10 Operation of LCD Display
User Manual
84
When the PV inputs are changed, the corresponding “fault” state will
be shown on the main screen. You can perform the PVS Detect Reset
function to re-detect the PV input strings number.
10.13.2 AFD Settings
Main Screen(Press
ENTER
)
→
Menu screen(Press
j
×
4)
→
Advanced Settings(Press
ENTER
)
→
Enter password(Press
ENTER
)
→
Advanced Settings(Press
j
, Press
ENTER
)
→
AFD Settings
A password confirmation screen will occur. Press
h
to
move cursor right and Press
j
to input the password
111111.
AFD Detect represents the arcing faults detection. Press
ENTER
to confirm.
Press
j
to select AFD function settings. Press
ENTER
to
confirm the selection.
When you choose AFD Self-test, the results of the
self-test will show on the LCD screen.
If the self-test result is OK, the inverter will continue to
AC grid connection.