Appendix A
Physical Characteristics
A-3
A.2.2
PICMG Board Cooling Requirements
TABLE A-1
provides the blade server board cooling requirements. No alarms are
triggered at any of the listed temperatures for the given airflow.
A.2.3
PICMG ARTM Cooling Requirements
TABLE A-2
provides the Pressure Drop vs. Flow Rate for the ARTM.
TABLE A-1
Airflow Requirements
Watts
m
3
/min
CFM
Power Level
25˚C
28˚C
40˚C
55˚C
25˚C
28˚C
40˚C
55˚C
140
0.045
0.045
0.91
0.91
16
16
32
32
205
0.045
0.045
0.91
0.91
16
16
32
32
210
0.045
0.045
0.91
0.91
16
16
32
32
TABLE A-2
ARTM Pressure Drop
Volumetric
Flow Rate
(CFM)
Volumetric
Flow Rate
(m
3
/min)
Pressure Drop
2 DIMMs (Pa)
Pressure Drop
2 DIMMs
(inches of H
2
O)
Pressure Drop
8 DIMMs (Pa)
Pressure Drop
8 DIMMs
(inches of H
2
O)
0
0
0
0
0
0
17
0.48
11.16
0.05
11.16
0.05
24
0.68
18.61
0.08
18.61
0.08
30
0.85
28.53
0.12
31.01
0.13
34
0.96
34.73
0.14
38.45
0.16
42
1.19
48.38
0.2
54.58
0.22
45
1.27
59.05
0.24
64.5
0.26
48
1.36
64.5
0.26
71.95
0.29
51
1.44
71.95
0.29
79.39
0.32
54
1.53
79.39
0.32
86.83
0.35
Содержание Sun Netra CP3220
Страница 8: ...viii Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 12: ...xii Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 14: ...xiv Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 34: ...1 16 Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 43: ...Chapter 2 Hardware Installation and Service 2 9 FIGURE 2 1 Installing the Sun Netra CP32x0 ARTM...
Страница 78: ...3 8 Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 94: ...4 16 Sun Netra CP3220 Blade Server User s Guide January 2010...
Страница 96: ...5 2 Sun Netra CP3220 Blade Server User s Guide January 2010 5 1 Block Diagram FIGURE 5 1 Block Diagram...
Страница 117: ...Appendix B BIOS Screens B 3 FIGURE B 2 BIOS Main Menu FIGURE B 3 Advanced Configuration Menu...
Страница 119: ...Appendix B BIOS Screens B 5 FIGURE B 6 Super IO Configuration Menu FIGURE B 7 ACPI Settings Menu...
Страница 121: ...Appendix B BIOS Screens B 7 FIGURE B 10 PCI Express Configuration Menu FIGURE B 11 SMBIOS Configuration Menu...
Страница 125: ...Appendix B BIOS Screens B 11 FIGURE B 18 Boot Device Priority Menu FIGURE B 19 Boot Hard Disk Drive Priority Menu...
Страница 127: ...Appendix B BIOS Screens B 13 FIGURE B 22 Chipset Main Menu FIGURE B 23 NorthBridge Chipset Configuration Menu...
Страница 131: ...Appendix B BIOS Screens B 17...
Страница 135: ...Index 4 Sun Netra CP3220 Blade Server User s Guide January 2010...