The connection piping should consist of P235 or a similar steel, like the water piping in the chiller, to avoid the
risk of corrosion at the transition to the external piping.
The connection is carried out in the shape of flange connections. We recommend to insulate the pipes of the
external system, if they get in contact with external air, to prevent the introduction of heat from the ambient air
as well as possible.
• Remove the protective hoods from the water pipes.
• Connect the external piping to the chilled water lines of the chiller free of mechanical stress.
Rear view
Water inlet
Water outlet
Chilled water connection
Construction size 7:
Side view
Construction size
7
type
CSO 4602 CSO 5002 CSO 5902
Chilled water connection
DN 100
flange
DN 100
flange
DN 100
flange
Construction size
7
type
CQO 4002 CQO 4602 CQO 5002
Chilled water connection
DN 80
flange
DN 100
flange
DN 100
flange