SUNFAR C300 81
C300 series of non-sensor current vector-control inverter manual
Fu.10
Output grounding
(Reserved)
1.The output terminal
of inverter grounds
2. The wire is too long
between inverter and motor
and the carrier frequency is
too high.
1. Check the connecting wire
2. Shorten the connection wire
or
reduce the carrier frequency.
Fu.11 Interfere of inverter
Fault action caused by
disturbance of
electromagnetism
Add absorb circuit around
inverter
Fu.12 Inverter
over-loading
1. Load is too heavy.
2. Acceleration time is
too short.
3. Torque boost is too high
or V/F curve is not suitable.
4. Voltage of Power supply is
too low
5. User starts rotating motor
but doesn’t set function of
detecting speed and restart.
1.Reduce the load or replace
with higher capacity inverter.
2. Prolong Acc time.
3. Decrease the torque boost or
adjusting V/F curve.
4. Check Voltage of Power
supply
5. To set function of detect
speed
and restart
Fu.13 Motor
over-loading
1. Load is too heavy.
2. Acceleration time is too
short.
3. The setting of protection
factor is too small
4.Torque boost is too high or
V/F curve is not suitable.
1. Reduce the load
2. Prolong Acc time
3. Increase the over-loading
protection factor of motor
[F4.13]
)
4. Decrease torque boost
voltage and adjust V/F curve.
Fu.14 Inverter
overheat
1. Wind hole is blocked
2. Environmental temperature
is too high
3. Fan is damaged
1. Clear air duct or improve the
air condition.
2. Improve ventilation condition
or decrease carrier frequency.
3. Replace fan.
Fu.15 Reserved
Fu.16
External equipment
failure
There is signal input on the
peripheral. Equipment fault
input terminal of Inverter
Check the signal source and
the
pertinent equipments.
Fu.17
Inverter output
lack phase
Inverter output lack phase
Check the wire of applied motor.
Fu.18 Reserved
Fu.19
Main contactor of
inverter is poor contact
1. Power supply is too low
2. Contactor is damaged.
3. Starting resistance is
damaged.
4. Control circuit is damaged.
1. Check power supply
2. Replace contactor
3. Replace starting
resistance.
4. Contract Us
Fu.20
Current
checking error
1.The current detecting
equipment or circuit is
damaged
2.Auxiliary power supply has
problem
Contract Us