reheat
EN
Commissioning
The reheats are controlled and monitored by the controller of your A/C unit. No further measures are required for
commissioning.
Installation
The reheats are installed and connected in the A/C unit. The HW reheat is to be connected on site to the external
hot water circuit. The pipelines are to be routed out of the A/C unit. The thread sizes for the connection piping of
the HW reheat are listed in the following table.
Malfunction causes
Alarm: Reheat defect
All reheat alarms are received by the controller and can be requested according to the equipment.
C7000-control system:
no display (display only externally)
C7000 advanced terminal:
indication on the display
C1002:
display: HEA
Cabinet size
Pipe - Ø
mm
Thread size
inch
Temperatures:
Water inlet:
60°C
Water outlet: 40°C
Air inlet:
13°C
Glycol: 0%
1
2
3
4
5
7
16
22
22
22
22
22
1/2
3/4
3/4
3/4
3/4
3/4