6 Electrical Connection 

 

User Manual 

32  

 

6.1 

 

Connection Conduit Entries 

Conduit entries for all versions are located on the bottom and at the sides of the 
combiner unit.

 

Conduit entries are illustrated below. 

 

Fig. 6-1

 

Conduit entries 

No. 

Description 

DC cable openings with plastic threaded plug. Trade size 1-1/2''

AC cable openings with plastic threaded plug. Trade size 1'' 

Communication cable openings with plastic threaded plug. Trade size 1/2'' 

Make sure the appropriate conduit hub is used in order to maintain required 
spacing between wiring groups and ensure the integrity of the NEMA 4X 
environmental rating. 

 

If inverter is wall-mounted or horizontally-mounted, both the bottom 
and the knockouts on the two side of the inverter can be used for 
conduit entries installation. 

If inverter is ground-mounted, only the knockouts on the two side of 
the inverter can be used for conduit entries installation. 

 

 

 

 

 

 

 

 

Содержание SG30KU

Страница 1: ...SG30KU_SG36KU UEN Ver10 201403 Version 1 0 User Manual SG30KU SG36KU PV Grid Connected Inverter...

Страница 2: ......

Страница 3: ...about other devices at www sungrowpower com or via webpage of device manufacturer Target Group The manual is targeted to technical personnel who is responsible for inverter installation and commissio...

Страница 4: ...ided will result in death or serious injury WARNING indicates a hazard with a medium level of risk which if not avoided could result in death or serious injury CAUTION indicates a hazard with a low le...

Страница 5: ...utility grid and from the PV input before touching any inner live parts Hot surface In order to reduce the risk of burns do not touch the hot surface when the device is running Look over the user man...

Страница 6: ...ription 10 2 3 1 Principle Description 10 2 3 2 Functions Description 11 2 3 3 Derating 12 3 Installation Flow 14 4 Unpacking and Storage 16 4 1 Unpacking and Inspection 16 4 2 Available Versions 17 4...

Страница 7: ...cond Protective Earth Terminal 44 6 6 Communication Connection 45 6 6 1 Communication Overview 45 6 6 2 Communication System 46 6 6 3 RS485 Communication Connection 48 6 6 4 Configurable Dry Contact 5...

Страница 8: ...74 10 6 1 Running Information Records 74 10 6 2 Fault Records 74 10 7 Start and Stop Inverter 75 10 8 Input Parameter Settings Password 75 10 9 System Parameters Setting 76 10 9 1 Time Setting 76 10...

Страница 9: ...der voltage Parameter 88 11 3 Grid Over Under frequency Parameter 88 11 4 P Q Curve 88 11 5 Automatic Power Derating 89 11 5 1 Temperature related Power Derating 89 11 5 2 Input Voltage related Power...

Страница 10: ......

Страница 11: ...nverter and other properties that belong to the operator or a third party Therefore the following safety instructions must be read and always kept in mind prior to any work All detailed work related s...

Страница 12: ...cted System performance loss due to bad ventilation The equipment requires good quality ventilation during operation It is essential to keep the unit upright and nothing covering the heat sink in orde...

Страница 13: ...ind that the inverter is power supplied by dual power source PV arrays and utility grid Before any service work you should obey the following procedures y Disconnect inverter from the utility grid sid...

Страница 14: ...oss of any or all warranty rights There is a risk of inverter damage due to electrostatic discharge The printed circuit boards contain components sensitive to electrostatic discharge Wear a grounding...

Страница 15: ...he inverter assures to detect the arc fault defined by UL1699B The DC ARC Fault circuit is for series arcing faults or a type 1 device The SG30KU and SG36KU inverter s DC Arc Fault Detection AFDI func...

Страница 16: ...PV Power System Item Description Note A PV strings Monocrystalline silicon polycrystalline silicon and thin film without grounding of protection class II B Inverter SG30KU SG36KU C Metering device Mt...

Страница 17: ...ndles The handles are designed for holding the unit when transporting installing or servicing 4 Second PE Terminals Second protective earth terminals as specified in EN 50178 5 Air outlet Exit of hot...

Страница 18: ...interaction interface LCD display panel comprises LED indicators buttons and LCD display screen on the front panel of the inverter y LEDs indicate the working status of the inverter y The current runn...

Страница 19: ...ters to be set Tab 2 2 Description of LED Indicator Status LED Status Description RUN on Inverter is feeding AC power to the utility grid FAULT off RUN off A fault happens or protection function trigg...

Страница 20: ...ts DC power into AC power which will be fed into the utility grid via five core terminals Protective circuits are designed to guarantee inverter safe operation and human safety A DC switch is integrat...

Страница 21: ...ion for optimal operation y Communication interface Standard RS485 interface for connecting other monitoring devices into the PV system is included y Arc Fault Detection If a DC arc fault is detected...

Страница 22: ...ce the power evenly to the maximum limit and keep the output power at nominal value Fig 2 6 PV Overload Derating Power Limit Setting User may allocate output power value of the inverter via LCD contro...

Страница 23: ...ge The deration lower limitation is about 33 If the modules temperature and the inner temperature are both exceed the limit the actual derating power value will be the less one Grid Under voltage Dera...

Страница 24: ...14 3 Installation Flow Fig 3 1 shows the installation flow of inverter for installer Please follow these procedures Fig 3 1 Installation Flow Chart...

Страница 25: ...it if not install immediately Section 4 4 4 Choose the best installation site Section 5 1 5 Moving the inverter to installation site Section 5 2 6 Install the inverter against the chosen wall Section...

Страница 26: ...y Check the inner contents for damage after unpacking y Check the completeness of delivery contents according to the inner packing list If there is visible damage to the packaging or the inner conten...

Страница 27: ...KU S1 VERSION SG30_36KU S11 VERSION SG30_36KU S12 VERSION SG30_36KU S13 VERSION Tab 4 2 Wiring box configurations available Type Available Components SG30_36KU S0 VERSION DC Switch DC Input Fuses SG30...

Страница 28: ...oduct you receive may differ Item Description 1 SUNGROW logo and product type 2 Technical data of inverter 3 Marks of certification institutions of inverter 4 Company name website and origin Tab 4 3 D...

Страница 29: ...ts Seven units It is used for fastening backplate onto concrete wall D Fastener set Seven units It is used for fastening backplate onto metal frame E Fix screws 2 M4 16 screws for fix the inverter to...

Страница 30: ...e unit must be stored in a clean and dry place to protect against dust and moisture y The storage temperature should be always between 30 and 85 And the storage relative humidity can reach 100 y The r...

Страница 31: ...long period of time y Install the unit where is accessible to install electrical connect or service y Do not install the unit on the wall of flammable materials y Do not install the inverter where con...

Страница 32: ...age to the internal device components y Avoid exposing inverter to direct sunlight or rain or snow to extend its service life despite the NEMA 4X protection degree Exposure to the sun may cause additi...

Страница 33: ...produced during running of inverter which may affect your daily life 5 2 Moving Inverter to Installation Site If the inverter is to be installed remove the unit from the packaging and move it to the...

Страница 34: ...don t use the supplied backplate you may drill holes refer to its dimension below Fig 5 1 Dimensions of Backplate unit mm There are two sets of stainless fasteners supplied for attaching the backplate...

Страница 35: ...oid electrical shock or other injury inspect existing electronic or plumbing installations before drilling holes Step 5 Attach the backplate to the wall firmly with the supplied expansion bolt set The...

Страница 36: ...the backplate as the template Step 4 Drill 6 holes at the marks you have made If the shape of the metal frame doesn t fit the holes on the backplate re drill holes on the backplate of appropriate pos...

Страница 37: ...late and then slide down to make sure that the recesses on the back of the inverter fit perfectly together with the backplate Step 8 After fit the inverter to the backplate fasten the inverter to the...

Страница 38: ...he positions to drill holes using the floor bracket as the template Step 5 Drill holes according to the marks made before In order to avoid electrical shock or other injury inspect existing electronic...

Страница 39: ...rter and make sure them fit perfectly together with the mounting ear Fix the bracket with two M4 16 screws Step 3 Install the fixing plates on the bracket Step 4 Assemble the cap onto the inverter for...

Страница 40: ...hanical Installation User Manual 30 L1 Distance from the center of the fans to the floor L2 The shortest distance from the top cover of the inverter to the PV panel You may order the brackets from Sun...

Страница 41: ...ules Improper operation during the wiring process can cause fatal injury to the operator or unrecoverable damage to the inverter Only qualified personnel can perform the wiring work Prior to any elect...

Страница 42: ...d plug Trade size 1 3 Communication cable openings with plastic threaded plug Trade size 1 2 Make sure the appropriate conduit hub is used in order to maintain required spacing between wiring groups a...

Страница 43: ...iner unit layouts are shown below Tab 6 1 Complete list of combiner unit components No Description No Description 1 DC switch 6 AC switch 2 DC SPDs Surge Protection Devices 7 AC SPD 3 Configuration ci...

Страница 44: ...6 Electrical Connection User Manual 34 SG30_36KU S11 VERSION SG30_36KU S12 VERSION SG30_36KU S13 VERSION...

Страница 45: ...h must trigger at a failure current of 300mA or higher 6 3 2 Grid Connection Wiring methods used should be in accordance with the National Electric Code ANSI NFPA 70 and or any prevailing local codes...

Страница 46: ...ction is mandatory Danger to human life due to high voltage existing inside the inverter Make sure that all the DC and AC cables to the inverter are not live before you start the electrical work To pr...

Страница 47: ...he PE conductors to the corresponding terminals on the AC Terminal Block y Observe the pin assignment of AC terminal block If a phase wire is connected to the PE terminal it may permanently destroy th...

Страница 48: ...he inverter will not function properly Before connecting the PV arrays to the inverter make sure that the impedances between the positive terminal of the PV string and Earth and the impedances between...

Страница 49: ...ter should choose independent mode due to different orientation angle between the two PV inputs To make sure maximum DC power can be utilized PV strings connected to individual input area should have...

Страница 50: ...the two PV inputs Prior to connecting the inverter to PV inputs the following electrical specifications must be met simultaneously Total DC Power Limit Open circuit Voltage Limit for Each Input Short...

Страница 51: ...maximum For conductors with finer stranding a suitable UL listed wire ferrule must be used Cross section Area Range Max Withstand Voltage Max input current for each PV string 3 33 16 0mm2 12AWG 6AWG 1...

Страница 52: ...ion not less than 6mm2 10 AWG as the following diagram shown The existing cable connections are not displayed in the below diagram The connection of each four ports in one terminal is equipotential St...

Страница 53: ...sure Where there is only one inverter in the PV power system connect PE cable to the installation ground Where there are multiple inverters in the PV power system connect PE cables of all inverters an...

Страница 54: ...als There are two second PE terminals on the right side of the inverter Users may choose one to connect PE connection Fig 6 5 Second PE Terminals Second PE Connection Fig 6 6 Connection of the Second...

Страница 55: ...s on the configuration circuit board RS485 A B terminal blocks and RJ45 plug in terminals In the case of a need of terminating resistor switch on the 120 terminating resistor switch a terminating resi...

Страница 56: ...ly out Only out Yes For Multiple Inverters Where there is more than one inverter all inverters can be connected to data logging device in daisy chain The first and last inverters in the chain must be...

Страница 57: ...Connection 47 Inverter Communication Connection RS 485 A B bus or RJ 45 Terminating Resistor RS 485 A B bus RJ 45 Inverter 1 Only out Only out Yes Inverter 2 n 1 In and Out In and Out No Inverter n I...

Страница 58: ...o confirm whether they are fastened firmly Step 6 According to the position of the inverter refer to the prior section switch ON or OFF the terminating resistor Step 7 If there is no other connection...

Страница 59: ...to the RS485 out RS485 in terminal on the configuration circuit board Step 6 Pull cables outwards to confirm whether they are fastened firmly Step 7 According to the position of the inverter refer to...

Страница 60: ...cted to the relays must comply with the related requirements AC Requirements DC Requirements Max Voltage 250Vac Max Current 5A Max Voltage 30Vdc Max Current 5A LOCAL STOP dry contacts The dry contacts...

Страница 61: ...ories are correctly connected 6 Cables are routed in safe place or protected against mechanical damage 7 Specification of AC circuit breaker is reasonable 8 Terminals not used underneath the inverter...

Страница 62: ...rrectly during commissioning reset the protective parameters as dictated in 10 11 Protective Parameters Setting There may be faults if otherwise Step 5 Configure grid code on the display Press j to se...

Страница 63: ...TER Step 9 After configuring all parameters there will be a setting confirmation screen Check whether all above mentioned parameters are correct Confirm by Pressing ENTER Cancel by Pressing ESC and re...

Страница 64: ...witch at the sides of the inverter to the OFF position and prevent them from reconnecting 2 Turn off the upstream DC circuit break or cover the PV arrays with opaque materials Please strictly follow t...

Страница 65: ...er 1 Remove the cap and loose the screws from the upper lid 2 Lift up the upper lid slightly release the locking part of the ribbing of the LED screen and remove the lid 3 Disconnect all connection ca...

Страница 66: ...ismantling and Disposing the Inverter User Manual 56 4 Unscrew all connection screws between the electrical cabinet and the combiner box with a suitable spanner and detach the electrical cabinet from...

Страница 67: ...ing the Inverter Users should take the responsibility for the disposal of the inverter Some parts and devices in the inverter such as LCD displayer batteries capacitors may cause environment pollution...

Страница 68: ...C switch to the OFF position 3 Check the correctness of electrical connection of inverter See 6 Electrical Connection 4 Check whether DC input voltage exceeds the inverter start voltage of inverter 5...

Страница 69: ...e circuit and manually remove the fault by pressing ENTER 9 1 4 Troubleshooting of Faults in LCD Screen When faults occur Fault state will be shown on the main screen Press j to view multiple current...

Страница 70: ...le upper limit 1 Check the frequency of the grid 2 If the grid frequency exceeds the permissible range of inverter protective parameters ask utility grid company for solution 3 If the grid frequency i...

Страница 71: ...ecovery 2 If the fault occurs repeatedly contact Sungrow Service Dept 0020 The bus voltage is high 1 Wait a moment for inverter recovery 2 If the fault occurs repeatedly contact Sungrow Service Dept 0...

Страница 72: ...verter recovery 2 If the fault occurs repeatedly contact Sungrow Service Dept 0040 AC or DC overcurrent fault or DC overvoltage fault 1 Wait a moment for inverter recovery 2 If the fault occurs repeat...

Страница 73: ...the grid Contact Sungrow Service Dept 0075 Solar irradiation is not sufficient for inverter operation 1 Wait for higher irradiation 2 If this recurs at medium irradiation check the PV system design a...

Страница 74: ...file Refer to the manuals of the data logging devices Once a month General state of system Visual check any damage or deformation of the inverter Check any abnormal noise during the running of the in...

Страница 75: ...ide of the inverter for active cooling during running operation If the fans are dirty or out of work the inverter may not be cooled down well and its efficiency may accordingly decrease Therefore it i...

Страница 76: ...elease the locking part of four connectors by pressing on the ribbing of the locking hooks and pull outwards 8 Remove fans from the inverter 9 You can clean the dirty fans with soft brush or vacuum cl...

Страница 77: ...cting Dismantling and Disposing the Inverter 5 Check using a multimeter the assignment and conductivity of the fuse A fault occurs to the related fuse if it is non conductive 6 Check the fault fuse by...

Страница 78: ...any problems in operating on the inverter please contact us Service hotline 86 551 65327817 Email service sungrow cn We need the following information to provide you the best assistance y Type of the...

Страница 79: ...ds or increase the set value Hereinafter it is referred to as Press j Press more than two seconds Return to the previous menu or cancel the command Hereinafter it is referred to as Press ESC Press les...

Страница 80: ...10 Operation of LCD Display User Manual 70 10 2 Inverter Menu Structure Fig 10 1 Menu Tree English...

Страница 81: ...e inverter tracks the PV arrays maximum power point MPP and feeds AC power to grid This mode is the normal mode Standby Inverter will enter into Standby mode for insufficient input power In this mode...

Страница 82: ...ng of the fault code please refer to 9 1 4 Troubleshooting of Faults in LCD Screen Tab 10 3 Icon Description Icon Description Inverter is in IAP update process Inverter in power reduction state Fans i...

Страница 83: ...he DC power of each input Indep Paral mode is the PV configuration mode of the two PV inputs indicates the corresponding input is at work P W is inverter output active power S Va is inverter output ap...

Страница 84: ...to select the date you want to view Confirm by pressing ENTER Inverter shows historical running information pages Scroll pages by pressing j Change to the next record by pressing h 10 6 2 Fault Recor...

Страница 85: ...nfirm 10 8 Input Parameter Settings Password The parameter settings are protected by the password If you want to set the inverter s parameters you have to input the correct password 1 Press ENTER to e...

Страница 86: ...h to move the cursor right and Press j to set the correct date and time Confirm settings by pressing ENTER 10 9 2 Energy Deviation Adjustment If the accumulative value of E total in the inverter is di...

Страница 87: ...ssword Press ENTER Sys param Press ENTER Press j 3 Load default Press ENTER A password confirmation screen will occur Press h to move cursor right and Press j to input the password 111111 Press ENTER...

Страница 88: ...ss j to set the appropriate value Confirm by Pressing ENTER Tab 10 4 Specification of Running Parameters Parameter Explanation Default Range Standby time The time from inverter initialization to inver...

Страница 89: ...ctive power can be regulated by the parameter PF on the Run param screen Qt Mode The reactive power can be regulated by the parameter Q Var limits in on the Run param screen Off Mode The PF is limited...

Страница 90: ...e correct country code by Press j and Press ENTER to confirm The description of country code is illustrated below Country Code Full Name Language CA Canada English US United States English Other Count...

Страница 91: ...ppropriate value Confirm settings by Pressing ENTER Tab 10 5 Single stage Protective Parameter Explanation Parameter Explanation Max V grid Grid over voltage value Min V grid Grid under voltage value...

Страница 92: ...frequency protection Max F grid Stage Grid over frequency f Max F time Stage Grid over frequency f tripping time Max F grid Stage Grid over frequency f Max F time Stage Grid over frequency f tripping...

Страница 93: ...igned for PV strings current abnormal condition detection and arcing faults detection that can trigger the protective functions of the inverter 10 13 1 PVS Detect Settings Main Screen Press ENTER Menu...

Страница 94: ...s ENTER Enter password Press ENTER Advanced Settings Press j Press ENTER AFD Settings A password confirmation screen will occur Press h to move cursor right and Press j to input the password 111111 AF...

Страница 95: ...User Manual 10 Operation of LCD Display 85 If a potential problem on the AFD board is detected the self test will result in fault...

Страница 96: ...60A 2 Output Side Data Nominal AC output power 30000W 36000W Max AC output power PF 1 33240W 39800W Max AC output apparent power 33240VA 39800VA Max AC output current 40A 48A Nominal AC voltage 480Va...

Страница 97: ...derating 13 140 113 derating Allowable relative humidity range 0 100 no condensing Cooling method Smart forced air cooling Max operating altitude 4000m 3000m derating 13123ft 9842ft derating Display...

Страница 98: ...V 88 adjustable Adjustable 0 16 to 2 88 V 110 adjustable Normal operation 110 V 120 Adjustable 0 16 to 1 V 120 0 16 11 3 Grid Over Under frequency Parameter Frequency range Hz Clearing time s 60 5 0...

Страница 99: ...ly reduces the amount of power it feeds to the grid 11 5 1 Temperature related Power Derating Operating parameters such as input voltage grid voltage and power available from the photovoltaic arrays c...

Страница 100: ...90 Pout W 11 5 2 Input Voltage related Power Derating The following graph shows the automatic reduction in output power when the input voltage exceeds the threshold value...

Страница 101: ...ing safety warnings and instructions contained in all documents relevant to the product y Installing or operating the product under incorrect safety or protection conditions y Altering the product or...

Страница 102: ...um reliability and enhanced safety Contact Information Should you have any question about this product please contact us Company Sungrow Power Supply Co Ltd Website www sungrowpower com Email info sun...

Отзывы: