NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

13

Figure 17a

Figure 16

Select Venting System - 
Horizontal or Vertical

With the appliance secured in framing, de-
termine vent routing and identify the exterior 
termination location. The following sections 
describe vertical (roof) and horizontal (exterior 
wall) vent applications. Refer to the section 
relating to your installation.

 A list of approved 

venting components is shown on 

Pages 32 

to 34

.

Figure 15

Step 3. INSTALL THE VENT SYSTEM

 

General Information

These instructions should be used as a guide-
line and do not supersede local codes in any 
way. Install vent according to local codes, 
these instructions, the current National Fuel 
Gas Code (ANSI-Z223.1) in the USA or the 
current standards of CAN/CGA-B149.1 and 
-B149.2 in Canada. 

Use only approved venting components.  See 

Approved Vent Components

 on 

Page 2.

These fi replaces must be vented directly 
to the outside.

The vent system may not service multiple 
appliances, and must never be connected to a 
fl ue serving a solid fuel burning appliance. The  
vent pipe is tested to be run inside an enclosing 
wall (such as a chase). There is no requirement 
for inspection openings in the enclosing wall at 
any of the joints in the vent pipe. 

Preparing the Appliance Vent Collar

Each of the unit's two vent collars are sealed 
with a cover plate and a seal cap.  The cover 
plate and seal cap must be removed from the 
cent collar being used.  Refer to 

Figure 15

  for 

top vent usage and 

Figure 16

 

 for rear, and 

the following steps to prepare the appropriate 
collar for use.

From the vent collar being used, remove the 
screw securing the vent seal cap.  Twist the cap 
counterclockwise to disengage it from the vent 
collar.  Remove and discard the seal cap.

When the top vent is being used

, remove the 

lintel cover plate by pushing it back towards 
the rear of the fi replace by its front fl ange.  It 
can then be removed by pulling it forward.  
Loosen the two screws in the keyhole slots of 
the vent cover plate and remove the remaining 
two vent cover plate securing screws.  Remove 
and discard the vent cover plate.  Reinstall and 
securely tighten all four cover plate screws.  
Reinstall the lintel cover plate.

When the rear vent is being used

, from inside 

the fi rebox, remove the two screws securing the 
baffl e to the rear wall of the fi rebox, then remove 
the baffl e.  Loosen the two screws in the keyhole 
slots of the cover plate and remove the remaining 
two cover plate securing screws.  Remove and 
discard the cover plate.  Reinstall and securely 
tighten all four cover plate screws.  Re-secure 
the baffl e to the rear wall of the fi rebox. 

Preparing The Appliance Top Or Rear Vent 
Outlet

When There Is 3 Feet Or More Of Vertical 
Venting, install a vent restrictor (provided) in 
the appliance top or rear fl ue outlet as shown 
in 

Figures 17a & 17b

. It is held in place by 

friction, only.

VENT SEAL CAP

FIREBOX TOP

CABINET TOP

SECURING SCREWS

VENT

COVER PLATE

TOP VENT

TOP VENT SEAL CAP & COVER PLATE

REMOVAL WHEN USING THE TOP VENT

VENT COVER PLATE

SECURING SCREW

CROSS SECTION

(INSIDE UNIT)

(OUTSIDE UNIT)

LINTEL

LINTEL

COVER PLATE

PUSH TO BEGIN REMOVAL

PROCESS OF LINTEL COVER PLATE

VENT SEAL CAP

SECURING SCREWS

CROSS SECTION

BAFFLE

SECURING

SCREWS

BAFFLE

REAR VENT

COVER PLATE

SECURING SCREWS

REAR VENT SEAL CAP & COVER PLATE REMOVAL

WHEN USING THE REAR VENT

CABINET BACK

(INSIDE UNIT)

(OUTSIDE UNIT)

TOP VENT

Restrictor Installation

If 3 ft. or more of vertical venting is used, install 
a vent restrictor in the top vent of the fi replace 
outlet. It can be installed from the inside or 
outside of the unit, in the inner fi replace collar. 
It is held in place by friction only.

Appliance Top

Vent Outlet

Restrictor

Inner
Fireplace
Collar

Inner Fireplace 

Collar

Appliance Rear 
Vent Outlet

Restrictor

REAR VENT

Restrictor Installation

If 3 ft. or more of vertical venting is used, install 
a vent restrictor in the rear vent of the fi replace 
outlet. It can be installed from the inside or 
outside of the unit, in the inner fi replace collar. 
It is held in place by friction only.

Figure 17b

     

WARNING

Failure to reinstall and securely 
tighten cover plate screws could 
result in leakage of fl ue products 
into the living space. Vent cover 
plate and vent seal plate must 
remain securely installed on 
unused vent collar. Failure to do 
so could result in leakage of fl ue 
products into living space.

