NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

6

COLD CLIMATE INSULATION

For cold climate installations, seal all cracks 
around the appliance with noncombustible 
material and wherever cold air could enter 
the room. It is especially important to insulate 
outside chase cavity between studs and under 
fl oor on which the appliance rests, if fl oor is 
above ground level.  Gas line holes and other 
openings should be caulked or stuffed with 
unfaced fi berglass insulation. If the fi replace 
is being installed on a cement slab, in cold 
climates, a sheet of plywood or other raised 
platform can be placed underneath to prevent 
conducting cold up into the room. It also helps to 
sheetrock inside surfaces and tape for maximum 
air tightness and caulk fi restops.

LOCATION

In selecting the location, the aesthetic and func-
tional use of the appliance are primary concerns. 
However, vent system routing to the exterior 
and access to the fuel supply are also important. 
Consideration should be given to traffi c ways, 
furniture, draperies, etc., due to elevated surface 
temperatures (

Figure 3

).

 The location should 

also be free of electrical, plumbing or other 
heating/air conditioning ducting.

These direct vent appliances are uniquely 
suited for installations requiring a utility shelf 
positioned directly above the fi replace. Utility 
shelves like these are commonly used for locat-
ing television sets and decorative plants. 

Be 

aware that this is a heat producing appliance. 
Objects placed above the unit are exposed to 
elevated temperatures.

To provide for the lowest possible shelf surface 
use the alternate rear vent outlet with attached 
venting routed in a way to minimize obstructions 
to the use of the space above the appliance. 

Do 

not insulate the space between the appliance 
and the area above it. See

 Figure 8

.

 The mini-

mum height from the base of the appliance to 
the underside of combustible materials used to 
construct a utility shelf in this fashion is shown 
in the Table in 

Figure 8

.  

The appliance should be mounted on a fully 
supported base extending the full width and 
depth of the unit. The appliance may be located 
on or near conventional construction materials. 
However, if installed on combustible materials, 
such as carpeting, vinyl tile, etc., a metal or 
wood barrier covering the entire bottom surface 
must be used.

N

O

I

T

A

C

I

L

P

P

A

 

T

N

E

V

 

R

A

E

R

N

O

I

T

A

C

I

L

P

P

A

 

T

N

E

V

 

P

O

T

 APPLICATION

TOP VENT

T

N

E

R

A

E

R

N

OI

T

A

CI

L

P

P

T

N

E

P

O

T

N

OI

T

A

CI

L

P

P

RECESSED

INSTALLATION

TOP VENT

 APPLICATION

N

OI

T

A

CI

L

P

P

T

N

E

P

O

T

N

OI

T

A

CI

L

P

P

T

N

E

P

O

T

(Rear Vent

VERTICAL VENT

 Application)

(Rear Vent Application

HORIZONTAL VENT

 without a chase)

HORIZONTAL VENT
(Rear Vent Application
With a chase)

HORIZONTAL VENT
(Top Vent
 Application)

VERTICAL VENT
(Top Vent

Application)

Figure 3

 - 

Typical Locations

Содержание SDDV-35

Страница 1: ...OUR SAFETY What to do if you smell gas DO NOT light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone...

Страница 2: ...mponents are labeledforidentification DONOTuseanyother manufacturer s vent components with these appliances Use only the correct size venting 4 1 2 inner 7 1 2 outer These appliances comply with Natio...

Страница 3: ...eld converted Inlet Gas Supply Pressure all models Fuel Minimum Maximum Natural Gas 5 0 WC 1 24 kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4...

Страница 4: ...rizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection T...

Страница 5: ...n SeeMaintenanceinstructionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have the...

Страница 6: ...thesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide for the l...

Страница 7: ...2 1 2 64 mm or less See Figure 5 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 6 on Page 8 Figure 5 Side Elevation View Note See Figure...

Страница 8: ...15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm 3 feet 91 cm J Clearanc...

Страница 9: ...inimum Distance to Unprotected Side Wall Top View of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figu...

Страница 10: ...eld Wiring a MillivoltAppliances Theoperatingcontrol switch is factory installed b Electronic Appliances Connect 120 VAC electrical power to the appliance recep tacle Step 5 Page 25 Install blower kit...

Страница 11: ...8 1019 37 1 8 943 24 610 34 1 2 876 40 1 8 1019 27 1 2 698 26 1 2 675 13 3 4 337 G H Top View Co Axial Direct Vent Pipe Collars Top Rear Vent Flue Outlet 4 1 2 114 Combustion Air 7 1 2 190 275 FRAMING...

Страница 12: ...under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can result in sooting severe delayed ignition o...

Страница 13: ...ve and discard the vent cover plate Reinstall and securely tighten all four cover plate screws Reinstall the lintel cover plate When the rear vent is being used from inside thefirebox removethetwoscre...

Страница 14: ...0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1...

Страница 15: ...lectinglengthcombinations Elbows areavailablein90 and45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent sec...

Страница 16: ...t the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of...

Страница 17: ...WhenusingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When usin...

Страница 18: ...048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max Table C H H1 Maximum HMaximum V Minimum feet meter feet meter feet meter 5 1 524 2 0 610 1 0 305 10...

Страница 19: ...ureVent useSV4 5VFfirestop spaceratceilingjoists whenusingSecureFlex use SF4 5VF firestop spacer If there is living spaceabovetheceilinglevel thefirestop spacer must be installed on the bottom side of...

Страница 20: ...ing of the Horizontal Square Termination SV4 5HT 2 SeeFigure13 onPage 11 for Min Distance to Base of Appliance For thicknesses greater than 10 see Table 12 I Continue installation of horizontal inclin...

Страница 21: ...ES H H 28 in 711 mm Maximum 7 in 178 mm When using Secure Flex use Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF H Wall Firestop Spacer SV4 5HF V When using Secure Flex use Firestop Spacer SF4...

Страница 22: ...Example If 20 feet of H H1 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 fe...

Страница 23: ...e 12 on Page 21 as an aid in venting component selection for a particular range of exte rior wall thicknesses Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum of V verti...

Страница 24: ...inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1 3 4 inches from the end and that it is free...

Страница 25: ...power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the control within th...

Страница 26: ...BLACK BL BLUE R RED W WHITE G GREEN BK W BK BK BL R GROUND 24 V Transformer View A J Box Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which...

Страница 27: ...mpartment access door Removing Control Compartment Door Openthedoorby gentlyliftingitupwarduntilthe hook catches on boths sides clear the locating slots Then pull door out to remove D Turn on burner t...

Страница 28: ...ogs have locating notches which cor respond to locating brackets and holes which correspond to locating pins to help ensure that they are properly positioned Proper log placement is critical to preven...

Страница 29: ...g Installation Instructions refer to Figure 52 Carefully position the ceramic fiber logs into the firebox as shown here Logs should be placed in the order shown and per the following instructions 1 Se...

Страница 30: ...G The glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to...

Страница 31: ...Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avoid injury while adjusting f...

Страница 32: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Страница 33: ...12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV4 5HRK36 Hor...

Страница 34: ...ed exactly a fire explosion or produc tion of carbon monoxide may result causing property damage personal injury or loss of life The installation is not proper and complete until the operation of the...

Страница 35: ...rtoFigure59 andremovethepilot hood assembly to access the hexed pilot orifice Remove and replace the orifice with the one provided with the kit Pilot for SIT Millivolt Gas Valve Figure 59 Pilot Orific...

Страница 36: ...move the orifice from the manifold and replace it with the one provided in the kit See Table 14 for orifice sizes fornaturalandpropanemodels Figure 61 illustrates the orifice b Retrievetheburnerandhol...

Отзывы: