Installation
900948-00C, 06/2019
Innovative Hearth Products
DRT2000-C Series Direct-Vent Gas Fireplaces
15
MINIMUM CLEARANCES TO COMBUSTIBLES
Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials
on all sides (Table 8), with the following exception: The unit may not
be recessed (allowance made for mantel legs / side trim in Figure 5).
When the unit is installed with one side flush with a wall, the wall on the
other side of the unit must not extend beyond the front edge of the unit
(Figure 5).
The fireplace must be mounted on a fully supported base extending
the full width and depth of the unit. The fireplace may be located on
or near conventional construction materials. However, if installed on
combustible materials, such as carpeting, vinyl tile or other combustible
material other than wood flooring, the appliance shall be installed on a
metal or wood panel extending the full width and depth of the appliance.
Table 8 - Minimum Clearances *
Back ***
1-1/2” (38mm) to wrapper
0” (0 mm) to Spacers
Sides
1/2” (13 mm) to wrapper
0” (0 mm) to Spacers **
Top Standoffs
0” (0 mm) to top standoffs
Floor
0” (0 mm)
From Bottom of Unit to Ceiling
64” (1626 mm)
Vent
3” (77 mm)—Top *
1” (26 mm)—Sides and Bottom
Front Service Clearance—
clearance immediately in front of
viewing area(s)
36” (914 mm)
*
3” (77 mm) above any horizontal/inclined vent component.
**
See
Page 21
for clearance requirements to the nailing flange
located at each side of the unit and any screw heads adjacent to it.
***
When in top vent mode; no combustible material shall be allowed to
contact the rear flue cap/cover.
Hearth Extension
A hearth extension is not required with this fireplace. Any hearth extension used is for appearance only and does not have to conform to
standard hearth extension installation requirements.
Shelf Height
To provide for the lowest possible shelf surface, use the rear vent model. For top vent models, the venting attached to the top vent should
be routed in a way to minimize obstructions to the space above the fireplace. Do not insulate the space between the fireplace and the
area above it (Tables 9A anc 9B). The minimum height from the base of the fireplace to the underside of combustible materials used to
construct a utility shelf in this fashion is shown in Tables 9A and 9B.
Table 9A- Combustible Shelf Height—Top Vent
Table 9B - Combustible Shelf Height—Rear Vent
* Includes 3” clearance to combustibles (required above vent components)
** In alternative, Rear Vent applications, Top Vent will be sealed as detailed in Installation Sequence
Step 4
(Page 20).
Model
Top Vent with one 90° Elbow *
Secure Vent
®
(using rigid elbow)
Secure Flex
®
(using flex elbow)
35” Models
47” (1194 mm)
49” (1245 mm)
40” Models
52” (1321 mm)
54” (1372 mm)
45” Models
52” (1321 mm)
54” (1372 mm)
CLEARANCES TO COMBUSTIBLES MUST BE MAINTAINED
:
No combustible materials or insulation is permitted in the shaded area
between the appliance and the shelf above it.
WARNING
: CRITICAL INSTALLATION INFORMATION THAT IF NOT FOL-
LOWED CAN RESULT IN A SAFETY HAZARD!
Model
Rear Vent with two 90° Elbows **
Secure Vent
®
(using rigid elbow)
Secure Flex
®
(using flex elbow)
35” Models
36-1/4” (921 mm)
36-1/4” (921 mm)
40” Models
40-1/2” (1029 mm)
40-1/2” (1029 mm)
45” Models
45-1/2” (1156 mm)
45-1/2” (1156 mm)
CLEARANCES TO COMBUSTIBLES MUST BE MAINTAINED
:
No combustible materials or insulation is permitted in the shaded area
between the appliance and the shelf above it.
WARNING
: CRITICAL INSTALLATION INFORMATION THAT IF NOT FOL-
LOWED CAN RESULT IN A SAFETY HAZARD!
Shelf Height
(see table)
Shelf Height
(see table)
≥
3” clearance from shelf to
top of fireplace and/or vent
pipe, whichever is higher