Содержание SDDV-35

Страница 1: ...OUR SAFETY What to do if you smell gas DO NOT light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone...

Страница 2: ...mponents are labeledforidentification DONOTuseanyother manufacturer s vent components with these appliances Use only the correct size venting 4 1 2 inner 7 1 2 outer These appliances comply with Natio...

Страница 3: ...eld converted Inlet Gas Supply Pressure all models Fuel Minimum Maximum Natural Gas 5 0 WC 1 24 kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4...

Страница 4: ...rizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection T...

Страница 5: ...n SeeMaintenanceinstructionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have the...

Страница 6: ...thesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide for the l...

Страница 7: ...2 1 2 64 mm or less See Figure 5 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 6 on Page 8 Figure 5 Side Elevation View Note See Figure...

Страница 8: ...15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm 3 feet 91 cm J Clearanc...

Страница 9: ...inimum Distance to Unprotected Side Wall Top View of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figu...

Страница 10: ...eld Wiring a MillivoltAppliances Theoperatingcontrol switch is factory installed b Electronic Appliances Connect 120 VAC electrical power to the appliance recep tacle Step 5 Page 25 Install blower kit...

Страница 11: ...8 1019 37 1 8 943 24 610 34 1 2 876 40 1 8 1019 27 1 2 698 26 1 2 675 13 3 4 337 G H Top View Co Axial Direct Vent Pipe Collars Top Rear Vent Flue Outlet 4 1 2 114 Combustion Air 7 1 2 190 275 FRAMING...

Страница 12: ...under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can result in sooting severe delayed ignition o...

Страница 13: ...ve and discard the vent cover plate Reinstall and securely tighten all four cover plate screws Reinstall the lintel cover plate When the rear vent is being used from inside thefirebox removethetwoscre...

Страница 14: ...0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1...

Страница 15: ...lectinglengthcombinations Elbows areavailablein90 and45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent sec...

Страница 16: ...t the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of...

Страница 17: ...WhenusingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When usin...

Страница 18: ...048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max Table C H H1 Maximum HMaximum V Minimum feet meter feet meter feet meter 5 1 524 2 0 610 1 0 305 10...

Страница 19: ...ureVent useSV4 5VFfirestop spaceratceilingjoists whenusingSecureFlex use SF4 5VF firestop spacer If there is living spaceabovetheceilinglevel thefirestop spacer must be installed on the bottom side of...

Страница 20: ...ing of the Horizontal Square Termination SV4 5HT 2 SeeFigure13 onPage 11 for Min Distance to Base of Appliance For thicknesses greater than 10 see Table 12 I Continue installation of horizontal inclin...

Страница 21: ...ES H H 28 in 711 mm Maximum 7 in 178 mm When using Secure Flex use Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF H Wall Firestop Spacer SV4 5HF V When using Secure Flex use Firestop Spacer SF4...

Страница 22: ...Example If 20 feet of H H1 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 fe...

Страница 23: ...e 12 on Page 21 as an aid in venting component selection for a particular range of exte rior wall thicknesses Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum of V verti...

Страница 24: ...inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1 3 4 inches from the end and that it is free...

Страница 25: ...power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the control within th...

Страница 26: ...BLACK BL BLUE R RED W WHITE G GREEN BK W BK BK BL R GROUND 24 V Transformer View A J Box Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which...

Страница 27: ...mpartment access door Removing Control Compartment Door Openthedoorby gentlyliftingitupwarduntilthe hook catches on boths sides clear the locating slots Then pull door out to remove D Turn on burner t...

Страница 28: ...ogs have locating notches which cor respond to locating brackets and holes which correspond to locating pins to help ensure that they are properly positioned Proper log placement is critical to preven...

Страница 29: ...g Installation Instructions refer to Figure 52 Carefully position the ceramic fiber logs into the firebox as shown here Logs should be placed in the order shown and per the following instructions 1 Se...

Страница 30: ...G The glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to...

Страница 31: ...Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avoid injury while adjusting f...

Страница 32: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Страница 33: ...12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV4 5HRK36 Hor...

Страница 34: ...ed exactly a fire explosion or produc tion of carbon monoxide may result causing property damage personal injury or loss of life The installation is not proper and complete until the operation of the...

Страница 35: ...rtoFigure59 andremovethepilot hood assembly to access the hexed pilot orifice Remove and replace the orifice with the one provided with the kit Pilot for SIT Millivolt Gas Valve Figure 59 Pilot Orific...

Страница 36: ...move the orifice from the manifold and replace it with the one provided in the kit See Table 14 for orifice sizes fornaturalandpropanemodels Figure 61 illustrates the orifice b Retrievetheburnerandhol...

Отзывы: