Site Planning for the Sun Blade 8000 Series Systems
5
■
Optional power cord for connecting a rackmounted chassis to a modular
power system - IEC320-C19 to IEC320-C20 (5 feet/1.5 meter; Sun part number
X5076A-Z); (6 feet/2 meter; Sun part number X5077A-Z)
If you are using a Sun modular power system (MPS) in the cabinet, refer to the
documentation supplied with the cabinet for the MPS power requirements. If you
are not using an MPS, you must supply a branch circuit with a connector that meets
the requirements of your system.
Power Calculations
You can use the Sun Blade 8000 Series Power Calculators to help you determine the
power requirements of either the Sun Blade 8000 or Sun Blade 8000 P Modular
System. The intent of the Power Calculator is to provide guidance for estimating the
electrical and heat loads per populated chassis for racking and facilities planning
purposes. The power results given by the Power Calculator represent the worst-case,
maximum sustained total server module and chassis power consumption for room
temperatures below 25
o
C. The results represent CPU under maximum possible
stress and 100% utilization.
■
To access the
Sun Blade 8000 Power Calculator
, go to:
http://www.sun.com/servers/blades/8000chassis/calc/index.jsp
■
To access the
Sun Blade 8000 P Power Calculator
, go to:
http://www.sun.com/servers/blades/8000pchassis/calc/index.jsp