background image

04

CRC1100A

Operation

When  operating  in  the  field  of  refrigeration,  temperature 
controls  is  performed  with  a  positive  differential.  The 
compressor  stops  when  the  Setpoint  temperature  is 
reached  and  restarts  when  the  temperature  reaches 
setpoint plus the differential. 

Two different defrost types can be selected : electrical (the 
compressor is stopped) or at cycle inversion (warm gas; 
the    compressor  keeps  working).  It  is  also  possible  to 
select the interval between defrosts (and the interval count 
type) and a   maximum time (time-out) after which defrost 
is interrupted. The same probe which controls the defrost 
cycle is used to control the evaporator fans. It is possible to 
set the temperature, the delay time after a defrost and the 
relation of fans with the compressor. 

A  series  of  “safety  controls”  (delay  at  start-up,  minimum 
disable time, minimum time between activation) protects 
the compressors from close starts. In case of probe error 
or    temperature  alarm,  the  instrument  signals  the  event 
through acoustic signal and by closing the   relay contact. 
By pressing the mute key, the buzzer is silenced and the 
relay  contact  is  opened.  The  functions  can  be  easily 
customised  by  setting  some  programming  parameters. 
Other parameters allow to suit the instrument to various 
applications.

Subzero Cold Room Controller  CRC-1100A
Introduction

Features :

LCD with backlighting & 7 segment display to display all parameters.
2 NTC probes for cold room temp + evap. coil temperature.

O

O

O

Range: -50 C to + 50 C (1 C res.)
Relay outputs : Comp Evap. Fan + Cond. Fan + Alarm.

Audible alarm.    

HP/LP/OSS trip protection for compressor.      

Auto/Man defrosting facility (Time/Temp based).

Special Software to indicate probable heater fault.

Digital inputs : 2nos  (a) Door Switch  (b) Pressure cutout.

Compressor protection algorithm.

03

CRC1100A

Items included 

NO.

1.

2.

3.

4.

QTY

ITEMS

MOUNTING CLAMP

NTC SENSOR 1.5 METER

3 X 20 SCREW

CATALOG

2

1

2

2

Down & Alarm 

Key

UP & Quick 
Freeze Key

Set Key

Defrost Key

LCD Display

7 Segment 
Display

LED 
Indications

E

C

SET

SZ-CRC-1100A

Get to Know Your Controller

Содержание SZ-CRC-1100A

Страница 1: ...COLD ROOM CONTROLLER SZ CRC 1100A USER MANUAL www pvrcontrols com...

Страница 2: ...e 9 COIL PROBE CALIB L5 Parameter Evap fan status during defrost 9 FAN WHEN DEFROST L6 Parameter Index DESCRIPTION PARAMETER Pg No CRC1100A Evap fan status on door open FAN WITH DOOR L7 Parameter 9 Al...

Страница 3: ...obe error or temperature alarm the instrument signals the event through acoustic signal and by closing the relay contact By pressing the mute key the buzzer is silenced and the relay contact is opened...

Страница 4: ...his mode press QF key for 4 seconds The compressor operates in this mode for time duration set through quick freeze time duration Ct parameter and set pint through Quick freeze set point CS parameter...

Страница 5: ...time parameter press the SET key PROGRAMMING MODE COMP IN PRB FAIL P8 Parameter PROGRAMMING MODE CYC ON TIME ON Time Parameter 07 CRC1100A 08 CRC1100A 3Min 20Min 4Min 9B Function If P8 1 Cyclic OFF t...

Страница 6: ...PROGRAMMING MODE FAN WITH DOOR L7 parameter 0sec 30sec 10sec 18 Function To set Condenser delay to start before comp Example If this parameter set to 10 sec and P6 3 min then condenser will turn ON 1...

Страница 7: ...Parameter 0Min 99Min 30Min 26 Function To set Maximum defrost duration PROGRAMMING MODE MAX DEF DURATION E4 Parameter 11 CRC1100A 12 CRC1100A This is the maximum amount of time allowed for a defrost I...

Страница 8: ...This is most useful to avoid the nuisance alarms when the ambient are high when machine is switched on after long time Technical Data Operating Messages and Icon Status Message Description Parameter H...

Страница 9: ...Hours DEFROST No Defrost because O coil temp 8 C E5 Parameter UNIT ON UNIT ON 4 Hours DEFROST DEFROST 6 Hrs E3 Parameter Setting Manual Defrost Key Pressed Depends on E4 E5 Parameter whichever achiev...

Страница 10: ...ts in materials and workmanship for a period of one year from the date of purchase During the warranty period product determined by us to be defective in form or function will be repaired or at our op...

Страница 11: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Отзывы: