Studer Innotec SA
BSP
User manual
V1.3
21
9
BSP SPECIFICATIONS
9.1
T
ECHNICAL DATA
Supply voltage range
7…85 Vdc
Supply current
9 mA @ 12 V
5 mA @ 24 V
3 mA @ 48 V
Input voltage range
7…85 Vdc
Shunt measurement input range
±195 mV
RMS continuous current @ 25 °C
±500 A (BSP 500)
±1200 A (BSP 1200)
Maximum measurable peak current
±1950 A (BSP 500)
±4680 A (BSP 1200)
Voltage measurement accuracy
0.3 %
Current measurement accuracy
0.5 %
Battery capacity
20…20000 Ah
Operating temperature range
-20...55 °C
Packed weight
900 g (BSP 500)
1500 g (BSP 1200)
Displayable values
see table 6.1
Protection degree
IP20
Conformity
LVD 2014/35/EU, EN 62368-1:2014, EMC 2014/30/EU,
EN 61000-6-2:2005, EN 61000-6-4:2007/A1:2011,
RoHS 2011/65/EU
9.2
R
EADOUT RESOLUTIONS
Voltage
±0.01 V
Current (A) and capacity (Ah)
±0.01 (1…10)
±0.1 (10...100)
±1(100...999)
±10 (1000...9999)
±100 (10000...65000)
State of charge
±0.1 %
Temperature
±0.1 °C
Time to go
±1'