25 92L09 SV FSTFE Firestop Thimble SV Flat with Extension 25 92L10 SV FST1E Firestop Thimble SV 1 12 Pitch with Extension 25 92L11 SV FST2E Firestop Thimble SV 2 12 Pitch with Extension 26...

Страница 37: ...or dance with the manufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproduct...

Страница 38: ...Page 29 Step 11 Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3 5 inches water column 0 87 kPa for natural gas and 10 0 inches water column 2 49 kPa f...

Страница 39: ...39 NOTES...

Страница 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Отзывы: