User Manual
10 Operation of LCD Display
83
10.12
Communication Parameters Setting
Main Screen(Press
ENTER
)
→
Menu screen(Press
j
×
3)
→
Set-param(Press
ENTER
)
→
Enter password(Press
ENTER
, Press
j
×
3)
→
Com-param(Press
ENTER
)
Press
h
to move cursor right and
Press
j
to set the
appropriate value. Confirm settings by Pressing
ENTER
.
The range of communication address is 1...247.
10.13
Advanced Parameters Setting
Advanced parameters are designed for PV strings current abnormal condition
detection and arcing faults detection that can trigger the protective functions of the
inverter.
10.13.1 PVS Detect Settings
Main Screen(Press
ENTER
)
→
Menu screen(Press
j
×
4)
→
Advanced Settings(Press
ENTER
)
→
Enter password(Press
ENTER
)
→
Advanced Settings(Press
ENTER
)
→
PVS
Detect Settings
A password confirmation screen will occur. Press
h
to
move cursor right and Press
j
to input the password
111111.
PVS Detect represents the PV strings current abnormal
conditions detection. Press
ENTER
to confirm.
Press
j
to select PVS Detect function settings. Press
ENTER
to confirm the selection.