5

FIREPLACE INSTALLATION

4.  Check the level of the fireplace and shim with sheet metal if neces-

sary.

5.  Before securing fireplace to prepared framing, the ember protector 

(provided) must be placed between the hearth extension (not sup-

plied) and under bottom front edge of fireplace to protect against 

glowing embers falling through. If fireplace is to be installed on a 

raised platform, a Z-type ember protector (not supplied) must be 

fabricated to fit your required platform height. The ember protec-

tor should extend under fireplace a minimum of 1 

1

/

2

". The ember 

protector should be made of galvanized sheet metal (28 gauge 

minimum) to prevent corrosion.

6.  Using screws or nails, secure fireplace to framing through flanges 

located on sides of fireplace.

DRAIN PAN (DP36)

For outdoor installations, the fireplace enclosure must allow for 

adequate drainage and fresh air ventilation. It is recommended that 

a sealed, corrosion resistant catch pan with provision for drainage 

be installed under the fireplace within the fireplace enclosure (see 

Accessories on page 19).

41 

3

/

4

"

(1061 mm)  

41 

3

/

4

"

(1061 mm)  

21 

7

/

8

"

(556 mm)  

Figure 1 - Framing Dimensions

Figure 2 - Corner Installation

SELECTING LOCATION

 WARNING: DO NOT INSTALL IN SLEEPING ROOM 

OF MOBILE HOMES.

To determine the safest and most efficient location for the fireplace, 

you must take into consideration the following guidelines:
1.  The location must allow for proper clearances (see Figures 1 and 

2).

2.  Consider a location where the fireplace will not be affected by 

drafts, air conditioning ducts, windows or doors.

3.  A location that avoids the cutting of joists or roof rafters will make 

installation easier.

4.  An outside air kit is available with this fireplace (see Optional Outside 

Air Kit on page 7).

MINIMUM CLEARANCE TO COMBUSTIBLES

Ceiling                                                       40" (1016 mm) minimum
Back and sides of fireplace                        3/4" (19 mm) minimum*
Floor** 

 

0" (0 mm) minimum

Perpendicular wall to opening                    12" (305 mm) minimum
Top spacers                                                      0" (0 mm) minimum
Mantel clearances 

 

see Mantels, page 6.

Chimney outer pipe surface 

 

1" (26 mm) minimum

* Not required at nailing flanges

** See step 2 of Framing

 WARNING: Do not pack required air spaces with 

insulation or other materials.

Minimum/Maximum Chimney Height for Residential Installation

The minimum height of the chimney, measured from the base of 

the fireplace to the flue gas outlet of the termination, is 14.5 feet for 

straight flue or a flue with one elbow set. The maximum distance 

between elbows is 6 feet. For systems with two elbow sets, the 

minimum height is 22 feet. The maximum height of any system is 

50 feet. This measurement includes the fireplace, chimney sections 

and the height of the termination assembly at the level of the flue gas 

outlet (see Figure 18, page 11).

Minimum/Maximum Chimney Height for Outdoor Installation

The minimum height of the chimney, measured from the base of the 

fireplace to the flue gas outlet of the termination, is 7 

1

/

2

 feet (minimum 

of 4 feet of chimney pipe sections required for outdoor installation).

FRAMING

1.  Frame opening for fireplace using the dimensions shown in Figures 

1 and 2.

2.  If fireplace is to be installed directly on carpeting, tile or any 

combustible material other than wood flooring, the fireplace must 

be installed upon a metal or wood panel extending the full width 

and depth of fireplace.

3.  Set fireplace directly in front of this opening and slide unit back 

until nailing flanges touch side framing.

Maintain 

3

/

4

Clearance at 

Sides and 

Back of 

Fireplace

   

3

/

4

" Clearance Not 

Required at Nailing Flanges 

  

 24 

1

/

2

(623 mm) 

 52 

1

/

4

(1328 mm) 

 17 

3

/

8

(442 mm) 

 73 

7

/

8

" (1877 mm) 

Содержание WRE3036WH

Страница 1: ...ADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L au...

Страница 2: ...Venting Installation 7 Optional Gas Line Installation 12 Operation and Maintenance Guidelines 13 Technical Service 14 Replacement Parts 14 Important Notices Canada 15 Parts 16 Accessories 18 Draft Sm...

Страница 3: ...canposeasignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNINGIMPROPERFUEL I E CHAR COAL CAN RESU...

Страница 4: ...9 mm 29 737 mm 41 1042 mm 1 26 mm 1 26 mm 21 534 mm 8 204 mm 35 889 mm 37 940 mm 41 1042 mm 1 26 mm AIRSPACE TO COMBUSTIBLE MATERIAL 0 0 mm TO TOP SPACERS 0 0 mm TO BOTTOM 8 204 mm EACH SIDE NO COMBUS...

Страница 5: ...air kit is available with this fireplace see Optional Outside Air Kit on page 7 MINIMUM CLEARANCE TO COMBUSTIBLES Ceiling 40 1016 mm minimum Back and sides of fireplace 3 4 19 mm minimum Floor 0 0 mm...

Страница 6: ...concrete metal glass marble stone etc Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a noncom bustible material see F...

Страница 7: ...ability to individual site requirements Actual lengths gained after fitting overlaps must be taken into consideration lineal gain and are given in the lineal gain chart see Figure 6 Lineal gain is the...

Страница 8: ...ht above offset rests on return elbow Straps must be securely nailed to rafters or joists see Figure 8 details A and B 3 Maximum length of pipe between supports return elbow or 12S 8DM is 6 of angle r...

Страница 9: ...lowasshowninFigure10 They also provide complete separation from one floor space to another or attic space as required by most codes When the double wall pipe passes through a framed opening into an at...

Страница 10: ...ny shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 13 DO NOT NAIL THROUGH FLASHING CONE Installing Flashing on a Metal Roof When in...

Страница 11: ...of that is within a horizontal distance of 10 feet see Figure 17 FINISHING FIREPLACE Combustible materials such as wallboard sheet rock drywall ply wood etc may make direct contact with sides and top...

Страница 12: ...d connections must be tested for leaks after the installation is completed After ensuring that the gas valve is on apply soap and water solution to all connections and joints Bubbles formingshowaleak...

Страница 13: ...of the appliance imme diately if doors are damaged and contact a qualified installer for repair Only doors certified with the ap pliance shall be used WARNING Do not slam or strike doors Damage can r...

Страница 14: ...through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the fireplace...

Страница 15: ...all Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT...

Страница 16: ...SuperiorFireplaces us com 127020 01_E 16 PARTS 9 24 16 31 25 16 4 30 32 19 12 23 20 28 17 8 1 5 21 2 18 11 14 3 13 22 10 6 29 7 33 34 26 27 15 MODEL CATALOG NO WRE3036WS F0449 WRE3036WH F0450...

Страница 17: ...5 Damper Can Collar 1 16 J8012 Kit Screen Assembly 1 17 Firebox Top Assembly 1 18 J3980 Air Kit Door Assembly 1 19 Face Weldment 1 20 J4470 Air Deflector 1 21 Fireplace Top Insulation 1 22 J4052 Acces...

Страница 18: ...Her White S36 1 4 Refractory Rear Her White S36 1 5 Refractory Btm Rear White S36 1 6 Refractory Btm Frnt White S36 1 1 2 4 3 6 5 Stacked Refractory Shown ACCESSORIES REFRACTORY STAIN KITS Use the re...

Страница 19: ...ection Hi Temp Double Wall Pipe Snap Lock F0882 18 8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double W...

Страница 20: ...F0921 ETL 8DM Square Top with Slip Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SL...

Страница 21: ...electing the proper venting system for your installation American National Standards Institute ANSI NFPA 211 Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appli ances See Draft Section...

Страница 22: ...ance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of...

Страница 23: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 24: ...7020 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Отзывы: