USER MANUAL

Models SD-820 to SD-1710 with DDS

Rev 04 – October 2005

10

When sized correctly, the Sullair type SD air dryer with DDS is designed to provide a
specific pressure dewpoint performance (generally -40°F (-40°C)) at worst-case
operating conditions (maximum flow at lowest pressure and highest inlet temperature).
The regeneration purge flow rate required for the dryer is adjusted to achieve that
dewpoint based on those conditions.

For example, for dryers operating at 100 psig (690 kPa) and 100°F (38°C), the purge
flow rate is approximately 15% of the specified maximum inlet flow. Dryers operating
under less severe inlet conditions will introduce a reduced humidity load. The DDS
controls have been factory programmed to monitor the dryer outlet dewpoint so that
regeneration will only begin when low desiccant performance registers.

Sullair SCH high-efficiency prefilters and SCR reverse-flow afterfilters are designed to
remove solids, oil and water condensate from compressed air and other neutral,
compressed gases. These filters provide high flows and low differential pressures.

Solids are filtered out by impact or by the effect of inertia, whereas oil particles and
drops of moisture are filtered out by the effect of coalescence. Contaminants collect in
the bottom of the filter vessel and are drained either automatically or manually.

Filters are provided separately unless the 3-Valve Bypass option has been purchased
(see paragraph 1.2).

3.2 OPERATOR CONTROLS

This adsorption dryer includes a Dewpoint Dependent Switching system that monitors
the dryer outlet dewpoint performance to set the optimum chamber changeover cycle
for desiccant regeneration.

The operator electrical control panel features the following indicators/controls:



Dryer nameplate – the nameplate information identifies your dryer



Three-way selector switch on the left side of the operator control panel:

o

DRYER OFF

o

DRYER ON

o

DDS ON.



Digital operations status display (see figure 2) used for system monitoring:

o

ECONOMY CYCLE

light emitting diode (LED) – lit when DDS is on

Содержание SD-1050 Series

Страница 1: ...el Series SD 820 to 1710 With Dewpoint Dependent Switching This dryer includes equipment options as selected X below DDS OPTION EDP OPTION 3V OPTION This Manual is part number 02250159 760 Applicable...

Страница 2: ...II...

Страница 3: ...ry downtime and minimize work for yourself and wear on the equipment In addition to carefully reading this technical manual in its entirety you must understand your National State and local rules and...

Страница 4: ...USER MANUAL Models SD 820 to SD 1710 with DDS Rev 04 October 2005 iv...

Страница 5: ...T OPERATION 9 3 1 GENERAL OPERATING PRINCIPLES 9 3 2 OPERATORCONTROLS 10 3 3 INITIAL START UP 12 3 4 SHORT TERM SHUT DOWN 13 3 5 SHUT DOWN IN CASE OF A FAULT OR FOR MAINTENANCE 13 3 6 RESTARTING 13 3...

Страница 6: ...USER MANUAL Models SD 820 to SD 1710 with DDS Rev 04 October 2005 vi APPENDIX A DRYER OPERATING SEQUENCE A 1 APPENDIX B DRYER FLOW CAPACITY B 1...

Страница 7: ...ation of Sullair pre and afterfilters refer to paragraph 1 8 which are shipped separately Sullair reserves the right to make changes at any time as may be necessary for increasing safety or efficiency...

Страница 8: ...followed during set up operation and servicing It is of utmost importance that it be read by the assembly technician before installation and start up as well as by the specialist operator in charge I...

Страница 9: ...the purchaser Further the purchaser is to ensure that all personnel completely understand and follow the content of this manual Attention Never make structural changes to the adsorption dryer Only us...

Страница 10: ...er size SCH SCR 910 1315 1315 2120 2120 Controls Printed Circuit Board Operating electrical power 110 115 120 Vac 1 Phase 50 60 Hertz Drying time per tower Standard 5 minutes With EDP Option 2 minutes...

Страница 11: ...thin your company site only the skid of the adsorption dryer may be used for lifting Lifting at any other points on the equipment will void the warranty and damage the equipment 1 7 STORAGE If the ads...

Страница 12: ...USE OF A PREFILTER AND AFTERFILTER CONTINUED Both filters should be equipped with an incident monitor i e differential pressure indicator to advise of premature blockage of the filter elements Elemen...

Страница 13: ...vided see paragraph 1 2 or can be customer furnished If vibration occurs at the installation site the adsorption dryer skid frame must be placed onto vibration dampers 2 2 ELECTRICAL CONNECTION Since...

Страница 14: ...ARGER THAN DRYER EXHAUST Extending purge exhaust piping must not cause excessive back pressure on the chamber being regenerated A pressure reading of 3 psig there is considered too high for the dryer...

Страница 15: ...e EDP dryers Wet air enters the working desiccant chamber it can be either the left or right at the inlet switching valve bottom and is dried as it flows upward through the desiccant bed Dry air exits...

Страница 16: ...remove solids oil and water condensate from compressed air and other neutral compressed gases These filters provide high flows and low differential pressures Solids are filtered out by impact or by th...

Страница 17: ...LED lit at a down arrow indicates that the chamber is in regeneration mode A chamber which is finished regenerating and is standing by will have no LED lit FIGURE 2 STATUS DISPLAY There are two Sulla...

Страница 18: ...lve and observe the pressure build up on the chamber pressure gauge of the adsorption dryer Avoid an abrupt pressure build up as this may damage the dryer Turn the switch to the DRYER ON position NOTE...

Страница 19: ...olation valves up and downstream of dryer Then immediately switch DRYER OFF Danger Dryer will remain pressurized 3 5 SHUT DOWN IN CASE OF A FAULT OR FOR MAINTENANCE Follow this sequence when switching...

Страница 20: ...fails or loses power the DEW POINT display will read either sens or 999 3 7 2 HIGH HUMIDITY ALARM The hygrometer has been programmed to initiate an alarm if the dryer outlet dew point rises above the...

Страница 21: ...ust be conveyed to Sullair This information is given on the nameplate mounted on the control cabinet 4 1 2 WEEKLY CHECK Check the incident monitor on the prefilter A value in the red suggests the elem...

Страница 22: ...te the dewpoint sensor humidity probe NOTE In order to ensure continuous and trouble free operation a maintenance agreement with your authorized Sullair distributor is recommended 4 2 CHANGING THE FIL...

Страница 23: ...input gas e g air Constancy of flow and temperature Whether full service cycling or low demand usage Time in service The following clues will suggest that you examine the desiccant and consider its r...

Страница 24: ...art up 4 4 CHANGING THE PURGE REGENERATION ORIFICE Depressurize the dryer and switch DRYER OFF The regeneration orifice is integrated into pipe fittings that are threaded directly into the top manifol...

Страница 25: ...0159 630 1 02250159 630 1 Gasket 3 inch 02250159 622 4 02250159 622 4 Check Valve 02250130 326 2 02250130 326 2 Purge Valve Purge Valve Kit 02250138 847 2 02250138 847 2 Solenoid Block 02250159 641 1...

Страница 26: ...630 1 Gasket 3 inch 02250159 622 4 02250159 622 4 02250159 622 4 Check Valve 02250130 326 2 02250130 326 2 02250130 326 2 Purge Valve Purge Valve Kit 02250138 847 2 02250138 847 2 02250138 847 2 Sole...

Страница 27: ...ation gas too low Check regeneration orifice for soiling clean if necessary check operation of muffler and depressurization valve replace if necessary Back pressure in regenerating vessel Check if muf...

Страница 28: ...k valve failed Verify springs and bushings on valves Verify seat O ring is not damaged Exhaust valve not fully open Verify operation of pneumatic actuator Verify pilot air to actuator Verify if valve...

Страница 29: ...USER MANUAL Models SD 820 to SD 1710 with DDS Rev 04 October 2005 23 7 DRAWINGS...

Страница 30: ...USER MANUAL Models SD 820 to SD 1710 with DDS Rev 04 October 2005 24...

Страница 31: ...lve positioned for left chamber drying When 3 seconds have passed go to next step 2 DEPRESSURIZE RIGHT CHAMBER Keep EV 1L energized If in DRYER ON mode Energize EV 2R opening right chamber dump exhaus...

Страница 32: ...energized De energize EV 2L close left chamber dump exhaust valve The repressurization timer begins a countdown of 40 seconds Inlet valve remains in current position NOTE The actual timer setting may...

Страница 33: ...1450 1510 1700 1825 1950 SD 1710 1325 1515 1710 1810 1945 2080 2230 NOTE Higher pressures available as an option Consult factory 2 CORRECTION FACTOR FOR INLET TEMPERATURE TEMP DEGREES F 80 90 100 105...

Страница 34: ...USER MANUAL Models SD 820 to SD 1710 with DDS Rev 04 October 2005 B 2...

Страница 35: ......

Страница 36: ...AIR EUROPE S A Zone des Granges BP 82 42602 Montbrison Cedex France Tel 33 4 77 96 84 70 Fax 33 4 77 96 84 99 SULLAIR CORPORATION Subsidiary of Sundstrand Corporation 3700 East Michigan Boulevard Mich...

Отзывы: