11
DEFROST COMPUTING
21
Function: To set type of computation for
defrost time.
To change Defrost Computing
parameter, press the set key.
0
1
0
Use UP/DOWN keys to set desired
value.
0 = Total of real time.
Example
:
This means that the time
calculation for defrost frequency will be
for the total hours the unit has been
running.
1 - Sum of total compressor operating
times.
This means that for time
calculation, the unit will add the total
time the compressor has been in an ON
mode.
It keeps a record of the hours /-1
Hour incase of a power failure.
Example
: If Defrost frequency is set to 6
hrs. and 3 ½ hrs have passed after unit
has started and power fails, then defrost
cycle will stat after 3 hours when power
resumes.
12
CRC1200
CRC1200
To change Coil Probe Cal.
parameter, press the set key.
COIL PROBE CAL.
17
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
EVAP At DEFROST
18
Function: To set Evap. Fan status during
defrost.
Use UP/DOWN keys to set desired
value.
0 = Evaporator Fan will stay OFF during
defrost.
1 = Evaporator Fan will stay ON during
defrost.
To change Evap At Defrost
parameter, press the set key.
0
1
0
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
0
1
0
EVAP At DOOR OPEN
Use UP/DOWN keys to set desired
value.
0 = ON
1 = OFF
19
Function : Evap fan status during door
open condition.
To change Evap at Door Open
parameter, press the set key.
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
In time it may be possible that the display
may be offset by a degree or so. To
compensate for this error, you may need
to add or minus the degrees required to
achieve the correct temperature. Setting
o
o
value is from -10 C to + 10 C
O
-10 C
O
10 C
O
0 C
Function: To set coil probe calibration.
Use UP/DOWN keys to set desired
value.
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
(LCD Message)
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
(LCD Message)
DEFROST TYPE
Use UP/DOWN keys to set desired
value.
0 = Heater defrost in which case
Compressor is OFF.
1 = Hot gas defrost where Compressor
is ON.
20
Function : To set type of defrost.
To change Defrost Type
parameter, press the set key.
0
1
0
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
DEFROST FREQUENCY
Use UP/DOWN keys to set desired
value.
This is the amount of time between two
defrost cycles.
22
Function: To Set Defrost frequency.
To change Defrost Frequency
parameter, press the set key.
1 Hrs
12 Hrs
4 Hrs
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Use UP/DOWN keys to set desired value.
This is the maximum amount of time
allowed for a defrost. If set to 0, there will
be no defrost cycle.
To change Defrost Duration
parameter, press the set key.
DEFROST DURATION
23
Function:To set Maximum Defrost
duration.