0Min
30MIn
3Min
7
Function : To set time delay
between comp. relay restart
time.
This parameter is used to
protect the compressor from
restarting in a short period of
time. It can be set between
0 to 30Min.
Use UP/DOWN key to set
desired value.
Example :
If this parameter
set at 3 minutes, the relay will
cutoff at set temperature, but
will not restart for a minimum
of 3 minutes, even if the
differential is achieved earlier.
This parameter is good to
protect the life of the
compressor or even in
applications where the probe
is placed at places where
there are sudden and short
changes in temperature like
above a cold room door.
P6 parameter,
press the SET key.
To change the
PROGRAMMING MODE
COMP. TIME DELAY
P6 Parameter
Use UP/DOWN key to set
desired value.
This is time for which the Fan,
Compressor, Condenser,
Heater will stay OFF so that
the defrost water can drip and
drain out. It can be set
between 0 to 20Min.
To change the
P7 parameter,
press the SET key.
0Min
20MIn
1Min
8
Function : To set drip time for
defrost water to drain out.
PROGRAMMING MODE
DRIP TIME
P7 Parameter
0
2
1
9
Function : To set comp. Relay
status on room probe failure.
0 = Compressor relay ON.
'on' minutes
two parameter). (see Sr.
performs a duty cycle of
2 = Compressor relay OFF.
Use UP/DOWN key to set
desired value.
1 = Compressor relay
9A and 9B)
and 'oF' minutes(see next
press the SET key.
To change the
P8 parameter,
2Min
60Min
10Min
9A
Function :
If P8=1 Cyclic ON
time .
Use UP/DOWN key to set
desired value.
This parameter will be
active only when P8 = 1.
This is cyclic ON time of
Comp relay.
To change the
On time parameter,
press the SET key.
PROGRAMMING MODE
COMP IN PRB FAIL
P8 Parameter
PROGRAMMING MODE
CYC. ON TIME
ON Time Parameter
07
CRC1100A
08
CRC1100A
3Min
20Min
4Min
9B
Function :
If P8=1 Cyclic OFF
time .
Use UP/DOWN key to set
desired value.
This is cyclic OFF time of
Comp relay.
This parameter will be
active only when P8 = 1.
Off time parameter,
press the SET key.
To change the
PROGRAMMING MODE
CYC. OFF TIME
OFF Time Parameter
O
-50 C
O
50 C
O
2 C
11
PROGRAMMING MODE
FAN STOP TEMP.
L1 parameter
Function :
Evap. Fan stop coil
temp.
Use UP/DOWN key to set
desired value.
This setting is used to limit
maximum temperature
beyond which the evap. fan
will cutoff
To change the
L1 parameter,
press the SET key.
0Min
30MIn
10Min
10
Function :
To set door open
alarm delay.
Use UP/DOWN key to set
desired value.
Example :
If P9 = 10 minutes, alarm for
door open fault will be
generated if door open fault
present for 10 minutes.
To change the
press the SET key.
P9 parameter,
PROGRAMMING MODE
DOOR ALARM DLY
P9 Parameter
0Min
99Min
1Min
12
Function :
To set time delay
between evap. fan relay
restart time.
Example :
If this is set 3
minutes, the evap. fan relay
will cutoff at the temp. set by
L1 parameter(Fan stop temp.)
but the fan will not come on
for a minimum of 3 minutes if
L4 is achieved earlier.
Use UP/DOWN key to set
desired value.
press the SET key.
To change the
L2 parameter,
PROGRAMMING MODE
FAN TIME DELAY
L2 Parameter
0
1
1
13
compressor is OFF.
Use UP/DOWN key to set
desired value.
0 = Evap. fan OFF when
when compressor will be
Example :
If this parameter is
set to 1, then when comp.
OFF, evap. fan will remain
ON.
1 = Evap. fan will be stay ON
off.
To change the
L3 parameter,
press the SET key.
Function
: Evap. Fan
operation when compressor is
off.
PROGRAMMING MODE
FAN IF COMP OFF
L3 Parameter