C300 series of non-sensor current vector-control inverter manual
Parameters’
Types
Function Code
Name
Setting range
Minimum
Setting
Manufacture
Setting
Modify
Limit
F0. 13
Acc/Dec initial section of
S curve
10 .0~ 50.0
(
%
)
0.1
20.0
★
F0. 14
Acc/Dec ascend/decline
section of S curve
10.0 ~ 80.0
(
%
)
0.01
60.0
★
F0. 15
Reserved
F0. 16
Carrier wave frequency
1.5~ 12.0 KHz
0.1
6.0*
F0. 17
Carrier wave characteristics
The first part of LED (form right to left):
Reserved
The second part of LED (form right to
left):
0
:
The relation between out current and
Carrier wave is off.
1
:
The relation between out current and
Carrier wave is on.
The third part of LED (form right to left):
0
:
The relation between module temp
and Carrier wave is off.
1
:
The relation between module temp
and Carrier wave is on.
The third part of LED (form right to left):
0
:
The relation between out frequent and
Carrier wave is off.
1
:
The relation between out frequent and
Carrier wave is on.
1 1110
Ba
si
c op
er
a
tio
n
p
a
ra
me
te
r
u
n
it
F0. 18
Parameter write-protect
1
:
Forbid to modify all parameter, except
F0.2 and F0.18
2
:
Forbid to modify all parameter, except
F0.18
1 0
Pr
ima
ry
ap
pli
ed
pa
ra
m
e
te
r u
n
it
F1. 0
Type of V/F Curve
(Parameters [F1.0]
~
[F1.13] is only under the
control mode
that is [F0.0]
=
0,valid.)
0
:
Constant torque curve
1
:
Low-freq. torque curve 1
2
:
Low-freq. torque curve 2
3
:
V/F user-defined curve
1 0
★