Chapter 2
Hardware Installation and Service
2-7
2.2.2.1
Verify Chassis Fan Tray Upgrade
Caution –
The Sun Netra CT 900 server fan tray upgrade kit (594-4953) must be
installed in the chassis before the Sun Netra CP3220 blade server is installed. This
fan tray upgrade is required to provide adequate cooling and prevent the system
from overheating or shutting down due to an over temperature condition that can
occur with the older fan trays.
●
To verify if the fan tray upgrade is installed on a Sun Netra CT 900 server, log
into the Shelf Manager and issue the following command for fan trays 1,2, and
3:
If "Product Part / Model Number = 371-3033-xx", an upgraded fan tray is
installed. If "Product Part / Model Number" is not 371-3033, an old fan tray is
installed and the upgrade is required. Refer to the
Sun Netra CT 900 Server
Upgrade Guide
(820-3255) for more information.
2.2.2.2
Installing Optional Components
Use the following table to locate your options and installation instructions.
# clia
fruinfo fan_tray 1 | grep "Product Part"
DIMMs
Section 2.3.6.1, “DIMM Requirements” on page 2-19
Section 2.3.6.2, “Installing a DDR2 DIMM” on page 2-21
Compact Flash card
Section 2.3.7, “Installing the Optional Compact Flash Card” on
page 2-24
AMC card
Section 2.3.8, “Installing Optional AMC Cards” on page 2-26
Содержание Sun Netra CP3220
Страница 8: ...viii Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 12: ...xii Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 14: ...xiv Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 34: ...1 16 Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 43: ...Chapter 2 Hardware Installation and Service 2 9 FIGURE 2 1 Installing the Sun Netra CP32x0 ARTM...
Страница 78: ...3 8 Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 94: ...4 16 Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 96: ...5 2 Sun Netra CP3220 Blade Server User s Guide January 2010 5 1 Block Diagram FIGURE 5 1 Block Diagram...
Страница 117: ...Appendix B BIOS Screens B 3 FIGURE B 2 BIOS Main Menu FIGURE B 3 Advanced Configuration Menu...
Страница 119: ...Appendix B BIOS Screens B 5 FIGURE B 6 Super IO Configuration Menu FIGURE B 7 ACPI Settings Menu...
Страница 121: ...Appendix B BIOS Screens B 7 FIGURE B 10 PCI Express Configuration Menu FIGURE B 11 SMBIOS Configuration Menu...
Страница 125: ...Appendix B BIOS Screens B 11 FIGURE B 18 Boot Device Priority Menu FIGURE B 19 Boot Hard Disk Drive Priority Menu...
Страница 127: ...Appendix B BIOS Screens B 13 FIGURE B 22 Chipset Main Menu FIGURE B 23 NorthBridge Chipset Configuration Menu...
Страница 131: ...Appendix B BIOS Screens B 17...
Страница 135: ...Index 4 Sun Netra CP3220 Blade Server User s Guide January 2010...