14
Sun Blade 8000 Series Site Planning Guide • February 2008
AC Power Requirements
Thermal Design Specifications
TABLE 8
AC Power Requirements (Sun Blade 8000 and 8000 P Systems)
Function
Specification
Voltage
200 to 240 VAC
Frequency
50 to 60 Hz
Current
16A per power supply.
Number of AC inputs
Sun Blade 8000 Chassis - 6
Sun Blade 8000 P Chassis - 4
AC input connection
• Sun Blade 8000 Chassis:
Americas Domestic - NEMA L6-20P to IEC320-C19
(4 m, Sun PN X5044A-Z)
International - IEC309 to IEC320-C19 (4 m, Sun PN X5045A-Z)
Installed in rack with modular power system -
IEC320-C319 to IEC320-C20 (1.5 m, Sun PN X5046A-Z;
2.0 m, Sun PNX5047A-Z)
• Sun Blade 8000 P Chassis:
Americas Domestic - NEMA L6-20P to IEC320-C19
(4 m, Sun PN X5074A-Z)
International - IEC309 to IEC320-C19 (4 m, Sun PN X5075A-Z)
Installed in rack with modular power system -
IEC320-C319 to IEC320-C20 (1.5 m, Sun PN X5076A-Z;
2.0 m, Sun PNX5077A-Z)
TABLE 9
Thermal Design Specifications (Sun Blade 8000 and 8000 P Systems)
Parameter
Specification
Total system volumetric airflow
1500 cfm
Total heat dissipation/HVAC load
30,735 BTU/hr
(9000W N+N configuration for Sun Blade 8000
Modular System or 9000W N+1 configuration for
Sun Blade 8000 P Modular System)
Average temperature rise through
chassis
15
o
C (59
o
F)