TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
35-EN
Table 6.
Model WBS-A Magna
450
Nominal heat output kW
450
Min. / Max. heat output kW
330÷450
Height H mm
2590
Width L / Depth D mm
1140/2600
Mantle volume L
1300
Combustion chamber volume L
1000
Combustion chamber resistance Pa/mbar
23/0.23
Required chimney draught Pa/mbar
50/0.50
Recommended fuel
wood, wood briquettes; coal
Max. lenght of firewood logs m
1,5
Burning time partial / full load h
5.5/3.5
Operating temperature range /
Max. temperature
°C
65÷85 /95
Exhaust gas temperature
(operation mode)
°C
150÷180
Power consumption
W
760
Power supply
V/Hz
230/50
Operating pressure Bar
4
Weight kg
3100
Cold water inlet A, mm
DN 125/ 500
Hot water outlet B, mm
DN 125/ 1700
Safety line sleeve
К1, mm
К2, mm
DN 50/800
DN 50/1700
Flue gases outlet
F, ø/mm
J, mm
ø 450/2170
570
Flue cleaning opening
O1, mm
O2, mm
1850
1850
Chimney draught flap G
Loading door N, mm
650х700
Inspection door P, mm
1100х1000
Cold water inlet R, mm
890х260
Blower fans T, mm
1450
Main switchboard and controller U
Ocular V
Drain Y, mm
G 1
1/2
”/150
Pellet Burner opening Z
Содержание BURNiT Magna WBS-A 450
Страница 2: ......
Страница 17: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL 17 EN Diagram 6...
Страница 34: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL 34 EN 12 2 Technical parameters...
Страница 37: ...2 TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL...
Страница 38: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL...
Страница 39: ......