Site Planning for the Sun Blade 8000 Series Systems
13
Environmental Specifications
TABLE 6
Chassis and Component Physical Specifications (Sun Blade 8000 P System)
Dimension or Weight
Specification
Chassis height
24.26 inches (616.21 mm); (14 rack units without clearance)
Chassis depth
28.43 inches (722 mm); includes chassis metal and front bezel
Chassis depth
in rack
27.56 inches (700 mm); distance from the front vertical mounting
rail to rear of the chassis
Chassis width
17.5 inches (444.5 mm); does not include rackmounting ears
Chassis weight
Fully configured system: 420 lb (190.51 kg)
Empty chassis: 75 lb (34 kg)
Subassembly weights:
• Chassis handles: 20 lb (9.07 kg)
• I/O chassis with midplane: 15 lb (6.80 kg)
• Power supply module: 9.25 lb (4.19 kg)
• Server Module: 23 lb (10.43 kg)
• Rear fan module: 3 lb (1.36 kg)
• Network Express Module: 7 lb (3.18 kg)
TABLE 7
Environmental Specifications (Sun Blade 8000 and 8000 P Systems)
Specification
Operating
Nonoperating
Temperature
5 to 35
o
C
(41 to 95
o
F)
noncondensing
-40 to 65
o
C
(-40 to 149
o
F)
noncondensing
Optimum ambient temperature
22
o
C (71.6
o
F)
Relative humidity
10 to 90% RH,
noncondensing,
27
o
C max wet bulb
5 to 93% RH,
noncondensing,
38
o
C max wet bulb
Optimum ambient relative
humidity
45 to 50% RH,
noncondensing
Altitude
0 to 7500 feet (2286 m)
0 to 10,000 feet (3048 m)
Sine Vibration
Z (vertical)-axis: 0.15G
X/Y axis: 0.10G
5 to 500 Hz sine
Z (vertical)-axis: 0.50G
X/Y axis: 0.25G
5 to 500 Hz sine
Shock
3Gs, 11 msec, half sine
(rackmounted enclosure)