background image

10  

 

 

Commissioning 

Before starting SG36KTL-M, make sure all installation and connections are 
completed and verified. 

Step 1

 

Close the AC circuit breaker.

Step 2

 

Rotate DC switch to “ON” position.

Step 3

 

Suppose there are sufficient sunlight and enough DC power. PV arrays 
initialize and supply DC power to inverter. The LCD display is activated 
when DC voltage exceeds inverter startup votlage. If there is a defect on the 
display, contact Sungrow. 

Button 

Operation

Description

 

Press for less 
than 2 seconds

Move upwards or downwards or scroll among set 
values. Hereinafter, it is referred to as “Press 

”. 

Press for more 
than two 
seconds 

Return to the previous menu or cancel the command. 
Hereinafter, it is referred to as “Press 

ESC

”. 

 

Press for less 
than 2 seconds

Move left or right, or turn pages. Hereinafter, it is 
referred to as “Press 

”. 

Press for more 
than two 
seconds 

Enter into the sub-menu or confirm the command. 
Hereinafter, it is referred to as “Press 

ENTER

”. 

 

Step 4

 

Press 

 to choose country code. 

Confirm the settings by 

Pressing 

ENTER

 

Step 5

 

Select the country code 
according to the installation 
country of the inverter. Each 
country code represents 
corresponding local protective 
parameters that have been 
preset before delivery. Before 
country setting, there is warning 
screen. Operate according to the 
warning information and press 

ENTER.

 

 

Содержание SG36KRL-M

Страница 1: ...uctions of the user manual and other related regulations before installing the equipment Any violation could result in personal death or injury or device damage 1 Unpacking and Inspection Step 1 Remov...

Страница 2: ...nclude quality certificate packing list product test report and quick user manual D Fastener set Six units It is used for fastening backplate onto metal frame E Fix screws 2 M4 16 screws for fix the i...

Страница 3: ...horizontal position Step 2 Mark the positions to drill holes by using the backplate as the template Step 3 Drill 6 holes at the marks you have made If the shape of the metal frame doesn t fit the hole...

Страница 4: ...n the back of the inverter fit perfectly together with the backplate Step 6 After fit the inverter to the backplate fasten the inverter to the backplate with two M4 16 screws Item Description Remark A...

Страница 5: ...er are not live before you start the electrical work Do not turn on the AC side or DC side circuit breaker until all inverter electrical connections have completed 3 1 Open the Connection Cabinet Loos...

Страница 6: ...cables Range 16 50mm2 DC Cables Cross sectional area Cable External diameter Max withstand voltage Max input current for each PV string 4 6mm2 12AWG 10AWG 6 9mm 1100V 12A Second PE Cable The cross se...

Страница 7: ...the correct polarity and that the open circuit voltage does not exceed the inverter input limit 1100V even under the lowest operating temperature Check the positive and negative polarity of the PV ce...

Страница 8: ...There is a second PE terminal on one side of the inverter and it should be grounded Fig 3 1 Second PE terminal The ground connection of this second PE terminal cannot replace the connection of the PE...

Страница 9: ...re provided on the configuration circuit board of the junction box A 120 terminating resistor can be connected between the A and B communication cable through the dip switch 3 7 Completing Installatio...

Страница 10: ...ter it is referred to as Press Press for more than two seconds Return to the previous menu or cancel the command Hereinafter it is referred to as Press ESC Press for less than 2 seconds Move left or r...

Страница 11: ...where LV signifying low voltage grid MV signifying medium voltage grid Press to select grid code and press ENTER to confirm If the country code set as TK a Grid codes page as shown in the right will a...

Страница 12: ...the data logging Press to move the cursor and Press to set the specific time and date Press ENTER to confirm setting Step 9 After configuring all parameters there will be a setting confirmation scree...

Отзывы: