FAQ

Xcom-LAN

I don’t have a DHCP server in my net

-

work. What should I do?

By  default,  the  Xcom-LAN  is  in  DHCP/

BOOTP  mode.  You  can  set  a  static  IP  ad

-

dress by accessing the gateway.

1. 

Open your browser

2. 

Enter the default IP address in the ad

-

dress bar (indicated on the back of the 

gateway)

3. 

Enter  the  password  (default  pass

-

word: xcomlan)

4.  Click  on  "Network  Settings"  in  the 

navigation bar

5.  Change IP configuration from "DHCP/

BOOTP" to "Static"

6. 

Set IP address, netmask, gateway and 

DNS server

7. 

Click on "Submit"

8. 

Click on "Save/Restart"

My Xcom-LAN is connected to a company 

network. What should I do?

The  TCP  port  83  may  be  blocked  due 

to  security  settings.  Please  change  the 

 

outbound rule for this port.

My Xcom-LAN is well-configured and con

-

nects to the server, but I can’t register it 

with the given GUID. What should I do?

Check  the  Moxa’s  TX  counter  (see  Moxa 

web interface -> monitor -> Async -> TxCnt). 

If this counter is at zero, the Xcom’s TX line 

is damaged and must be replaced. Please 

contact the Studer Innotec support in  

order to replace your set. 

Xcom-portal

I can’t register my new installation. What 

should I do?

To register a new installation, the installa

-

tion needs to be:

1. 

Configured  correctly  and  in  accord

-

ance with the user manual.

2. 

Have been connected to the server at 

least once.

In order to validate that the installation has 

been  correctly  configured,  the  Xcom  sys

-

tem info (available on the RCC connected to 

the  system)  should  indicate  either  Xcom-

LAN (for an installation with Xcom  -LAN) or 

Xcom-GSM (for an installation with Xcom-

GSM).
To  validate  that  the  connection  with  the 

installation is well established, control that 

the RCC displays the message "Server con

-

nected" when turning on the installation.

There are no datalogger files in the Data

-

logger tab. What should I do?

If the installation is new and the Micro SD 

card of the Xcom-LAN/-GSM is empty, it is 

normal that there are no files on the server.
To activate the automatic recovery of the 

Datalogger:

1. 

The Xcom-LAN/-GSM needs to have a 

software version higher than 1.5.36

2. 

The datalogger needs to be activated 

on  the  Xcom-LAN/-GSM  (the  green 

LED should be continuously lit).

3. 

The Xcom-LAN/-GSM needs to have a 

micro SD card inserted continuously

Содержание Xcom-LAN

Страница 1: ...Remote communication set for Xtender systems Xcom LAN Quickguide Copyright Studer Innotec SA V 1 2 1 4O9E7 ...

Страница 2: ...ance between the Xcom 232i and the Studer system should not exceed 10 meters The distance between the Xcom 232i and the Ethernet gateway should not exceed 0 25 m All cables you need are provided in the set ATTENTION The metallic casing of the Ethernet gateway is connected to the negative battery pole Therefore it is necessary to isolate its casing from any metallic surface Wiring Set the terminati...

Страница 3: ...here is no message the Xcom is not connected to the server Use the FAQ of this Quick guide to see what could have gone wrong 10 11 i n T T Run the Xcom configurator 8 Choose LAN as Xcom mode No other parameters are re quired The gateway is already configured Press Generate to save the parameter settings A window will automatically confirm the successful file generation Take note of your GUID file ...

Страница 4: ...c support in order to replace your set Xcom portal I can t register my new installation What should I do To register a new installation the installa tion needs to be 1 Configured correctly and in accord ance with the user manual 2 Have been connected to the server at least once In order to validate that the installation has been correctly configured the Xcom sys tem info available on the RCC conne...

Страница 5: ...a logger If the Xcom 232i detects an error the signalisation LED is continuously red Blinks Ton 10 Toff 90 MicroSD card full If the Xcom 232i detects that the MicroSD card is full the signalisation LED blinks in red with a cyclical ratio of 10 Green Always on Data logging When the data logging function is activated the signalisa tion LED is green Blinks continuously Ton 20 Toff 80 Communication vi...

Страница 6: ... one year starting from the date of purchase The updates are no longer guaranteed beyond this date and a hardware upgrade may be required Please contact your reseller for any additional information on compatibility SAFETY PRECAUTIONS Generalities Carefully read all safety instructions before pro ceeding with the installation and commissioning of the device Failure to follow these instructions migh...

Отзывы: