SOFTWARE FEATURES
SOFTWARE FEATURES - SOFTWARE FEATURES
1. The control unit closes the cover and checks effective drop in temperature when the set temperature,
as in diagram 1 in previous page, is exceeded.
2. The end run stop system, adjusted on 230V motor
3. Example, if the set temperature is 85°C:
• when this value is exceeded the processor activates the descent relay output and keeps it active for 2
minutes.
• The descent relay relaxes when the set time (2 min) expires, after 30 minutes the system controls a
further jog to check the cover is effectively closed. (the control is given 3 times every 30 minutes)
• The temperature must at least drop below 65°C for the processor to consider the alarm reset. When
below 65°C, the processor considers the alarm reset and activates the relay output for the ascent and
keeps it active for 2 minutes.
• The processor will always control an ascent run ignoring the detected temperature when switched on
in automatic. (Reset)
• The ascent relay relaxes when the set time (2 min) expires, after 30 minutes the system controls a fur-
ther jog to check the cover is effectively open (the control is given 3 times every 30 minutes)
• The processor checks probe status and, if required, closes the cover when end run is reached.