Burner Orifi ce Sizes 

Elevation 0-4500 feet ( 0-1372 meters)

Model
Series

Natural

Gas

drill size 

(inches)

Propane

Gas

drill size (inches)

SDDV-35

#40 (.098") 

*

69L96 •

#53 (.0595") 

*

39L10 •

SDDV-40

#36 (.1065") 

*

18L40 •

#52 (.0635")

*

LB-55874D •

* Standard size installed at factory
•  Part /Cat. Number

Table 14

Figure 62

Note: If the Igniter is damaged, a replacement kit is available - order Catalog Number 87L54.

Figure 61 -

 Burner Orifi ce

All Models

Step 8.  (Refer to 

Figure 57 on Page 35)

a.  Remove  the orifi ce from the manifold 

and replace it with the one provided in 
the kit. See 

Table 14 

 for orifi ce sizes 

for natural and propane models

. Figure 

61 

 illustrates the orifi ce. 

b.  Retrieve the burner and hold the venturi 

tube  above the orifi ce . Place the shut-
ter adjusting rod in the propane slot 
of the shutter arm (see 

Figure 55 on 

Page 31)

.  Set the burner assembly into 

its position and secure the trapezoidal 
plate with the two screws previously 
removed.

c.  Reinstall the baffl e with the two baffl e 

securing screws. 

Step 9

.  Reassemble all removed components 

by reversing the procedures outlined 
in the preceding steps.  Use pipe joint 
compound or Tefl on tape on all pipe 
fi ttings before installing (ensure pro-
pane resistant compounds are used in 
propane applications, do not use pipe 
joint compounds on fl are fi ttings).

Step 10

.  Attach the conversion label provided in 

the conversion kit to the rating plate on 
the appliance.

Step 11

.Turn on gas supply and test for gas 

leaks.

Pilot Assembly

Igniter Assembly

Retaining Clip

Pilot Orifi ce

Flare Nut

Содержание SDDV-35

Страница 1: ...OUR SAFETY What to do if you smell gas DO NOT light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone...

Страница 2: ...mponents are labeledforidentification DONOTuseanyother manufacturer s vent components with these appliances Use only the correct size venting 4 1 2 inner 7 1 2 outer These appliances comply with Natio...

Страница 3: ...eld converted Inlet Gas Supply Pressure all models Fuel Minimum Maximum Natural Gas 5 0 WC 1 24 kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4...

Страница 4: ...rizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection T...

Страница 5: ...n SeeMaintenanceinstructionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have the...

Страница 6: ...thesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide for the l...

Страница 7: ...2 1 2 64 mm or less See Figure 5 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 6 on Page 8 Figure 5 Side Elevation View Note See Figure...

Страница 8: ...15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm 3 feet 91 cm J Clearanc...

Страница 9: ...inimum Distance to Unprotected Side Wall Top View of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figu...

Страница 10: ...eld Wiring a MillivoltAppliances Theoperatingcontrol switch is factory installed b Electronic Appliances Connect 120 VAC electrical power to the appliance recep tacle Step 5 Page 25 Install blower kit...

Страница 11: ...8 1019 37 1 8 943 24 610 34 1 2 876 40 1 8 1019 27 1 2 698 26 1 2 675 13 3 4 337 G H Top View Co Axial Direct Vent Pipe Collars Top Rear Vent Flue Outlet 4 1 2 114 Combustion Air 7 1 2 190 275 FRAMING...

Страница 12: ...under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can result in sooting severe delayed ignition o...

Страница 13: ...ve and discard the vent cover plate Reinstall and securely tighten all four cover plate screws Reinstall the lintel cover plate When the rear vent is being used from inside thefirebox removethetwoscre...

Страница 14: ...0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1...

Страница 15: ...lectinglengthcombinations Elbows areavailablein90 and45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent sec...

Страница 16: ...t the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of...

Страница 17: ...WhenusingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When usin...

Страница 18: ...048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max Table C H H1 Maximum HMaximum V Minimum feet meter feet meter feet meter 5 1 524 2 0 610 1 0 305 10...

Страница 19: ...ureVent useSV4 5VFfirestop spaceratceilingjoists whenusingSecureFlex use SF4 5VF firestop spacer If there is living spaceabovetheceilinglevel thefirestop spacer must be installed on the bottom side of...

Страница 20: ...ing of the Horizontal Square Termination SV4 5HT 2 SeeFigure13 onPage 11 for Min Distance to Base of Appliance For thicknesses greater than 10 see Table 12 I Continue installation of horizontal inclin...

Страница 21: ...ES H H 28 in 711 mm Maximum 7 in 178 mm When using Secure Flex use Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF H Wall Firestop Spacer SV4 5HF V When using Secure Flex use Firestop Spacer SF4...

Страница 22: ...Example If 20 feet of H H1 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 fe...

Страница 23: ...e 12 on Page 21 as an aid in venting component selection for a particular range of exte rior wall thicknesses Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum of V verti...

Страница 24: ...inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1 3 4 inches from the end and that it is free...

Страница 25: ...power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the control within th...

Страница 26: ...BLACK BL BLUE R RED W WHITE G GREEN BK W BK BK BL R GROUND 24 V Transformer View A J Box Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which...

Страница 27: ...mpartment access door Removing Control Compartment Door Openthedoorby gentlyliftingitupwarduntilthe hook catches on boths sides clear the locating slots Then pull door out to remove D Turn on burner t...

Страница 28: ...ogs have locating notches which cor respond to locating brackets and holes which correspond to locating pins to help ensure that they are properly positioned Proper log placement is critical to preven...

Страница 29: ...g Installation Instructions refer to Figure 52 Carefully position the ceramic fiber logs into the firebox as shown here Logs should be placed in the order shown and per the following instructions 1 Se...

Страница 30: ...G The glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to...

Страница 31: ...Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avoid injury while adjusting f...

Страница 32: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Страница 33: ...12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV4 5HRK36 Hor...

Страница 34: ...ed exactly a fire explosion or produc tion of carbon monoxide may result causing property damage personal injury or loss of life The installation is not proper and complete until the operation of the...

Страница 35: ...rtoFigure59 andremovethepilot hood assembly to access the hexed pilot orifice Remove and replace the orifice with the one provided with the kit Pilot for SIT Millivolt Gas Valve Figure 59 Pilot Orific...

Страница 36: ...move the orifice from the manifold and replace it with the one provided in the kit See Table 14 for orifice sizes fornaturalandpropanemodels Figure 61 illustrates the orifice b Retrievetheburnerandhol...

Отзывы: