13
1Min
10 Min
5 Min
To change Defrost Duration IN
Coil PRB. Fail parameter, press
the set key.
DEFROST DURATION
IN COIL PRB.FAIL
26
Function: To set Defrost duration IN Coil
probe Failure.
This is the maximum amount of time
allowed for a defrost IN Coil probe fail.
Example
: If this is set to 5 minutes,
then Manual defrost for 5 minutes will
take place during Coil probe fail.
0
1
0
To change Pump Down
parameter, press the set key.
PUMP DOWN
27
Function: To activate Solenoid Valve
Relay.
Use UP/DOWN keys to set desired value.
0 = SV relay will not activate.
1 = SV relay will get activated and will cut
out and cut-in according to set
temperature.
KEYPAD LOCK
28
To change Keypad Lock
parameter, press the set key.
0
1
0
Function: To activate Keypad Lock.
This parameter can lock the keypad so
that tempering is not possible by by-
standers.
0 - deactivates keypad lock.
1 - activates keypad lock.
This parameter can lock the keypad so
that tempering is not possible by-
standers. When locked all parameters
can only be viewed, but not modified.
FACTORY RESET
29
Function: Revert to Factory Parameters.
To change Factory Reset
parameter, press the set key.
Use UP/DOWN keys to set desired value.
1=Revert to factory set parameters.
If we set this parameter 1 and press set
Key then all factory default parameter
will get loaded.
0
1
0
SAVE PROGRAMMING
Use UP/DOWN keys to set desired value.
1> Send To External Key.
2> Exit Programming.
30
Function: To save system programming
parameters.
To change Save Programming
parameter, press the set key.
14
CRC1200
CRC1200
0 Min
45 Min
15 min
Example
: If this parameter is set to 15
minutes, and Defrost frequency
parameter is set at 1 hr. Then ‘1 hr’ after
power is applied to the controller,
defrosting for 15 minutes will take place.
This cycle will repeat every ‘1 hr’.
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
(LCD Message)
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
(LCD Message)
O
0 C
O
15 C
O
4 C
To change Defrost stop
temperature parameter, press
the set key.
DEFROST STOP
TEMPERATURE
24
Function: Final defrost temperature. (Coil
probe).
Use UP/DOWN keys to set desired value.
This is the maximum temperature
allowable at which the defrost process will
stop.
DEFROST STOP
TEMPERATURE
Example
:If this parameter is set to
0
7 C,then if defrosting is
in progress then when
temperature reaches
0
7 C, the defrost process will stop.
0
1
0
To change Power ON Defrost
parameter, press the set key.
POWER ON DEFROST
Function: To activate power ON Defrost.
Use UP/DOWN keys to set desired value.
This parameter will decide to start power
ON defrost or Not.
This also depend on Coil Temperature
0 = No Power Up Defrost
1 = Power Up Defrost
23
25
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set