User Manual
45
Aluminum cable
Conversion terminal
The device may be damaged or operate abnormally if the aluminum
cable is directly connected to the copper bar.
The DC cable must be selected in accordance with the local installation
requirements.
The range of DC cables is: 70mm
2
-185 mm
2
(AWG2/0-350Kcmil).
DC Cable Connection
High voltage inside the inverter!
Make sure all DC and AC cables connected to the inverter are voltage-
free before electrical connection.
Do not connect the AC circuit breaker before electrical connection is
completed.
Step 1
Rotate the DC switch to the “OFF”
position.
Step 2
Strip the insulation layer of the DC cable
to proper length according to the DC cable
specification.
Step 3
Insert the end of the DC cable to the cable socket that matches with the
M10 bolt and tighten it with the proper tool.