22
Kältemittel
R410A
Niederdruckschalter
Auslösung bei
bar
3,0
automatischer Reset bei
bar
6,0
Hochdruckbegrenzer
Auslösung bei
bar
36
Manueller Reset möglich bei
bar
29
Sicherheitsventil
Auslösung bei
bar
40
EN/06.2018/G42 © STULZ GmbH – all rights reserved
cybercool 2 scroll original insTrUcTions
Sensors
The following sensors are installed in the chiller as standard:
for each refrigerant circuit:
- condensation pressure -> for condenser fan control
- suction gas temperature
- suction gas pressure (evaporation pressure)
Chilled water circuit:
- chilled water inlet temperature
- chilled water outlet temperature
- flow sensor
- frost protection thermostat
- intermediate temperature (free cooling)
In units with free cooling exists an additional sensor for the
chilled water temperature which is measured at the free cool-
ing coil outlet.
Air temperatures:
- electric cabinet inside temperature
- compressor housing temperature
- outdoor temperature
to control the expansion valve
}
Refrigerant
low pressure switch
releases at
bar
automatic reset at
bar
High pressure limiter
releases at
bar
manual reset possible at
bar
Safety valve
releases at
bar
Setting of the safety devices