FIREPLACE INSTALLATION 

Continued

HEARTH EXTENSION

A hearth extension projecting a minimum of 20" in front of and a 

minimum of 12" beyond each side of fireplace opening is required 

to protect combustible floor construction in front of fireplace. Fabri-

cate a hearth extension using a material which meets the following 

specifications: a layer of noncombustible, inorganic material having a 

thermal conductivity of k=0.84 BTU IN/FT, HR. F (or less) at 1" thick. 

For example, if the material selected has a k factor of 0.25, such as 

glass fiber, the following formula would apply:
 

0.25 x 1.0" = 0.30" thickness required

 0.84
Thermal conductivity "k" of materials can be obtained from manufac-

turer or supplier of noncombustible material. If hearth extension is 

to be covered, use noncombustible material such as tile, slate, brick, 

concrete, metal, glass, marble, stone, etc. Provide a means to prevent 

hearth extension from shifting and seal gap between fireplace frame 

and hearth extension with a noncombustible material (see Figure 8). 

 WARNING: Hearth extension is to be installed only 

as shown in Figure 8.

Figure 8 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front Raised 

Hearth

Fireplace Front Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth 

Extension

MANTELS

A mantel may be installed if desired (see Figure 9). Woodwork such 

as wood trims, mantels or any other combustible material projecting 

from front face must not be placed within 12" of the fireplace (NFPA 

211, Section - Clearance from Combustible Material).
Mantels or any other combustible material also may come up to side 

edge of black metal face of fireplace as long as projections from front 

face fall within limit shown in Figure 9.

Figure 9 - Mantel Clearances to Combustible Materials

Finished Wall
Header

Noncombustible

Wall Covering

Fireplace Opening

Combustible

Mantel

Spacer

 

*

 A 1-1/2

"

 Projection Is Permitted

Between The Face Top And Mantle

*

12

"

(305 mm)

Min.

12

"

(305 mm)

Max.

4-17/32

"

(115 mm)

30˚

Combustible Materials

Allowed in Shaded Area

1/2

"

(13 mm)

12

"

 (305 mm)

Minimum Distance

to Protected Side Wall

Содержание WRT3538WH

Страница 1: ...60 or Z21 84 standards or for use with a vent free gas log heater approved to ANSI Z21 11 2 standard FOR CANADA The authority having jurisdiction such asthemunicipalbuildingdepartment firedepartment...

Страница 2: ...vicinity of this or any other appliance Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Do not place clothing or other flammable materials...

Страница 3: ...s and troubleshooting WARNING BURNINGIMPROPERFUEL I E CHAR COAL CAN RESULT IN CARBON MONOXIDE POISON ING WHICH MAY LEAD TO DEATH Carbon Monoxide Poisoning Early signs of carbon monoxidepoisoningresemb...

Страница 4: ...assist you in selecting the proper venting system for your installation American National Standards Institute ANSI NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appli ances Se...

Страница 5: ...and the traffic flow in the room where the appliance is located allowing space in front of the unit for the hearth extension and the mantel and taking into consideration the locationofthehotairducts s...

Страница 6: ...1 2 292 mm 24 5 8 626 mm 8 204 mm 12 3 8 315 mm 15 381 mm 5 8 16 mm 1 26 mm CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL 1 26 mm AIR SPACE BACK AND SIDES 0 0 mm TO BOTTOM GAS LINE KNOCKOUT 12 30...

Страница 7: ...elbow set Maximum distance between elbows is 6 feet For systems with two elbow sets minimum height is 22 feet Maximum height of any system is 50 feet This measurement includes fireplace chimney secti...

Страница 8: ...raming Face Unfinished Shown Corner Installation AK4 Combustion Air Kit Figure 6 Corner Installation Figure 5 Inside Chase Figure 7 Outside Chase Figure 4 Fireplace Framing Fireplace Opening Width 38...

Страница 9: ...seal gap between fireplace frame and hearth extension with a noncombustible material see Figure 8 WARNING Hearth extension is to be installed only as shown in Figure 8 Figure 8 Hearth Extension Seal G...

Страница 10: ...e sections must be assembled independently as the chimney is installed When connect ing chimney directly to the fireplace the inner flue pipe section must be installed first with the lanced side up Th...

Страница 11: ...t be secured with two screws on the outer pipe only see Figure 12 Do not penetrate the inner stainless Figure 13 Ceiling Support Pipe 12S 12DM CAUTION THE STRUCTURAL INTEGRITY OF THE MANUFACTUREDHOMEF...

Страница 12: ...imble FST10 is required to avoid intrusion by insu lation and recommended to negotiate a joist Firestop Thimble FST10 Figure 16a Firestop Thimble PENETRATING ROOF To maintain a 1 clearance to the pipe...

Страница 13: ...HROUGH FLASHING CONE Installing Flashing on a Metal Roof When installing the flashing on a metal roof it is required that putty tape be used between the flashing and the roof The flashing must be secu...

Страница 14: ...termination to another We suggest that terminations be separated at least 24 center to center and stacked at a vertical height difference of 18 see Figure 21 Note If a decorative shroud is to be inst...

Страница 15: ...nd place flash ing over chase 4 Secure flashing through sides with 8 penny nails or sheet rock screws 5 Place galvanized sleeve through hole in flashing and around last section of chimney see Figure 2...

Страница 16: ...lvanized steel over chimney outlet see Figure 31 6 Attach storm collar where chimney pierces opening in flash ing Caulk where storm collar touches outer chimney pipe see Figure 31 NONCHASE INSTALLATIO...

Страница 17: ...ut lines line up Install the retaining bracket and tighten set screws Figure 33 4 Install the right and left refractory panels with the gas line knock outs oriented down toward the firebox bottom Inst...

Страница 18: ...and flush with the front of the fireplace Be careful not to pinch your fingers between the panel and firebox Figure 36 Note If replacing entire kit start with the masonry brick hearth panel then foll...

Страница 19: ...Side Brick with Access Hole Outside of Fireplace Gas Line Conduit Insulation Gas Conduit Cover 1 2 Dowel Remove Knockout Gas line hook up should be done by your supplier or a qualified service person...

Страница 20: ...ING This kit is to be installed by a qualified service technician or other qualified agency in accordance with the manufacturer s instructions and all codes and requirements of the Authority Having Ju...

Страница 21: ...Both the flue damper and glass doors must be fully opened before starting fire This will provide sufficient combustion air and maintain safe temperatures in firebox IMPORTANT The glass must be allowed...

Страница 22: ...lit logs split wood will light more quickly Arrange the logs to provide plenty of air space between them 5 Light the paper at both sides of the firebox 6 Close the screens to prevent the escape of spa...

Страница 23: ...s fireplace may be used if installed in accordance with the instructions by its manufacturer A locally fabricated shroud may be used with IHP Shroud Leg Spacer Kit SLK in accor dance with instructions...

Страница 24: ...2 3 5 6 7 8 2 9 2 11 12 13 20 2 14 3 15 21 16 22 17 23 26 25 27 28 29 31 2 32 2 30 33 2 34 24 18 19 10 4 MODEL CATALOG NO WRT3538WS F3412 WRT3538WH F3413 WRT4038IS F3414 WRT4038IH F3415 WRT3543WS F34...

Страница 25: ...nduit Gas Line LBRS 2 10 Insulation Dome 1 11 Assembly Dome LBR38 1 Assembly Dome LBR43 1 12 Assembly Lintel Extension LBR38 1 Assembly Lintel Extension LBR43 1 13 J4359 Bracket Damper Rod 1 14 See Pa...

Страница 26: ...t 38 White Stk Refractory Panels F3434 Kit 38 White HB Refractory Panels F3437 Kit 43 White Stk Refractory Panels F3438 Kit 43 White HB Refractory Panels CATALOG NO DESCRIPTION F3435 Kit 38 Ivory Spli...

Страница 27: ...tory 3 KEY NO CAT NO DESCRIPTION 38 Split Stk 43 Split Stk 38 Split HB 43 Split HB QTY 1 F3435 Kit 38 Ivory Split Stk Masonry Panels 1 2 Assembly Hearth Cut LBR38 Ivory 1 3 Assembly Panel Left Cut Ivo...

Страница 28: ...54 18 12HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0955 24 12HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0956 36 12HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0957 48 12HT 48 Sectio...

Страница 29: ...Louvered Screen FIRESTOP THIMBLE F0944 FST10 Firestop Thimble LABEL UL127 50PK WARNING HOT Fire Risk Insulation and combustibles must not touch pipe Consult manual for clearance requirements Ensure pr...

Страница 30: ...__________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Страница 31: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 32: ...0855 00 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Отзывы: