SECTION 5
WS CONTROLLER USER INTERFACE MANUAL
31
5.3
WS CONTROLLER FAULTS AND WARNINGS
5.4
MACHINE BEHAVIOR AFTER
A POWER INTERRUPTION
If the compressor was faulted prior to the power
interruption, the controller will resume the FAULTED
condition and display the reason for the fault. Repair
the cause of the fault and press the STOP
pad to reset the controller.
If the compressor was manually stopped prior to the
power interruption, the controller will return to the
manually stopped mode. Press the start button to
manually restart operation.
If the restart timer is greater than zero AND the
controller was in Automatic or Manual mode prior to
the interruption, the controller will resume that mode
after the restart timer expires. No key press is
necessary to restart the compressor.
5.5
INTERNAL BATTERY
The WS Controller employs an internal battery that
maintains the real-time clock and maintains the
integrity of the controller memory records when
power is disconnected from the controller. For best
performance, ensure that the battery is functioning.
If the controller is operated with a drained or dead
battery, the time-of-day records will not work properly
and loss of recent records could occur. If recent
records are lost due to an inoperative battery (or
other reason), the controller will revert to the last
saved versions of settings and records.
The internal battery is located inside the controller I/
O module and will operate for several years without
requiring maintenance. When the battery voltage
gets low, the controller will issue a “Replace Battery”
warning. Perform the following steps to replace the
battery.
Parameter
Type
Sensor
High
Limit
Low
Limit
Comment
Separator dP
Warning
P2-P1+offset
10 psid
offset for aftercooler or dryer
Sump Pressure
Fault
P1
135 psig
5 psig
100 psig machine
150 psig
5 psig
125 psig machine
175 psig
5 psig
150 psig machine
200 psig
5 psig
175 psig machine
165 psig
5 psig
100-140 psig VSD machine
200 psig
5 psig
150-175 psig VSD machine
System Pressure
Fault
P2
125 psig
10 psig
100 psig machine
150 psig
10 psig
125 psig machine
175 psig
10 psig
150 psig machine
200 psig
10 psig
175 psig machine
155 psig
10 psig
100-140 psig VSD machine
200 psig
10 psig
150-175 psig VSD machine
Air End Discharge Temperature
Warning
T1
225 F
0 F
Fault
T1
235/255F
0 F
Time delayed/immediate
Power Supply voltage
Fault
internal
28 V
20 V
VSD Temperature
Warning
158 F