Clearance To Combustibles
It is important to observe minimum clearance to combustibles at all times to avoid any possibility of
property damage or personal injury. Clearances must be maintained from vehicles parked beneath
heaters. Signs should be posted identifying any possible violation of the clearance distances from the
heater in vehicle areas. Also, maximum allowable stacking height in storage areas should be identified
with signs or appropriate markings. Table 2 lists minimum clearance to combustible materials
corresponding to the installation configuration.
Approved reflector configurations include the standard
(with or without decorative grille)
, the 45° tilt
reflector, single and dual side extension shields, standard U tube mounting and opposite 45° U tube
reflector mounting.
Bottom shields are also approved. The “below” clearance dimension for the horizontal configuration
(dimension “C” in Table 2)
may be reduced by 25% when an approved bottom shield is used.
Reduced clearances downstream from the burner are approved for all configurations, except those with
the U-bend. Dimensions “B”, “C”, and “D” can be reduced by 50% for locations 25' feet or more
downstream from the burner box.
Elbows and U-bends are un-heat-treated aluminized material and are typically installed without
reflectors. Clearance to combustibles is 18" inches above and from the end in all cases. When elbows
or U-bends must be reflectored due to the proximity of combustible material, a 90 degree mitered
reflector kit is available from your SRP dealer (part # CR039). Clearances in the case where mitered
reflector kits are used are the same as the previous section of reflector.