background image

 
 

 

 

TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL 

14-EN

by  a  qualified  professional.  The  required  distance  between  the  boiler  and  the 
chimney is 300 - 600 mm. 
 

Recommended chimney dimensions and characteristics

 

Power 

Boiler flue gases exit 

diameter 

Chimney inner cross 

section, diameter 

Effective 

chimney height 

Chimney 

draught 

450 kW 

450 mm 

450 mm 

15 m 

50 Pa 

400 mm 

20 m 

350 mm 

25 m 

 
Table  3.  Interdependence  between  boiler  rated  power  and  chimney  dimensions  and 
characteristics 

 
7.2. Connecting the boiler to the heating installation. 

 

Such  connection  must  be  performed  by  a  technician  /  service  shop 
authorized for such operations. 

 
When the boiler is connected to a heating system, it is mandatory to install a 4 bar 
relief  valve  and  expansion  vessel. No  shut-off  fittings may be installed  between  the 
relief valve, expansion vessel and boiler. 
 

 

It  is mandatory  to  install  a  three-way  valve (Laddomat  or similar)  or  a 
four-way  mixing  valve  which  to  ensure  that  the  temperature  of  the 
heating  medium  fed  into  the  boiler  from  the  heating  installation  is  at 
least 65°С. 

 

Table 4. TROUBLE-SHOOTING TABLE

 

Cause 

Solution 

Installation damage 

1. Due to unsealed connections 

1.  Install  the  connection  fittings  to  the 
boiler  fittings  –  no  pressure  allowed 
during  work.  Connect  the  hot  water 
outlet  of  the  installation  to  connection 
B.  Connect  the  cold  water  outlet  of  the 
installation  to  connection  A.  Mount  the 
stopcock to drain outlet Y.  

2.  Due  to  accumulation  of  deposits. 
Condensate  and  tar  formation  may  
reduce  the  performance  and  life  of  the 
heating  boiler.  The  temperature  at  the 

2.  It  is mandatory  to  install  a  three-way 
thermostatic  valve  which  will  prevent 
the temperature dropping under 65°C at 
the inlet. 

Содержание BURNiT Magna WBS-A 450

Страница 1: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL EN Model serial Version i0 1 1 Solid fuel boiler WBS A 450 Magna...

Страница 2: ......

Страница 3: ...0 6 INSTALLATION OF THE HEATING BOILER 10 6 1 Requirements 10 6 2 Assembly disassembly of the boiler housing 11 6 3 Check door tightness 12 7 SETUP OF THE HEATING BOILER 13 7 1 Connecting the boiler t...

Страница 4: ...nd correct installation start up and trouble free operation and maintenance of the heating boiler The heating boiler can be used for heating rooms only in the manner described in this manual Take note...

Страница 5: ...structions Customer must undergo boiler operation maintenance training by authorized installer service shop 1 2 2 Instructions to installation user DANGER of intoxication or explosion Toxic gases may...

Страница 6: ...inimum clearances in your country may differ from the ones specified bellow Please consult with your installer The minimum distance from the heating boiler or exhaust gas pipe to objects or walls must...

Страница 7: ...c hot water DHW circuits upon constant temperature indication signals The power of the intake fans can be regulated in a broad range depending on the used type and condition of the fuel and also the c...

Страница 8: ...agram 2 Relation between wood heating value and water content Table 2 Heating value of the most common wood species 4 TRANSPORTATION OF THE BOILER We recommend to transport the heating boiler to the i...

Страница 9: ...the lower part of the boiler are provided transportation openings Important When installing the boiler the wooden pallet onto which the boiler is placed must be removed by unscrewing the bolted conne...

Страница 10: ...ecessary to maintain combustion Boilers must not be placed in inhabitable rooms All boiler rooms must have correctly calculated vent depending on the boiler output The vent must be protected by means...

Страница 11: ...Rightside upper front panel 1 6 Leftside upper front panel 1 7 Rightside upper back panel 1 8 Leftside upper back panel 1 9 Frontside upper left panel 1 10 Frontside upper right panel 1 11 Frontside c...

Страница 12: ...boiler s air distribution body and fixing it to panels 4 and 13 using 5 25mm screws 8 pcs Step 13 Fix the main switchboard 14 to panel 5 using 5 12mm screws 2 pcs Step 14 Fix the blower fans 16 onto t...

Страница 13: ...outlet must be sturdy and properly sealed to avoid gas leak and allow for easy access for cleaning on the inside The inner section of the flue outlet must not be greater than the effective section of...

Страница 14: ...ssel No shut off fittings may be installed between the relief valve expansion vessel and boiler It is mandatory to install a three way valve Laddomat or similar or a four way mixing valve which to ens...

Страница 15: ...sure you are using dry fuel When using fuels with high percent humidity it is possible that the boiler works for a certain period after refilling with reduced power capacity while the fuel dries enou...

Страница 16: ...lectrical mains which complies with the local regulations Warning Be careful when connecting the circulation water pumps the controller is only capable of sending signals voltage for controlling the p...

Страница 17: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL 17 EN Diagram 6...

Страница 18: ...in a closed system Such connections must be performed by a technician service shop authorized for such operations Diagram 7 1 Thermostat 6 Hot water collector 2 Expansion vessel 7 Heating circuit 2 p...

Страница 19: ...LATION and OPERATION MANUAL 19 EN 7 4 2 Connection of BURNiT WBS A Magna boiler in an open system Diagram 8 1 Cold water inlet 5 Return valve 2 Drainage 6 Insulation 3 Air vent line 7 Hot water outlet...

Страница 20: ...the summer 9 BOILER OPERATION 9 1 Loading and ignition the boiler When igniting the boiler for the first time a condensate is formed which is later drained this is not a fault in the boiler The fuel...

Страница 21: ...ts as they obstruct normal heat transfer 2 Dismount the internal protective grates that lay onto the heat exchanging pipes in the combustion chamber of the boiler Clean thoroughly the heat exchanging...

Страница 22: ...period of time at an output lower than 50 When using a circulation pump closed system it is necessary to put a three way thermostatic valve which provides the optimal temperature of the return water T...

Страница 23: ...lue Explanation of buttons Navigation arrow UP PLUS Navigation arrow DOWN MINUS MENU button Enter menu approve settings EXIT button canceling settings Power switch ON OFF Fans CH PUMP Central heating...

Страница 24: ...damping time the controller will switch to the damping mode While in this mode the fan is deactivated and the display shows Damping 10 2 Main page During normal operation in only CH mode the LCD displ...

Страница 25: ...executive element can be switched off and on independently from all the other elements Pressing down MENU starts the fan which remains turned on until the next pressing of the MENU button Pressing do...

Страница 26: ...re It is the difference between the set temperature that is the boiler required temperature and the actual boiler temperature e g if the set temperature has the value of 55 C and the hysteresis is 5 C...

Страница 27: ...m right corner of the main screen 10 9 2 DHW priority WUW Priority Activating the DHW priority will cause the regulator to switch into the DHW priority mode In this mode the WUW pump is activated unti...

Страница 28: ...will show the WUW temperatures screen Set temperature can be changed with the buttons UP and DOWN After few seconds the display will return to its previous state ATTENTION In this mode a non return va...

Страница 29: ...ATTENTION Do not connect the room regulator to external electricity source 10 11 Suspension operation This option allows the user to set the working time of the fans in suspension mode above the set t...

Страница 30: ...s damaged or overheated the fan is disabled Automatic sensor check In case when the CH temperature sensor is missing or damaged an alarm is activated which additional reports the fault on the display...

Страница 31: ...at 63 C and it will remain in the duty mode maintaining the priority temperature of 65 C Fuse The controller has a network protection WT 3 15 A tube fuse ATTENTION Higher current ratings may cause da...

Страница 32: ...nd low chamber resistance Combustion chamber with three way passage of the exhaust gases through the smoke pipes protected by a water mantle Easy cleaning of the fume exhaust tubes thanks to the inspe...

Страница 33: ...igh temperature insulation of mineral wool 4 Fume exhaust tube 5 Water mantle 6 Three pass flue gas flow 7 Combustion chamber 8 Blower fans 9 Metal grate 10 Transportation openings 11 Ash removal door...

Страница 34: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL 34 EN 12 2 Technical parameters...

Страница 35: ...ll load h 5 5 3 5 Operating temperature range Max temperature C 65 85 95 Exhaust gas temperature operation mode C 150 180 Power consumption W 760 Power supply V Hz 230 50 Operating pressure Bar 4 Weig...

Страница 36: ...r recyclable waste containing materials with adverse effect on health and environment According to Directive 2002 96 EC regarding electrical and electronic equipment waste disposal thereof is required...

Страница 37: ...2 TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL...

Страница 38: ...TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL...

Страница 39: ......

Страница 40: ...aria t 359 54 874 555 f 359 54 874 556 e mail ftrade sunsystem bg 13 Chelopeshko Shose Str 1839 Sofia Bulgaria t 359 2 903 97 80 f 359 54 874 556 e mail sales sunsystem bg www sunsystem bg ISO 9001 20...

Отзывы: