CRC1200

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

(LCD Message)

QUICK FREEZE SP

Use UP/DOWN keys to set desired value. 
This Parameter will set QUICK Freeze Set 
Point during QUICK Freezing  Defrost will 
not occur.

0

Example 

: If this set to -20 C, and quick 

freeze frequency is set to 1 hr ,then when 

 

it  is  set  to  quick  freeze  mode,  then  the

0

  

Comp. will take -20 C set point for 1 hr.

To change Quick Freeze SP
parameter, press the set key.

05

Function: To set Quick Freeze Set Point.

- 0ºC

5

SP

-20ºC

Range

Min

Max

Fact. Set 

QUICK FREEZE DUR

Use UP/DOWN keys to set desired value. 
This  is  the  maximum  amount  of  time 
allowed  for  Quick  Freeze.  If  set  to  “0”, 
there will be no quick freeze.

Example 

: see QUICK FREEZE SP 

parameter. 

To change Quick Freeze Dur
parameter, press the set key.

06

Function: To set Quick Freeze Duration.

0Hrs

12 Hrs

0 Hrs

Range

Min

Max

Fact. Set 

Use UP/DOWN keys to set desired value.

0

Example  : 

If  setpoint  is  set  at  10 C  and 

0

differential  is  set  at  2 C,  then  when  the 

0

system  reaches  10 C,  the  compressor 
relay will cutout and since the differential is 

0

2 C, the relay will cutin (restart) 

0

0

0

at 12 C (10 C  + 2 C ). 

04

DIFFERENTIAL 

Function: To set the differential for 
compressor restart. 

To change 

DIFFERENTIAL 

parameter, press the set key.

1ºC

20ºC

2ºC

Range

Min

Max

Fact. Set 

08

CRC1200

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

(LCD Message)

ROOM PROBE CAL

07

Function: To set room probe 1 
calibration.

To change the Room Probe Cal 
parameter, press the set key.

Use UP/DOWN keys to set desired value. 

-10ºC

10ºC

0ºC

Range

Min

Max

Fact. Set 

In time it may be possible that the display 
may  be  offset  by  a  degree  or  so.  To 
compensate for this error, you may need 
to add or minus the degrees required to 
achieve the correct temperature. Setting 

o

o

value is from -10 C to + 10 C.

Example :

 The temperature on the 

o

display is 28 C, whereas the actual 

o

temperature is 30 C. You will need to set 
the Calib. Val to 2, which means that 
once out of the programming mode, the 

o

temperature will show 30 C 

o

o

(28 C + 2 C).

Use UP/DOWN keys to set desired value.
This  parameter  is  used  to  protect  the 
compressor  from  restarting  in  a  short 
period of time and can be set between 0 to 
20 minutes.

Example  :

  If  this  parameter  is  set  at  3 

minutes,  the  relay  will  cut  off  at  the  set 
temperature,  but  will  not  restart  for  a 
minimum  of  3  minutes,  even  if  the 
differential  is  achieved  earlier.  This 
parameter is good to protect the life of the 
compressor or even in applications where 
the probe is placed at places where there 
are  sudden  &  short  changes  in 
temperature .

COMP TIME DELAY

08

Function: To set time delay between 
compressors relay restart time.

0 Min

20 Min

3 Min

To change the Comp Time 
Delay parameter, press the set 
key.

Range

Min

Max

Fact. Set 

Содержание CRC 1200

Страница 1: ......

Страница 2: ...ressor function during Room probe failure 5 6 6 8 9 10 7 7 7 8 9 9 9 10 To set Evap Fan operation when compressor is off EVAP Wn COMP OFF 10 To set Evaporator Differential EVAP DIFFERENTIAL To set coi...

Страница 3: ...afety features which include shutting down the system incase of a fault from a pressure control or similar device Computer Connectivity over RS485 and Remote monitoring Optional Single Operation Quick...

Страница 4: ...o change Max Set Point parameter press the set key Use UP DOWN key to set desired value Once set at a particular value this will not allow set points to go above this value and below QUICK FREEZE SPse...

Страница 5: ...nge Min Max Fact Set 08 CRC1200 Sr No Parameter setting method Description of parameters and functions Parameter LCD Message ROOM PROBE CAL 07 Function To set room probe 1 calibration To change the Ro...

Страница 6: ...me for defrost water To change the Drip Time Dur parameter press the set key Use UP DOWN keys to set desired value During this period Compressor Evaporator Fan LSV relay and Heater will stay off so th...

Страница 7: ...ition To change Evap at Door Open parameter press the set key Range Min Max Fact Set Range Min Max Fact Set In time it may be possible that the display may be offset by a degree or so To compensate fo...

Страница 8: ...on To save system programming parameters To change Save Programming parameter press the set key 14 CRC1200 CRC1200 0 Min 45 Min 15 min Example If this parameter is set to 15 minutes and Defrost freque...

Страница 9: ...1 00 and 8 LEDs for indication 16X2 LCD Display For System Status Keypad 9 keys may change Rs485 Connectivity Modbus RTD Protocol Baud Rate 9600 N 8 1 Device ID 1 By Default Hot Key Optional Housing M...

Страница 10: ...use abrasive detergents petrol alcohol or solvents Controller Controller should be installed in a place protected by vibration water and corrosive gasses and where ambient temperature does not exceed...

Страница 11: ...advised of the possibility of such damages No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company A S Controls Pvt Ltd...

Отзывы: