User Manual
85
Tab. 9-8
Description of Active & reactive power parameters
Parameter
Description
Default
Range
Active power limit
Inverter
active
power
limitation
100.0%
0~100%
Speed control
Set the active power
change rate. When it is
set to [ON], user can set
the raise and decline rate.
[OFF]
[OFF]/ [ON]
Active
power
ascend speed
When Rate limit is ON, set
the active power rise rate.
39%/min
8~6000%/min
Active
power
descend speed
When Rate limit is ON, set
the active power decline
rate.
6000%/mi
n
8~6000%/min
Power
increase
enable
Set the power rise rate
when a fault is removed.
When it is ON, the active
power raise rate can be
set.
[OFF]
[OFF]/ [ON]
Power
increase
speed
Set the active power raise
rate.
100%/min
8~6000%/min
Fault slow start
[ON]
[OFF]/ [ON]
Power
increase
speed
10%/min
8~6000%/min
Reactive
adjusting
option
switch
Set the reactive power
regulation function
[ON]
[OFF]/ [ON]
Power factor
Inverter
output
power
factor
+1.000
-1.000~-
0.800/
+0.800~+1.00
0
Reactive
power
limit
Inverter reactive power
limitation
0.0%
0~+100%/ 0~-
100%
Active
setting
keep
[OFF]
[OFF]/ [ON]
Limited power
[ON]
[OFF]/ [ON]
Reactive
setting
keep
[ON]
[OFF]/ [ON]