background image

SuperiorFireplaces.us.com

127020-01_E

11

Figure 15 - Termination

Attach Bracket Tabs to 

Outer Pipe (3 Places) 

Secure with Screws

RLT-8DM

Level of Flue 

Gas Outlet

Caulk

Collar

Flashing

Underlap Shingles 

Bottom Only

Overlap Shingles 

Top and Sides

Figure 16 - Multiple Chase Installation

CHASE INSTALLATIONS

Instructions for chase installations are included with the chase style 

termination chosen. In a multiple chase installation, be sure to provide 

adequate distance between terminations to prevent smoke spillage 

from one termination to another. We suggest that terminations be 

separated at least 24", center to center and stacked at a vertical height 

difference of 18" (see Figure 16).

Note: 

If a decorative shroud is to be installed, contact the manufac-

turer for specifications.

10 FOOT RULE

All flue gas outlet chimney terminations must extend a minimum of 

3 feet in height above the highest point where it passes through the 

roof and must be at least 2 feet above the highest point of the roof 

that is within a horizontal distance of 10 feet (see Figure 17).

FINISHING FIREPLACE

Combustible materials, such as wallboard, sheet rock, drywall, ply-

wood, etc. may make direct contact with sides and top around the 

fireplace face. It is important that combustible materials do not overlap 

the face itself. Brick, glass, tile or other noncombustible materials 

may overlap the front face provided they do not obstruct essential 

openings like louvered slots or any other opening. When overlapping 

with a noncombustible facing material, use only noncombustible 

mortar or adhesive.

VENTING INSTALLATION

  

Continued

Figure 17 - 10 Foot Rule

Figure 18 - Typical Residential Installations

10

'

(3.05 m) 

10

'

(3.05 m) 

2

(0.61 m)

Min.

2

(0.61 m) Min.

3

(0.92 m)

Min.

3

(0.92 m)

Min.

Level of 

Flue Gas Outlet 

24" (610 mm)Min.

24" (610 mm)Min.

18" 

(458 mm)

Min. Typ.

EFFECTIVE HEIGHT

OF TERMINATION CAP 

EFFECTIVE HEIGHT

OF TERMINATION CAP 

EFFECTIVE HEIGHT

OF TERMINATION CAP 

EFFECTIVE HEIGHT

OF TERMINATION CAP 

30E-8DM

30E-8DM

UP TO 

6 FT (1.83 m)

MAX.

UP TO 

6 FT (1.83 m)

MAX.

14.5 FT 

(4.42 m)

MINIMUM 

HEIGHT

14.5 FT 

(4.42 m)

MINIMUM 

HEIGHT

MAX. HEIGHT

50 FT (15.24 m)

ANY SYSTEM

MIN. HEIGHT OF

22 FT. (6.71 m) WITH 

2 ELBOW SETS

MAX. HEIGHT OF

50 FT. (15.24 m)

Содержание WRE3036WH

Страница 1: ...ADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L au...

Страница 2: ...Venting Installation 7 Optional Gas Line Installation 12 Operation and Maintenance Guidelines 13 Technical Service 14 Replacement Parts 14 Important Notices Canada 15 Parts 16 Accessories 18 Draft Sm...

Страница 3: ...canposeasignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNINGIMPROPERFUEL I E CHAR COAL CAN RESU...

Страница 4: ...9 mm 29 737 mm 41 1042 mm 1 26 mm 1 26 mm 21 534 mm 8 204 mm 35 889 mm 37 940 mm 41 1042 mm 1 26 mm AIRSPACE TO COMBUSTIBLE MATERIAL 0 0 mm TO TOP SPACERS 0 0 mm TO BOTTOM 8 204 mm EACH SIDE NO COMBUS...

Страница 5: ...air kit is available with this fireplace see Optional Outside Air Kit on page 7 MINIMUM CLEARANCE TO COMBUSTIBLES Ceiling 40 1016 mm minimum Back and sides of fireplace 3 4 19 mm minimum Floor 0 0 mm...

Страница 6: ...concrete metal glass marble stone etc Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a noncom bustible material see F...

Страница 7: ...ability to individual site requirements Actual lengths gained after fitting overlaps must be taken into consideration lineal gain and are given in the lineal gain chart see Figure 6 Lineal gain is the...

Страница 8: ...ht above offset rests on return elbow Straps must be securely nailed to rafters or joists see Figure 8 details A and B 3 Maximum length of pipe between supports return elbow or 12S 8DM is 6 of angle r...

Страница 9: ...lowasshowninFigure10 They also provide complete separation from one floor space to another or attic space as required by most codes When the double wall pipe passes through a framed opening into an at...

Страница 10: ...ny shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 13 DO NOT NAIL THROUGH FLASHING CONE Installing Flashing on a Metal Roof When in...

Страница 11: ...of that is within a horizontal distance of 10 feet see Figure 17 FINISHING FIREPLACE Combustible materials such as wallboard sheet rock drywall ply wood etc may make direct contact with sides and top...

Страница 12: ...d connections must be tested for leaks after the installation is completed After ensuring that the gas valve is on apply soap and water solution to all connections and joints Bubbles formingshowaleak...

Страница 13: ...of the appliance imme diately if doors are damaged and contact a qualified installer for repair Only doors certified with the ap pliance shall be used WARNING Do not slam or strike doors Damage can r...

Страница 14: ...through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the fireplace...

Страница 15: ...all Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT...

Страница 16: ...SuperiorFireplaces us com 127020 01_E 16 PARTS 9 24 16 31 25 16 4 30 32 19 12 23 20 28 17 8 1 5 21 2 18 11 14 3 13 22 10 6 29 7 33 34 26 27 15 MODEL CATALOG NO WRE3036WS F0449 WRE3036WH F0450...

Страница 17: ...5 Damper Can Collar 1 16 J8012 Kit Screen Assembly 1 17 Firebox Top Assembly 1 18 J3980 Air Kit Door Assembly 1 19 Face Weldment 1 20 J4470 Air Deflector 1 21 Fireplace Top Insulation 1 22 J4052 Acces...

Страница 18: ...Her White S36 1 4 Refractory Rear Her White S36 1 5 Refractory Btm Rear White S36 1 6 Refractory Btm Frnt White S36 1 1 2 4 3 6 5 Stacked Refractory Shown ACCESSORIES REFRACTORY STAIN KITS Use the re...

Страница 19: ...ection Hi Temp Double Wall Pipe Snap Lock F0882 18 8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double W...

Страница 20: ...F0921 ETL 8DM Square Top with Slip Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SL...

Страница 21: ...electing the proper venting system for your installation American National Standards Institute ANSI NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appli ances See Draft Section...

Страница 22: ...ance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of...

Страница 23: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 24: ...7020 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Отзывы: