Air Inlet Liner (for combustion air) When 

terminating the air inlet liner at this point, a 

positive flue connection is required (to ensure 

combustion air is drawn down the chimney 

only).

Exhaust 3" (75mm) UL 

1777. A full length liner 

is required from the 

exhaust outlet on appli-

ance to center collar of 

termination cap.

Positive Flue Con-

nection (sealing 

fireplace throat 

using a noncombus-

tible seal-off plate 

or insulation).

The outside air inlet does not 

require a full reline (if intake 

liner is terminated in chimney 

and a positive flue connection 

is achieved as specified).

Ai

r I

nl

et

Ex

ha

us

t

Ai

r I

nl

et

Existing Fireplace Flue

(chimney)

Masonry and Factory Built Fireplaces

Figure 6a - Terminating Air Inlet in Chimney 

NOTE: Terminating the air intake liner as shown here may not be al-

lowed by some local codes.  Check with the authority having jurisdiction 

for your area.

Note:

  The minimum vertical rise (exhaust vent) is 10 feet (3.1 M) and the 

maximum vertical rise is 35 feet (10.7 M). These dimensions are measured 

from the starting collars of the unit to the end of the vent pipe.
The fireplace and fireplace chimney must be clean and in good working 

order and constructed of non-combustible materials. Inspect chimney 

cleanouts for proper fit and seal.
* Other approved vent components include; Standard Simpson Dura-

vent Co-linear Chimney Liner Kit, Direct-Vent Termination #991, Liner 

Termination Kit (includes termination connector and flashing) #923GK 

and 3" x 35' Alum Flex #2280

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Vertical Venting

The vent pipes must be connected to the proper collars on the unit and 

the exhaust vent pipe must be connected to the termination cap or the 

unit will not operate.
The combustion air intake pipe can be connected to the termination cap 

(see 

Figure 6b

) or it can terminate inside the chimney (see 

Figure 6a

).  

If combustion air intake pipe is terminated inside the chimney and not 

connected to the actual termination cap the bottom opening of the chim-

ney (chimney throat) must be sealed around the vent pipes.  Use a non 

combustible seal-off plate (i.e. 22 gage sheet steel) or unfaced fiberglass 

insulation (8 lb per square foot density minimum) to seal around the vent 

pipes.  Whichever “seal off” method is used must effectively seal the area 

to prevent room air passage to the chimney of the fireplace.  The insulation 

may give off an odor during the first hour of operation.

Venting Installation

Your Superior™ gas insert must be vented to the outside in accordance 

with the current edition of the National Fuel Gas Code ANSI-Z223.1 (In 

Canada,  the  current  CAN/CSA    B149.1  installation  code).    The  insert 

must not be connected to a chimney flue serving a separate solid fuel 

burning appliance.
This gas insert requires a 3” diameter listed flex liner. The vent should 

terminate with a listed direct-vent termination cap. The chimney should be 

sealed around the cap to prevent air and rain from entering the chimney. 

Adhere to the vent manufacturer's instructions for installation and vent 

termination. These appliances are approved for use with the following 

vent kits.

Vertical Cap

Termination 

Connector

Exhaust

Intake

Combustion Air Intake

The existing fireplace chimneys 

may  take  various  contours 

which  the  flexible  liners  will 

accommodate. However, keep 

the flexible liner as STRAIGHT 

as possible, avoid unnecessary 

bending.

Liner Requirements:

Vertical Height Min. = 10 ft. (3.1 M)

Vertical height Max. = 35 ft. (10.7 M)

Note: Measured from flue collar on 

unit to the end of the vent pipe or liner

Use 3" (76 mm) diameter listed gas 

vent liner (UL1777 ONLY) for the 

EXHAUST

Use 3" (76 mm) diameter listed 

liner (UL 181 or UL1777) for the 

AIR INTAKE.

The flexible vent pipe 

must NOT be allowed to 

sag behind  insert or in 

fireplace flue.

Make sure that both liners will pass through existing damper area. Remove 

or lock damper to allow the passage of the flexible liners. If the damper 

will not allow the passage of both liners, DO NOT PROCEED FURTHER.  

(If fireplace is masonry) Consult a local mason for removal of the damper 

without risk of structural damage or leakage (if the fireplace is factory 

built) The appliance may NOT be installed into the fireplace.

Figure 6b

        

WARNING

Direct-Vent Fireplace Insert Vent Requirements - Use liner 

listed to UL181 (Factory-made Air Ducts And Air Connec-

tors) or UL1777 (Chimney Liners) for the AIR INTAKE.  Use 

liner listed to UL1777 ONLY for the EXHAUST.
Do not substitute the heat-rated flex liner (UL1777) for the 

exhaust with any other type liner or a fire may result caus-

ing property damage, personal injury or loss of life.

The standard cap in Termination Kit TKDVI, and in 
Vent Kit DV3FK35

 

is a high wind cap

Vent Kits 

Cat. No.

Model

Description

H0909

FKDVI

Flex Liner Kit, DVI 3” X 35’ (requires 2, one for 
exhaust and one for intake)

TKDVI

TKDVI

Termination Kit, DVI (termination cap and flashing)

DV3FK35 DV3FK35 Flex Liner and Termination Kit, 3" X 35' (includes 2 

flex liners, termination and gear clamps)

INSTALLATION

Содержание SDVI and operation

Страница 1: ...ment o vous trouvez Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des inc...

Страница 2: ...ibles 9 Insert Leveling 9 Installation 10 12 Venting Installation 10 Zero Clearance Fireplace Installation 11 Log Set Installation 11 Surround Panels Installation 12 Face Installation 12 Gas Line Inst...

Страница 3: ...ler service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change to...

Страница 4: ...not be connected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance i...

Страница 5: ...uel Gas Code and local zoning and code authorities for details on installation requirements Mobile home installations must conform with the Mobile Home Con struction and Safety Standard Title 24 CFR P...

Страница 6: ...ess than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS NEW YORK CITY NEW YORK MEA Certification Gas appliances must be tes...

Страница 7: ...y Packaging List 1 Insert Body with Burner Cassette 1 Log Set 1 Bag of Embers 1 Fasteners 6 slotted 1 4 truss screws 6 speed nuts 9 spring clips 3 plastic adhesive wire restraints 1 Installation and O...

Страница 8: ...wood or synthetic logs Have the chimney and all inside surfaces of the fire place brushed and vacuumed so that no soot embers or loose combustion deposits can be drawnintotheheatcirculationblowerandbl...

Страница 9: ...TO COMBUSTIBLES Minimum clearances include any projections such as shelves window sills mantels spacers standoffsorsurfacestocombustibleconstruction etc above the appliance Paint or lacquer used to fi...

Страница 10: ...f an odor during the first hour of operation Venting Installation Your Superior gas insert must be vented to the outside in accordance with the current edition of the National Fuel Gas Code ANSI Z223...

Страница 11: ...iqu ne comporte pas d orifices d amen e du gaz un orifice d au plus 37 5 mm 1 5 po peut tre pratiqu selon les r gles de l art dans la partie inf rieure des parois ou au fond de la chambre de combustio...

Страница 12: ...ets on the surround brackets per instructions provided in decorative face kit C in Figure 12 Figure 12 A B C Spring Handle Latches Door Mounting Plates 4 Fasten top surround panel with the remaining t...

Страница 13: ...ck the pressure Again close the tap gently but securely after completing the check Check the taps for gas leaks with a gas leak test solution retighten if necessary If the pressure is not sufficient m...

Страница 14: ...ILLUSTRATIONS ARE NOT TO SCALE Moving shutter bracket to the right will open shutter to the left will close shutter Figure 14 Figure 15 SHUTTER ADJUSTMENT DETAIL See Detail Shutter Adjustment Shutter...

Страница 15: ...ermostat mural voir Figure B et le cas ch ant sur le bo tier delat l commande FigureC Pouracheverl instal lationcorrectedecefoyer proc dezcommesuitavec les tiquettesadh sivesenlangues trang resfournie...

Страница 16: ...quipped with a piezo ignition device to light the pilot When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell around the appliance area for gas Be sure to smell next to the...

Страница 17: ...aches operating temperature TO TURN OFF GAS TO APPLIANCE 1 Turn off the ON OFF rocker switch and or thermostat if installed to its lowest setting 2 Turn off electric power to the appliance if service...

Страница 18: ...he gas valve and orifice may make a rushing or whistling noise If this noise is objectionable it can be reduced by turning down the flame Turning down the flame can reduce total heat output by more th...

Страница 19: ...ches to the insert for example a rocker switch and a wall thermostat Additional switches may affect the system resistance and increase the chance of the burner not igniting Follow the instructions inc...

Страница 20: ...EVER ADJUST THE PILOT untilafterthegaspressurehasbeencheckedandthesupplylineshave been completely bled this may take an hour or more when bleeding through the pilot All pilots are checked and burned a...

Страница 21: ...lable from your Lennox Hearth Products dealer Do not use substitute parts or materials The glass is neo ceramic and alterna tive types must not be used NOTE BE CAREFUL NOT TO SPRAY COMMERCIAL GLASS CL...

Страница 22: ...wer and then lift the panel with the blower attached out of the firebox To reinstall the blower repeat these steps in the reverse order Figure 21 Blower Wiring Schematic Green Ground Black Hot From Po...

Страница 23: ...f pilot lights turn off pilot and trigger the igniter again If pilot lights an intermittent gas air supply may be the problem if longer purge will not light check gap between electrode and pilot shoul...

Страница 24: ...ontrol rheostat H5744 On Off Switch H6007 On Off Switch Wires H5745 Piezo Igniter H4635 Wall Thermostat Digital H5660 Power Cord ref form 506033 04 H5977 Blower Wire H5730 Speed Control Wire for rheos...

Страница 25: ...are the part numbers of the instruction sheets included in kits Face Surround Panel Kits Required Includes Black Face Surround and Black Trim Cat No Model Description H7014 SDVI A B Arched Black Face...

Страница 26: ...areil aux combustibles HOMOLOGU FOYER RADIANT PR FABRIQU AU GAZ INSERTION DE FOYER AU GAZ NE PAS UTILISER AVEC DU COMBUSTIBLE SOLIDE TEST SELON LA NORME ANSI Z21 88 2005 CSA 2 33 2005 FOYER RADIANT AU...

Страница 27: ...agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un conduit d vacuation vous pourriez risquer d tre empoisonn au monoxyde de carbone CO ce...

Страница 28: ...ur other documents for future refer ence Product reference information We recommend that you record the following important information about your appliance Please contact your LHP dealer for any ques...

Отзывы: