Fig. 5-5
Dimensions of Terminal (Single-hole terminal)
(Double-hole terminal) Dimensions: a
≤
43mm / 10.5mm
≤
b
≤
12.5mm / c
≤
16mm / d=25.4mm
a b
c
d
Fig. 5-6
Dimensions of Terminal (Double-hole terminal)
5.3.3 PV Input Connection
During the PV string input connection, the DC current of each string
should be gathered together by a combiner box (or other combining
devices) and then connected to the inverter.
DC Cable Requirements
Select DC cables according to the following factors:
The maximum operating temperature of the cable should no less than 90
°
C(+194
°
F).
The current rating of the cable should be selected in accordance with the
maximum short circuit current of the PV arrays connected to the inverter.
The voltage rating of the cable should no less than 1500V.
The Conductor type can be copper wire or aluminum wire.
If the aluminum cable is selected, in order to ensure a reliable electrical
connection, use the the copper and aluminum conversion terminal to avoid
direct contact between the DC copper bar and the aluminum cable.