- Gas emission in the combustion chamber may result in the formation of tar and
condensate (acids). Therefore, a mixing valve must be installed and it must be
adjusted so that the minimum temperature of the water returning in the boiler is
65°С. This extends the life span of the boiler and its warranty. The operating
temperature of the water in the boiler must be within the 75°С ÷ 85°С range.
- It is not recommended to operate the boiler for a long period of time at an output
lower than 50%.
- When using a circulation pump (closed system) it is necessary to put a three way
thermostatic valve which provides the optimal temperature of the return water
.
- The eco-friendly operation of the boiler is realized at rated output.
- It is recommended to install a buffer tank and pump type group with thermostatic
mixing valve to the boiler. The capacity of the storage tank is 55 L of water per 1 kW
installed boiler power.
- Personal training for maintenance and operation of the boiler is conducted by an
authorized installer.
Failure of fulfilling the installation and operating requirements described in
the manual and the service booklet voids the warranty.